Home > ATT > Communications System > ATT DEFINITY Communications System Generic 3 Planning And Configuration Instructions Manual

ATT DEFINITY Communications System Generic 3 Planning And Configuration Instructions Manual

    Download as PDF Print this page Share this page

    Have a look at the manual ATT DEFINITY Communications System Generic 3 Planning And Configuration Instructions Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 164 ATT manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaPOWER AND GROUNDING
    Figure 16 shows a typical power and grounding layout for a remotely located EPN cabinet.  A
    ground wire must be connected from the cabinet ground block of both the PPN and EPN cabinets
    to an approved ground.  (Also see ``Grounding, later in this section).
    OR EQUIVALENT UNIT
    REAR
    . ..
    DISTRIBUTION
    RECEPTACLE,
    60-HZ 50-AMP 115-VOLT
    60-HZ 30-AMP
    NEMA 5-50
    PROVIDED
    POWER
    PANEL CUSTOMERPOWER. ..
    CORD
    10 FEET6 AWG
    60-HZ 50-AMP
    SERVICECONDUCTOR
    10 AWGTO
    APPROVED
    GROUND
    (SEE NOTE)
    115-VOLT
    60-HZ 30-AMP
    TELEPHONE COMPANY OWNED PROTECTOR GROUND BLOCK 
    AT THE BUILDING ENTRANCE FACILITY
    UNIT
    REAR DISTRIBUTIONGROUND BLOCK
    COUPLED
    BONDING 6 AWG
    SINGLE-POINT
    POWER
    TO APPROVED FRONT
    POWERFRONT
    NOTE:GROUND BLOCK
    NETWORK CABINETPROCESSOR PORT
    NETWORK CABINETEXPANSION PORT
    TO AUXILIARY
    CABINET
    COUPLED
    BONDING
    CONDUCTOR10 AWG
    GROUND
    (SEE NOTE)
    6 AWG
    USE APPROVED GROUND LOCATED NEAREST THE REMOTELY
    LOCATED
    POWER PANEL
    SINGLE-
    POINT
    GROUND
    BLOCK
    CUSTOMER
    PROVIDED SERVICE
    OR L6-30R
    OR 208-VOLT OR 208-VOLT
    POWER
    CORD
    10 FEET
    FIGURE 16.  Typical Multi-Carrier AC Power and Grounding (Remote EPN)
    117 
    						
    							POWER AND GROUNDINGaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
    Single-Carrier Cabinet System
    Each cabinet requires a separate power outlet, as shown in Figures 17 and 18.  These outlets
    must not be shared with other equipment, must not be under switch control, and should be
    located outside the cross-connect field area, if possible.  Any available power source can be used
    as long as the phase or leg provides 120-volt AC at the required drain.
    The Manager I terminal or G3r-MT should be connected to the ``Administration Terminal power
    outlet, as shown in Figures 17 and 18.
    A system cabinet is UL-listed at 10 amperes, 120 volts, or 1200 watts per cabinet.  Therefore, the
    power required for a two-cabinet system is 2400 watts, the power required for a three-cabinet
    system is 3600 watts, and the power required for a four-cabinet system is 4800 watts.
    20-AMP
    CABINET A
    OR
    CABINET A
    15-AMPCABINET B 2 CABINET SYSTEM
    TERMINAL
    15-AMPCABINET B
    20-AMP
    CABINET A
    15-AMP3 CABINET SYSTEM
    CABINET B
    CABINET C
    OR
    CABINET A
    15-AMP
    15-AMPCABINET B
    15-AMPCABINET C
    20-AMP
    CABINET B
    4 CABINET SYSTEM
    CABINET A
    20-AMP
    CABINET C
    CABINET D
    20-AMP
    CABINET A
    15-AMP
    15-AMPCABINET B
    OR
    CABINET C
    CABINET D
    TERMINALTERMINAL
    TERMINALTERMINAL
    TERMINAL ADMINISTRATION ADMINISTRATIONADMINISTRATION
    ADMINISTRATIONADMINISTRATION
    ADMINISTRATION
    FIGURE 17.  AC Power Requirements for a Single-Carrier Cabinet System
    118 
    						
    							aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaPOWER AND GROUNDING
    20-AMP
    CABINET B
    CABINET A
    CABINET C
    CABINET D
    CABINET A OR
    MANAGER I
    TERMINAL
    MANAGER I 20-AMP20-AMPCABINET A
    OR
    CABINET A
    15-AMPCABINET B 2 CABINET SYSTEM
    15-AMPCABINET B
    4 CABINET SYSTEM
    20-AMP
    15-AMP
    15-AMPCABINET BCABINET C
    CABINET D
    TERMINAL EXPANSION PORT
    NETWORK (EPN)PROCESSOR PORT
    NETWORK (PPN)
    FIGURE 18.  AC Power Requirements for a Single-Carrier System (Remotely Located EPN)
    119 
    						
