Chapter 1      Removal and Replacement Procedures
  Removing and Installing the DC-Input Power Supplies
Figure 1-29 DC Power Cable Lug
CautionUse both hands to install and remove the power supplies. Each DC-input power supply weighs 32 pounds 
(14.5 kg). 
Step 5Grasp the power supply handle with one hand, and place your other hand underneath the power supply. 
Slide the power supply into the power supply bay. Make sure that the power supply...

Page 252

1-44
Catalyst 6500 Series Switches Installation Guide
OL-5781-08
Chapter 1      Removal and Replacement Procedures
  Removing and Installing the DC-Input Power Supplies
Step 8Remove the two screws that secure the left inner terminal block cover. Lift up on the cover to detach the 
cover tab from the slot in the power supply. Set the cover and the screws aside.
Step 9Remove the one screw that secures the right inner terminal block cover. Lift up on the cover to detach 
the cover tab from the slot in the...

Page 253

1-45
Catalyst 6500 Series Switches Installation Guide
OL-5781-08
Chapter 1      Removal and Replacement Procedures
  Removing and Installing the DC-Input Power Supplies
Figure 1-31 DC-Input Wire Connections for 2700 W Operation (Left-Side Power Bay)
Step 14
Wrap the large perforated flaps of the insulators around each pair of source DC cables, inserting each 
locking tab into the rear of the slot. Pull the tab until the cover is secured around the power cabling trim, 
and discard excess tab plastic....

Page 254

1-46
Catalyst 6500 Series Switches Installation Guide
OL-5781-08
Chapter 1      Removal and Replacement Procedures
  Removing and Installing the DC-Input Power Supplies
Step 19Turn the power switch to the on (|) position on the power supply. Turning on the power switch also 
engages a pawl that locks the power supply in the chassis.
Step 20Verify the power supply operation by ensuring that the power supply front panel LEDs are in the 
following states:
INPUT OK 1 LED—If you have source DC cables attached...

Page 255

1-47
Catalyst 6500 Series Switches Installation Guide
OL-5781-08
Chapter 1      Removal and Replacement Procedures
  Removing and Installing the DC-Input Power Supplies
To install a 4000 W DC-input power supply and wire it for 2700 W operation in the right power supply 
bay (POWER 2), follow these steps:
Step 1Ensure that the system (earth) ground connection has been made. 
For ground connection installation instructions, see the “Establishing the System Ground” section on 
page 1-52.
Step 2Remove the...

Page 256

1-48
Catalyst 6500 Series Switches Installation Guide
OL-5781-08
Chapter 1      Removal and Replacement Procedures
  Removing and Installing the DC-Input Power Supplies
Figure 1-33 Handling a 4000 W DC-Input Power Supply 
Step 6
Tighten the power supply captive installation screw.
Step 7Remove the two screws that secure the outer terminal block cover. Lift the cover up to detach the cover 
tabs from the slots in the power supply. Set the cover and the screws aside.
Step 8Remove the two screws that secure...

Page 257

1-49
Catalyst 6500 Series Switches Installation Guide
OL-5781-08
Chapter 1      Removal and Replacement Procedures
  Removing and Installing the DC-Input Power Supplies
Step 13From the right side of the power supply, connect the power supply ground cable and the source DC cables 
to the DC-input wires to the terminal block (Figure 1-34) in this order:
1.Ground cable lug to the ground terminal posts
2.Negative (–) source DC cables to any two pairs of (–) terminal posts (VE-1 and VE-2, VE-1 and 
VE-3, or...

Page 258

1-50
Catalyst 6500 Series Switches Installation Guide
OL-5781-08
Chapter 1      Removal and Replacement Procedures
  Removing and Installing the DC-Input Power Supplies
Step 18After you confirm that all installation steps are completed correctly, remove any safety flags, lockout 
devices, or adhesive tape from the source DC circuit breakers, and energize the input circuits to the 
power supplies. 
Step 19Turn the power switch to the on (|) position on the power supply. Turning on the power switch also...

Page 259

1-51
Catalyst 6500 Series Switches Installation Guide
OL-5781-08
Chapter 1      Removal and Replacement Procedures
  Removing and Installing the DC-Input Power Supplies
To install a 4000 W DC-input power supply and wire it for 4000 W operation in the left power bay 
(POWER 1), follow these steps:
Step 1Ensure that the system (earth) ground connection has been made. 
For ground connection installation instructions, see the “Establishing the System Ground” section on 
page 1-52.
Step 2Remove the power...

Page 260

1-52
Catalyst 6500 Series Switches Installation Guide
OL-5781-08
Chapter 1      Removal and Replacement Procedures
  Removing and Installing the DC-Input Power Supplies
Figure 1-36 Handling a 4000 W DC-Input Power Supply 
Step 6
Tighten the power supply captive installation screw. 
Step 7Remove the two screws that secure the outer terminal block cover. Lift the cover up to detach the cover 
tabs from the slots in the power supply. Set the cover and the screws aside. (See Figure 1-26.)
Step 8Remove the...