Page 121
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaPOWER AND GROUNDING Figure 16 shows a typical power and grounding layout for a remotely located EPN cabinet. A ground wire must be connected from the cabinet ground block of both the PPN and EPN cabinets to an approved ground. (Also see ``Grounding, later in this section). OR EQUIVALENT UNIT REAR . .. DISTRIBUTION RECEPTACLE, 60-HZ 50-AMP 115-VOLT 60-HZ 30-AMP NEMA 5-50 PROVIDED POWER PANEL CUSTOMERPOWER. .. CORD 10 FEET6 AWG 60-HZ 50-AMP...
Page 122
POWER AND GROUNDINGaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa Single-Carrier Cabinet System Each cabinet requires a separate power outlet, as shown in Figures 17 and 18. These outlets must not be shared with other equipment, must not be under switch control, and should be located outside the cross-connect field area, if possible. Any available power source can be used as long as the phase or leg provides 120-volt AC at the required drain. The Manager I terminal or G3r-MT should be connected to...
Page 123
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaPOWER AND GROUNDING 20-AMP CABINET B CABINET A CABINET C CABINET D CABINET A OR MANAGER I TERMINAL MANAGER I 20-AMP20-AMPCABINET A OR CABINET A 15-AMPCABINET B 2 CABINET SYSTEM 15-AMPCABINET B 4 CABINET SYSTEM 20-AMP 15-AMP 15-AMPCABINET BCABINET C CABINET D TERMINAL EXPANSION PORT NETWORK (EPN)PROCESSOR PORT NETWORK (PPN) FIGURE 18. AC Power Requirements for a Single-Carrier System (Remotely Located EPN) 119
Page 124
POWER AND GROUNDINGaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa Figure 19 depicts a typical power and grounding layout for a single-carrier system with the PPN and EPN cabinets colocated. A ground wire from the ground block on the bottom cabinet of the EPN connects to the single-point ground block on the bottom cabinet of the PPN. A 6-AWG ground wire connects the single-point ground block to an approved ground. (Also see ``Ground- ing, later in this section). 6 AWG GROUND APPROVED POWER CORD 10...
Page 125
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaPOWER AND GROUNDING Figure 20 shows a typical power and grounding arrangement for a system with the EPN remotely located. A ground wire must be connected from the cabinet ground block of both the PPN and EPN to an approved ground. (Also see ``Grounding, later in this section). 6 AWG GROUND APPROVED POWER CORD 10 FEETREAR 115-VOLT 60-HZ TERMINAL NOTE: TO APPROVED GROUND LOCATED NEAREST THE TELEPHONE COMPANY OWNED PROTECTOR GROUND BLOCK AT THE...
Page 126
POWER AND GROUNDINGaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa DC Power Requirements Multi-Carrier Cabinet System A DC power plant may be used to power the multi-carrier system cabinets. Figure 21 shows a typical power and grounding layout for a DC-powered multi-carrier cabinet. GROUND DISCHARGE BARAPPROVED GROUND (SEE NOTE) NOTE: 10 AWG COUPLED BONDING CONDUCTOR (CBC) REAR -48 V BATTERY PLANT REAR CABINET GROUND BLOCK SYSTEM SINGLE POINT GROUND UNIT DISTRIBUTIONFRONT EXPANSION PORT -48 V-48 V...
Page 127
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaPOWER AND GROUNDING Table Q provides the requirements for input DC power. TABLE Q. -48 Volt DC Input Power Requirements bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Parameter Requirements bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Static Voltage -48 V DC nominal, -42.5 V DC minimum, -52.5 V DC maximum (measured at input to system cabinet)...
Page 128
POWER AND GROUNDINGaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa TABLE Q (continued). -48 Volt DC Input Power Requirements bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Parameter Requirements bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Redundancy Redundancy of the battery chargers/rectifiers should be considered. This would also provide the additional current necessary to recharge the batteries after...
Page 129
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaPOWER AND GROUNDING Figures 17 and 18 provide a power and grounding layout for mixed AC-/DC-powered multi-carrier cabinet configurations. GROUND BARDISCHARGE REAR TELEPHONE COMPANY OWNED PROTECTOR GROUND BLOCK -48 V BATTERY PLANT CABINET GROUND BLOCK CABINET APPROVED GROUND (SEE NOTE)6 AWG 10 AWG COUPLED BONDING CONDUCTOR (CBC) GROUND BLOCK USE APPROVED GROUND LOCATED NEAREST THE -48 V-48 V RTN PROVIDED POWER PANEL OR EQUIVALENT CUSTOMERUNIT...
Page 130
POWER AND GROUNDINGaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa USE APPROVED GROUND LOCATED NEAREST THE GROUND BATTERY PLANT APPROVED GROUND (SEE NOTE) DISCHARGE 10 AWG COUPLED BONDING CONDUCTOR (CBC)CUSTOMER . ..60-HZ 50-AMP RECEPTACLE, AC POWER CORD 10 FEET OR EQUIVALENT115-VOLT NEMA 5-50 L6-30R PROVIDED POWERCOUPLED BONDING 6 AWGCONDUCTOR 10 AWG OR 208-VOLT 60-HZ 30-AMP SERVICE REAR CABINET GROUND BLOCKOR PANEL TELEPHONE COMPANY OWNED PROTECTOR GROUND BLOCK AT THE BUILDING ENTRANCE...