    							POWER AND GROUNDINGaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
    Figure 19 depicts a typical power and grounding layout for a single-carrier system with the PPN
    and EPN cabinets colocated.  A ground wire from the ground block on the bottom cabinet of the
    EPN connects to the single-point ground block on the bottom cabinet of the PPN.  A 6-AWG
    ground wire connects the single-point ground block to an approved ground.  (Also see ``Ground-
    ing, later in this section).
    6 AWG
    GROUND
    APPROVED POWER
    CORD
    10 FEETREAR
    6 AWG
    115-VOLT
    60-HZ
    TERMINAL
    NOTE:
    POWER
    CORD
    10 FEET
    115-VOLT
    60-HZCOUPLED
    BONDING
    CONDUCTOR 10 AWG
    WIRE TO
    COUPLED
    BONDING
    CONDUCTOR 10 AWG
    20 AMP
    SERVICE 15 OR
    20 AMP
    SERVICE 15 OR
    MANAGER
    I
    (SEE NOTE)(SEE NOTE)
    GROUND
    (SEE NOTE) OFF
    ON
    OFF
    ONSINGLE-POINT
    GROUND BLOCKCIRCUIT
    BREAKER
    CIRCUIT
    BREAKERPOWER
    SUPPLY15-AMP
    PLUG
    OFF
    ONOFF
    ONPOWER
    SUPPLY PROCESSOR PORT NETWORK
    CONTROL CABINET A
    15-AMP
    PLUG
    REAR
    CONTROL CABINET A EXPANSION PORT NETWORK
    TO APPROVED GROUND LOCATED NEAREST THE TELEPHONE COMPANY OWNED
    PROTECTOR GROUND BLOCK AT THE BUILDING ENTRANCE FACILITYNEMA 5-15 OR
    NEMA 5-20
    RECEPTACLE,
    OR EQUIVALENT
    FIGURE 19.  Typical Single-Carrier Power and Grounding Layout (EPN Colocated)
    120 
    						
    							aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaPOWER AND GROUNDING
    Figure 20 shows a typical power and grounding arrangement for a system  with the EPN remotely
    located.  A ground wire must be connected from the cabinet ground block of both the PPN and
    EPN to an approved ground.  (Also see ``Grounding, later in this section).
    6 AWG
    GROUND
    APPROVED POWER
    CORD
    10 FEETREAR
    115-VOLT
    60-HZ
    TERMINAL
    NOTE:
    TO APPROVED GROUND LOCATED
    NEAREST THE TELEPHONE COMPANY
    OWNED PROTECTOR GROUND BLOCK
    AT THE BUILDING ENTRANCE FACILITY
    POWER
    CORD
    10 FEET
    115-VOLT
    60-HZ
    COUPLED
    BONDING
    CONDUCTOR 10 AWGWIRE TOCOUPLED
    BONDING
    CONDUCTOR 10 AWG
    20 AMP
    SERVICE 15 OR
    20 AMP
    SERVICE 15 OR
    MANAGER
    I NEMA 5-15 OR NEMA 5-20
    (SEE NOTE)(SEE NOTE) GROUND
    (SEE NOTE) OFF
    ON
    OFF
    ONSINGLE-POINT
    GROUND BLOCKCIRCUIT
    BREAKER
    CIRCUIT
    BREAKERPOWER
    SUPPLY15-AMP
    PLUG
    OFF
    ONOFF
    ONPOWER
    SUPPLY PROCESSOR PORT NETWORK
    CONTROL CABINET A
    15-AMP
    PLUG
    REAR
    CONTROL CABINET A EXPANSION PORT NETWORK
    RECEPTACLE, OR EQUIVALENT
    6 AWG
    GROUND
    APPROVED WIRE TO
    GROUND
    (SEE NOTE)
    FIGURE 20.  Typical Single-Carrier AC Power and Grounding Layout (Remotely Located EPN)
    121 
    						
