Page 271

APPENDIX D:  D.1 FACTORY DEFAULT SETTINGS
GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-15
Setpoint > Protection Elements > Neutral Current > Neutral IOC
Neutral IOC 1 > Neutral IOC 2 > Neutral IOC 3
Setting DescriptionNameDefault ValueStepRangeUser 
Value
Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
Pickup level Pickup Level30.000.01 
A[0.05 : 160.00]
Trip time Trip Delay0.000.01 
s[0.00 : 900.00]
Reset time Reset Delay0.000.01 
s
[0.00 : 900.00]
Snapshot event generation Snapshot...

Page 272

D-16F650 DIGITAL BAY CONTROLLER GEK-113000-AF
D.1 FACTORY DEFAULT SETTINGS APPENDIX D:  
Setpoint > Protection Elements > Ground Current > Ground Directional >
Ground Directional 1 > Ground Directional 2 > Ground Directional 3
Setting DescriptionNameDefault ValueStepRangeUser 
Value
Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
Maximum Torque Angle MTA-451 
Deg[-90 : +90]
Operation Direction DirectionFORWARDN/A[FORWARD – REVERSE]
Polarization typePolarizationVON/A[V0 – IP – V0+IP – V0*IP ]...

Page 273

APPENDIX D:  D.1 FACTORY DEFAULT SETTINGS
GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-17
Operation timeDelay0.000.01 
s[0.00 : 900.00]
Deviation time to instantaneous Time to inst0.000.01 
s[0.00 : 900.00]
Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
Setpoint > Protection Elements > Sensitive Gr ound Current > Sensitive Ground Directional >
Sensitive Ground Directional 1 > Sensitive Ground Directional 2 > Sensitive Ground Directional 3
Setting DescriptionNameDefault...

Page 274

D-18F650 DIGITAL BAY CONTROLLER GEK-113000-AF
D.1 FACTORY DEFAULT SETTINGS APPENDIX D:  
Function permissionFunctionDISABLEDN/A[DISABLED – ENABLED]
Pickup Level Pickup Level101 V[3 : 300]
Trip time Trip Delay10.000.01 
s[0.00 : 900.00]
Reset time Reset Delay0.000.01 
s[0.00 : 900.00]
Operation logic LogicANY PHASEN/A[ANY PHASE – TWO PHASES 
– ALL PHASES]
Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
Setpoint > Protection Elem ents > Voltage Elements >
>Neutral OV High > Neutral...

Page 275

APPENDIX D:  D.1 FACTORY DEFAULT SETTINGS
GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-19
Curve shapeCurveDEFINITE TIMEN/A[DEFINITE TIME – INVERSE 
TIME]
Time Dial Delay10.000.01 
s[0.00 : 900.00]
Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
Setpoint > Protection Elements > Power > Forward Power
Forward Power 1 > Forward Power 2 > Forward Power 3
Setting DescriptionNameDefault ValueStepRangeUser 
Value
Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
Block from offline...

Page 276

D-20F650 DIGITAL BAY CONTROLLER GEK-113000-AF
D.1 FACTORY DEFAULT SETTINGS APPENDIX D:  
Pickup Delay for OvercurrentOC Pickup Delay0,20.01 
s[0.00 : 600.00]
Pickup Level for operating Power Power Pickup0,010.01 
W[0.01 : 4.50]
Max torque angle MTA01 
Deg[0 : 360]
Pickup Delay for Operating Power Power Pickup Delay0,20.01 
s[0.00 : 600.00]
Curve shape CurveDEFINITE TIMEN/A[DEFINITE TIME - INVERSE 
TIME - USER C

URVE A - 
USER CURVE B - USER 
CURVE C - USER CURVE D]
MultiplierMultiplier10.01 
s[0.02 :...

Page 277

APPENDIX D:  D.1 FACTORY DEFAULT SETTINGS
GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-21
Setpoint > Control Elements > Synchrocheck
Setting DescriptionNameDefault ValueStepRangeUser 
Value
Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
Dead bus voltage level Dead Bus Level10.000.01 
V[0.00 : 300.00]
Live bus voltage level Live Bus Level50.000.01 
V[0.00 : 300.00]
Dead line voltage level Dead Line Level10.000.01 
V[0.00 : 300.00]
Live line voltage level Live Line Level50.000.01 
V[0.00 :...

Page 278

D-22F650 DIGITAL BAY CONTROLLER GEK-113000-AF
D.1 FACTORY DEFAULT SETTINGS APPENDIX D:  
Lowset pickup levelLowset Pickup2.000.01 
A[0.05 : 160.00]
Internal arc pickup level Internal Arc Pickup0.100.01 
A[0.05 : 160.00]
Internal arc time delay Internal Arc Delay10.000.01 
s[0.00 : 900.00]
Retrip time delay Supervision Delay10.000.01 
s[0.00 : 900.00]
Hiset time delay HiSet Delay10.000.01 
s[0.00 : 900.00]
Lowset time delay LowSet Delay10.000.01 
s[0.00 : 900.00]
Second stage time delay 2nd Step...

Page 279

APPENDIX D:  D.1 FACTORY DEFAULT SETTINGS
GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-23
Multiplier factor for the pulse counterCntPulses Factor X1.0000.00
1[0.000 : 65000.000]
Overflow value for the pulse counter CntPulses Overflow X655351[0 : 1000000]
Board selection for the pulse counter CntPulses Board 
Origin XF
N/A[F,G,H,I]
Input index inside the selected board CntPulses Input Origin 
X1
1[1 : 32]
Note: X is the pulse counter index, up to 8. 
SETPOINT > CONTROL ELEMENTS > ANALOG COMPARATORS
SETTING...

Page 280

D-24F650 DIGITAL BAY CONTROLLER GEK-113000-AF
D.1 FACTORY DEFAULT SETTINGS APPENDIX D:  
Angle (Size of the blocking region)Angle51 
Deg[5 : 50]
Trip T ime Pickup Delay0.0000.00
1 s[0.000 : 65.535]
Reset T ime Reset Delay0.0000.00
1 s[0.000 : 65.535]
Snapshot Events Generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > MAX. NUMBERS OF STARTS
SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER 
VALUE
Function PermissionFunctionDISABLEDN/A[DISABLED- ENABLED]
Motor Full Load...