Page 271
APPENDIX D: D.1 FACTORY DEFAULT SETTINGS GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-15 Setpoint > Protection Elements > Neutral Current > Neutral IOC Neutral IOC 1 > Neutral IOC 2 > Neutral IOC 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Pickup level Pickup Level30.000.01 A[0.05 : 160.00] Trip time Trip Delay0.000.01 s[0.00 : 900.00] Reset time Reset Delay0.000.01 s [0.00 : 900.00] Snapshot event generation Snapshot...
Page 272
D-16F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.1 FACTORY DEFAULT SETTINGS APPENDIX D: Setpoint > Protection Elements > Ground Current > Ground Directional > Ground Directional 1 > Ground Directional 2 > Ground Directional 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Maximum Torque Angle MTA-451 Deg[-90 : +90] Operation Direction DirectionFORWARDN/A[FORWARD – REVERSE] Polarization typePolarizationVON/A[V0 – IP – V0+IP – V0*IP ]...
Page 273
APPENDIX D: D.1 FACTORY DEFAULT SETTINGS GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-17 Operation timeDelay0.000.01 s[0.00 : 900.00] Deviation time to instantaneous Time to inst0.000.01 s[0.00 : 900.00] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements > Sensitive Gr ound Current > Sensitive Ground Directional > Sensitive Ground Directional 1 > Sensitive Ground Directional 2 > Sensitive Ground Directional 3 Setting DescriptionNameDefault...
Page 274
D-18F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.1 FACTORY DEFAULT SETTINGS APPENDIX D: Function permissionFunctionDISABLEDN/A[DISABLED – ENABLED] Pickup Level Pickup Level101 V[3 : 300] Trip time Trip Delay10.000.01 s[0.00 : 900.00] Reset time Reset Delay0.000.01 s[0.00 : 900.00] Operation logic LogicANY PHASEN/A[ANY PHASE – TWO PHASES – ALL PHASES] Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elem ents > Voltage Elements > >Neutral OV High > Neutral...
Page 275
APPENDIX D: D.1 FACTORY DEFAULT SETTINGS GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-19 Curve shapeCurveDEFINITE TIMEN/A[DEFINITE TIME – INVERSE TIME] Time Dial Delay10.000.01 s[0.00 : 900.00] Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements > Power > Forward Power Forward Power 1 > Forward Power 2 > Forward Power 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Block from offline...
Page 276
D-20F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.1 FACTORY DEFAULT SETTINGS APPENDIX D: Pickup Delay for OvercurrentOC Pickup Delay0,20.01 s[0.00 : 600.00] Pickup Level for operating Power Power Pickup0,010.01 W[0.01 : 4.50] Max torque angle MTA01 Deg[0 : 360] Pickup Delay for Operating Power Power Pickup Delay0,20.01 s[0.00 : 600.00] Curve shape CurveDEFINITE TIMEN/A[DEFINITE TIME - INVERSE TIME - USER C URVE A - USER CURVE B - USER CURVE C - USER CURVE D] MultiplierMultiplier10.01 s[0.02 :...
Page 277
APPENDIX D: D.1 FACTORY DEFAULT SETTINGS GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-21 Setpoint > Control Elements > Synchrocheck Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Dead bus voltage level Dead Bus Level10.000.01 V[0.00 : 300.00] Live bus voltage level Live Bus Level50.000.01 V[0.00 : 300.00] Dead line voltage level Dead Line Level10.000.01 V[0.00 : 300.00] Live line voltage level Live Line Level50.000.01 V[0.00 :...
Page 278
D-22F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.1 FACTORY DEFAULT SETTINGS APPENDIX D: Lowset pickup levelLowset Pickup2.000.01 A[0.05 : 160.00] Internal arc pickup level Internal Arc Pickup0.100.01 A[0.05 : 160.00] Internal arc time delay Internal Arc Delay10.000.01 s[0.00 : 900.00] Retrip time delay Supervision Delay10.000.01 s[0.00 : 900.00] Hiset time delay HiSet Delay10.000.01 s[0.00 : 900.00] Lowset time delay LowSet Delay10.000.01 s[0.00 : 900.00] Second stage time delay 2nd Step...
Page 279
APPENDIX D: D.1 FACTORY DEFAULT SETTINGS GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-23 Multiplier factor for the pulse counterCntPulses Factor X1.0000.00 1[0.000 : 65000.000] Overflow value for the pulse counter CntPulses Overflow X655351[0 : 1000000] Board selection for the pulse counter CntPulses Board Origin XF N/A[F,G,H,I] Input index inside the selected board CntPulses Input Origin X1 1[1 : 32] Note: X is the pulse counter index, up to 8. SETPOINT > CONTROL ELEMENTS > ANALOG COMPARATORS SETTING...
Page 280
D-24F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.1 FACTORY DEFAULT SETTINGS APPENDIX D: Angle (Size of the blocking region)Angle51 Deg[5 : 50] Trip T ime Pickup Delay0.0000.00 1 s[0.000 : 65.535] Reset T ime Reset Delay0.0000.00 1 s[0.000 : 65.535] Snapshot Events Generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] SETPOINT > CONTROL ELEMENTS > MAX. NUMBERS OF STARTS SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER VALUE Function PermissionFunctionDISABLEDN/A[DISABLED- ENABLED] Motor Full Load...