    							POWER AND GROUNDINGaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
    DC Power Requirements
    Multi-Carrier Cabinet System
    A DC power plant may be used to power the multi-carrier system  cabinets. Figure 21 shows a
    typical power and grounding layout for a DC-powered multi-carrier cabinet.
    GROUND
    DISCHARGE
    BARAPPROVED
    GROUND
    (SEE NOTE)
    NOTE:
    10 AWG
    COUPLED
    BONDING
    CONDUCTOR
    (CBC)
    REAR
    -48 V
    BATTERY PLANT
    REAR
    CABINET
    GROUND
    BLOCK
    SYSTEM
    SINGLE
    POINT
    GROUND
    UNIT DISTRIBUTIONFRONT EXPANSION PORT
    -48 V-48 V RTN
    UNIT DISTRIBUTIONFRONT
    -48 V-48 V RTN
    NETWORK (EPN) CABINETPROCESSOR PORT
    NETWORK (PPN) CABINET
    1 GAUGE UP
    TO 50 FEET
    OR ENGINEERED
    THAN 1%
    VOLTAGE DROP FOR LESS DC POWERDC POWER
    USE APPROVED GROUND LOCATED NEAREST THE TELEPHONE
    COMPANY OWNED PROTECTOR GROUND BLOCK AT THE
    BUILDING ENTRANCE FACILITY(75A(75A
    CABINET
    GROUND
    BLOCK
    FIGURE 21.  Typical Multi-Carrier Cabinet System DC Power and Grounding Layout
    (EPN Colocated)
    122 
    						
    							aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaPOWER AND GROUNDING
    Table Q provides the requirements for input DC power.
    TABLE Q.  -48 Volt DC Input Power Requirements
    bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb
    Parameter Requirements
    bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb
    Static Voltage -48 V DC nominal, -42.5 V DC minimum, -52.5 V DC maximum
    (measured at input to system cabinet)
    bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb
    Dynamic Voltage Transient change in voltage (+/- 5% of steady state voltage)
    Allowed transient duration (up to 200 milliseconds)
    bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb
    AC Ripple Voltage Maximum wideband AC ripple (450 mvpp in the 3 kHZ-to-20 MHZ
    band)
    bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb
    Low Voltage Disconnect Automatic disconnect occurs when input voltage becomes less than
    -42.5 V DC (control provided with battery plant).
    bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb
    Overvoltage Protection Input voltage shall not exceed -52.5 V DC.
    bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb
    Voltage Drop Maximum drop must not exceed 0.5 V DC one-way on feeder cable
    between the power board and the system cabinet.
    Feeders must be UL approved and CSA certified.
    Feeder gauge must be no smaller than 6 AWG and no larger than
    1/0 gauge.
    Recommended -48 V DC feeder cableÐ
    Royal Electric #4905 or
    equivalent
    1-AWG is required for distances up to 50 feet.
    Cable resistance must be equal to or less than 0.1290 ohms per
    1000 feet.
    bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb
    Current Draw The battery plant rectifiers must be capable of providing current for
    the system, including current required for system holdover and for
    charging the batteries. In addition, this may include DC current
    required for an inverter that provides AC power to peripheral equip-
    ment, if it is installed, and for future growth.
    bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb
    Circuit Breaker A UL-listed and CSA-certified circuit breaker must be provided at the
    battery plant power board for each system cabinet feeder.
    The recommended circuit breakers are 
    75 ampere Airpax UPLI-1-
    REC2-52-753 or Heinemann AM1-B2-A-75-2
    .
    bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb c c c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c
    c c c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c
    c c c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c
    123 
    						
    							POWER AND GROUNDINGaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
    TABLE Q (continued).
    -48 Volt DC Input Power Requirements
    bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb
    Parameter Requirements
    bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb
    Redundancy Redundancy of the battery chargers/rectifiers should be considered.
    This would also provide the additional current necessary to recharge
    the batteries after being fully discharged.
    bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb
    Electrical Noise Voice band noise from the battery plant to the system must be less
    than 32dBmC.
    bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb
    Grounding A single point ground must be maintained.
    A ground conductor must be installed from the isolated Ground
    Discharge Bar* to the closest Approved Ground via the shortest
    route as required by the NEC/REC.  The gauge must be no smaller
    than the largest conductor in the system and larger than 6 AWG.
    The Ground Discharge Bar shall not be connected electrically to the
    chassis of the battery plant chargers, power board, or inverter(s).
    All output power shall be isolated from the input power.
    bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb
    Lightning Protection There must be adequate lightning protection in the battery plant to
    ensure that the system will not be damaged.
    bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb c c c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c
    c c c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c
    c c c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c c c
    c
    c
    c
    As shown in Figure 21, the size of the wire required for the -48 V DC and -48 V return must be
    engineered so that 
    the -48 V DC supplied by the battery plant to the G1 cabinets will be
    maintained between -42.5 and -52.5 V DC at all times 
    to ensure proper operation and to
    prevent hardware damage.
    aaaaaaaaaaaaaaaaaaa
    * Refer to 
    DEFINITYÒCommunications System  Generic 1 and Generic 3ÐInstallation and Test, 555-230-104, for parts
    and location information.
    124 
    						
