Page 41
NOTES : 1. 2. 3. 4. 5.115V AC, 60 Hz, 15 AMP OUTLETS (HUBBELL 5262 OR EQUIVALENT) MUST BE LOCATED WITHIN 4 FEET OF SYSTEM CABINETS. MULTIPLE CABINET SYSTEMS REQUIRE TWO QUAD OUTLETS, SINGLE CABINET SYSTEMS REQUIRE ONE QUAD OUTLET. ALLOW AT LEAST 24 INCHES OF SPACE IN FRONT OF CABINETS. TABLE MUST BE ABLE TO SUPPORT 250 POUNDS. BACKBOARD IS 3/4 INCHES THICK BY 48 INCHES WIDE BY 96 INCHES LONG (FOR MAXIMUM SYSTEM). SYSTEM 25 CABINETS AND BACKBOARD MUST BE LOCATED IN A RESTRICTED ACCESS AREA. RESTRICTED...
Page 42
INSTALLATION AC Power All cabinets and any locally-connected System 25 peripheral equipment (System Administration Terminal [SAT], Station Message Detail Recording [SMDR] device, Digital Tape Unit [DTU]), and Customer Service Unit (CSU) used for DS1 connections must be plugged into the common ac power outlet. This outlet must have an associated ground block connected to an approved building ground, using #6 AWG copper wire. (This ground block is the system’s single-point ground.) A 1-cabinet system...
Page 43
INSTALLATION 3. 4. metal frame of the building, a concrete encased ground, or a ground ring. If these grounds are not available, the water pipe ground can be supplemented by one of the following types of grounds. l Metal underground gas piping system—an electrically continuous metal underground gas piping system that is uninterrupted with insulating sections or joints and without an outer nonconductive coating. l Other local metal underground systems or structures—local underground structures such as...
Page 44
INSTALLATION l A single-point ground (SPG) system in which the green wire ground (system ground) and the telephone company ground are connected to approved building ground. l The coupled bonding conductor must be connected between the telephone company ground at the building entrance and System 25’s SPG. l Surge protection on the ac power to System 25. For greater than 99 percent of all lightning strikes, the protection outlined above will do the job.However, there are a few locations where the described...
Page 45
INSTALLATION Secondary Protection External secondary protection,located at the trunk access area of the System 25 cross-connect field, is required for all trunks and off-premises lines. Refer to Table 2-B for approved trunk protectors. FROM AC LOAD CENTER (TWO SEPARATELY FUSED 15 AMP CIRCUITS) SINGLE POINT GROUND HGROUNDI LOAD CENTER II (GREEN) (#14 AWG) I /TO CABINET NO. 1 GROUND BAR MOUNTED ‘GROUND BLOCK (MAX. ON 4“ BOX (SQUARE DLENGTH =20 FT.) PK9GTA OR APPROVED EQUIVALENT)4“ BOX (RACO 230 OR...
Page 46
INSTALLATION Building Wiring Building (station) wiring (must be 24 AWG or heavier) from voice and data terminals to the equipment location should already be in place. System 25 wiring requires that 4-pair circuits be distributed from the equipment location to each station’s wall jack.The SIP hardware (Figures 2-2 through 2-6), designed specifically for this purpose, is furnished with each system. Except in extraordinary circumstances, this cross-connect hardware must be used. In unusual circumstances...
Page 47
INSTALLATION INSTALL SYSTEM CABINETS Before beginning the cabinet installation, position the cabinet table within 2 feet of the ac power receptacle. Make sure that the cabinets are easily accessible from both the front and the back. Position Cabinet(s) Caution:A fully-equipped cabinet weighs 80 pounds. 1. 2. 3. 4. Check Unscrew and remove the upper rear panel of each unscrew the lower part with the 12 connectors. cabinet. Do not Near the center of the backplane, note an address plug in one of the...
Page 48
INSTALLATION Table 2-B. Circuit Packs, Their Functions, and Protectors Approved SecondaryCircuit PackFunction Wiring Protector N/AZTN78Supports single-line voice terminals. (Must not be used on out-of-building circuits, ) SCP-1 or 79ATN742Supports off-premises, out-of- building, and bridged single-line voice terminals. lTW/LlNX343* I ROBZTN79Supports the 7300H Series voice terminals used with a MERLIN® system. (Requires local (set) power for distances beyond 1000 feet.) ITWILINX343* lROBTN735Supports MET...
Page 49
INSTALLATION Two fans are located on the left-hand front side of each cabinet. The cabinet’s power supply is located behind the fans; to the right of the power supply are up to 12 CPs in individual slots.Each CP is identified by a label on the front. See Figure 2-10. 1.Remove the front cover of each cabinet. 2. Note any obviously bent or otherwise damaged circuit packs. 3. Check the CPs against the customer order. In case of irregularities or damage, follow established notification procedures. Danger:The...