    							aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaPOWER AND GROUNDING
    Figures 17 and 18 provide a power and grounding layout for mixed AC-/DC-powered multi-carrier
    cabinet configurations.
    GROUND
    BARDISCHARGE
    REAR
    TELEPHONE COMPANY OWNED PROTECTOR GROUND BLOCK 
    -48 V
    BATTERY PLANT
    CABINET
    GROUND
    BLOCK
    CABINET
    APPROVED
    GROUND
    (SEE NOTE)6 AWG
    10 AWG
    COUPLED
    BONDING
    CONDUCTOR
    (CBC) GROUND
    BLOCK
    USE APPROVED GROUND LOCATED NEAREST THE 
    -48 V-48 V RTN 
    PROVIDED
    POWER
    PANEL OR EQUIVALENT
    CUSTOMERUNIT
    REAR
    . ..60-HZ 50-AMP DISTRIBUTION
    NOTE:
    AC
    POWER
    CORD
    10 FEET
    CABINET
    115-VOLT NEMA 5-50
    OR
    SERVICE 60-HZ 30-AMP
    AT THE BUILDING ENTRANCE FACILITYFRONT
    NETWORK CABINETEXPANSION PORT
    FRONTPROCESSOR PORT
    NETWORK (PPN) CABINET
    DC POWER DISTRIBUTION UNIT
    AC POWER
    (75A
    OR L6-30R
    RECEPTACLE, 1 GAUGE UP
    ENGINEERED
    FOR LESS
    THAN 1%
    VOLTAGE DROP TO 50 FEET OR
    OR 208-VOLT
    TO AUXILIARY
    GROUND BLOCK
    FIGURE 22.  Typical Multi-Carrier Mixed AC/DC Power and Grounding Layout (EPN Colocated)
    125 
    						
    							POWER AND GROUNDINGaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
    USE APPROVED GROUND LOCATED NEAREST THE 
    GROUND
    BATTERY PLANT
    APPROVED
    GROUND
    (SEE NOTE)
    DISCHARGE
    10 AWG
    COUPLED
    BONDING
    CONDUCTOR
    (CBC)CUSTOMER
    . ..60-HZ 50-AMP RECEPTACLE,
    AC
    POWER
    CORD
    10 FEET
    OR 
    EQUIVALENT115-VOLT NEMA 5-50
    L6-30R
    PROVIDED
    POWERCOUPLED
    BONDING
    6 AWGCONDUCTOR 
    10 AWG
    OR
    208-VOLT
    60-HZ 30-AMP
    SERVICE REAR
    CABINET
    GROUND
    BLOCKOR
    PANEL
    TELEPHONE COMPANY OWNED PROTECTOR GROUND BLOCK 
    AT THE BUILDING ENTRANCE FACILITYFRONT
    NOTE:EXPANSION PORT
    REARFRONT
    PROCESSOR PORT
    NETWORK (PPN) CABINET
    1 GAUGE UP
    TO 50 FEET OR
    -48 V-48 V RTN 
    -48 VBAR
    TO 
    AUXILIARY
    CABINET
    GROUND
    BLOCK DISTRIBUTION UNITDC POWER 
    AC POWER
    DISTRIBUTION
    UNIT
    SINGLE
    POINT
    CABINET
    GROUND
    6 AWG
    TO
    APPROVED
    GROUND
    (SEE NOTE) NETWORK (EPN) CABINET
    (75A
    ENGINEERED FOR
    LESS THAN 1%
    VOLTAGE DROP
    FIGURE 23.  Typical Multi-Carrier Mixed AC/DC Power and Grounding Layout
    (Remotely Located EPN)
    For DC-powered systems,  a ground wire must be installed from the isolated Ground Discharge
    Bar on the battery plant to the Approved Ground.  (See ``Grounding.)  The size of the wire must
    be no smaller than the largest wire in the system and 
    must be larger than 6 AWG.  The approved
    ground connection must be identified with a Form 15657NR or equivalent grounding tag.  The
    Ground Discharge Bar shall not be connected electrically to the chassis of the chargers, power
    board, or inverters.  All output power must be isolated from the input power.
    A 6-AWG ground wire must be connected to the ground block in the bottom of each cabinet
    (Figure 21).  The ground wire is routed out of the cabinet and terminated on the battery plant.
    126 
    						
    All ATT manuals Comments (0)

    Related Manuals for ATT DEFINITY Communications System Generic 3 Planning And Configuration Instructions Manual