Home
>
ATT
>
Communications System
>
ATT DEFINITY Communications System Generic 3 Planning And Configuration Instructions Manual
ATT DEFINITY Communications System Generic 3 Planning And Configuration Instructions Manual
Have a look at the manual ATT DEFINITY Communications System Generic 3 Planning And Configuration Instructions Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 164 ATT manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaPOWER AND GROUNDING Figure 16 shows a typical power and grounding layout for a remotely located EPN cabinet. A ground wire must be connected from the cabinet ground block of both the PPN and EPN cabinets to an approved ground. (Also see ``Grounding, later in this section). OR EQUIVALENT UNIT REAR . .. DISTRIBUTION RECEPTACLE, 60-HZ 50-AMP 115-VOLT 60-HZ 30-AMP NEMA 5-50 PROVIDED POWER PANEL CUSTOMERPOWER. .. CORD 10 FEET6 AWG 60-HZ 50-AMP SERVICECONDUCTOR 10 AWGTO APPROVED GROUND (SEE NOTE) 115-VOLT 60-HZ 30-AMP TELEPHONE COMPANY OWNED PROTECTOR GROUND BLOCK AT THE BUILDING ENTRANCE FACILITY UNIT REAR DISTRIBUTIONGROUND BLOCK COUPLED BONDING 6 AWG SINGLE-POINT POWER TO APPROVED FRONT POWERFRONT NOTE:GROUND BLOCK NETWORK CABINETPROCESSOR PORT NETWORK CABINETEXPANSION PORT TO AUXILIARY CABINET COUPLED BONDING CONDUCTOR10 AWG GROUND (SEE NOTE) 6 AWG USE APPROVED GROUND LOCATED NEAREST THE REMOTELY LOCATED POWER PANEL SINGLE- POINT GROUND BLOCK CUSTOMER PROVIDED SERVICE OR L6-30R OR 208-VOLT OR 208-VOLT POWER CORD 10 FEET FIGURE 16. Typical Multi-Carrier AC Power and Grounding (Remote EPN) 117
POWER AND GROUNDINGaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa Single-Carrier Cabinet System Each cabinet requires a separate power outlet, as shown in Figures 17 and 18. These outlets must not be shared with other equipment, must not be under switch control, and should be located outside the cross-connect field area, if possible. Any available power source can be used as long as the phase or leg provides 120-volt AC at the required drain. The Manager I terminal or G3r-MT should be connected to the ``Administration Terminal power outlet, as shown in Figures 17 and 18. A system cabinet is UL-listed at 10 amperes, 120 volts, or 1200 watts per cabinet. Therefore, the power required for a two-cabinet system is 2400 watts, the power required for a three-cabinet system is 3600 watts, and the power required for a four-cabinet system is 4800 watts. 20-AMP CABINET A OR CABINET A 15-AMPCABINET B 2 CABINET SYSTEM TERMINAL 15-AMPCABINET B 20-AMP CABINET A 15-AMP3 CABINET SYSTEM CABINET B CABINET C OR CABINET A 15-AMP 15-AMPCABINET B 15-AMPCABINET C 20-AMP CABINET B 4 CABINET SYSTEM CABINET A 20-AMP CABINET C CABINET D 20-AMP CABINET A 15-AMP 15-AMPCABINET B OR CABINET C CABINET D TERMINALTERMINAL TERMINALTERMINAL TERMINAL ADMINISTRATION ADMINISTRATIONADMINISTRATION ADMINISTRATIONADMINISTRATION ADMINISTRATION FIGURE 17. AC Power Requirements for a Single-Carrier Cabinet System 118
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaPOWER AND GROUNDING 20-AMP CABINET B CABINET A CABINET C CABINET D CABINET A OR MANAGER I TERMINAL MANAGER I 20-AMP20-AMPCABINET A OR CABINET A 15-AMPCABINET B 2 CABINET SYSTEM 15-AMPCABINET B 4 CABINET SYSTEM 20-AMP 15-AMP 15-AMPCABINET BCABINET C CABINET D TERMINAL EXPANSION PORT NETWORK (EPN)PROCESSOR PORT NETWORK (PPN) FIGURE 18. AC Power Requirements for a Single-Carrier System (Remotely Located EPN) 119
POWER AND GROUNDINGaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa Figure 19 depicts a typical power and grounding layout for a single-carrier system with the PPN and EPN cabinets colocated. A ground wire from the ground block on the bottom cabinet of the EPN connects to the single-point ground block on the bottom cabinet of the PPN. A 6-AWG ground wire connects the single-point ground block to an approved ground. (Also see ``Ground- ing, later in this section). 6 AWG GROUND APPROVED POWER CORD 10 FEETREAR 6 AWG 115-VOLT 60-HZ TERMINAL NOTE: POWER CORD 10 FEET 115-VOLT 60-HZCOUPLED BONDING CONDUCTOR 10 AWG WIRE TO COUPLED BONDING CONDUCTOR 10 AWG 20 AMP SERVICE 15 OR 20 AMP SERVICE 15 OR MANAGER I (SEE NOTE)(SEE NOTE) GROUND (SEE NOTE) OFF ON OFF ONSINGLE-POINT GROUND BLOCKCIRCUIT BREAKER CIRCUIT BREAKERPOWER SUPPLY15-AMP PLUG OFF ONOFF ONPOWER SUPPLY PROCESSOR PORT NETWORK CONTROL CABINET A 15-AMP PLUG REAR CONTROL CABINET A EXPANSION PORT NETWORK TO APPROVED GROUND LOCATED NEAREST THE TELEPHONE COMPANY OWNED PROTECTOR GROUND BLOCK AT THE BUILDING ENTRANCE FACILITYNEMA 5-15 OR NEMA 5-20 RECEPTACLE, OR EQUIVALENT FIGURE 19. Typical Single-Carrier Power and Grounding Layout (EPN Colocated) 120
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaPOWER AND GROUNDING Figure 20 shows a typical power and grounding arrangement for a system with the EPN remotely located. A ground wire must be connected from the cabinet ground block of both the PPN and EPN to an approved ground. (Also see ``Grounding, later in this section). 6 AWG GROUND APPROVED POWER CORD 10 FEETREAR 115-VOLT 60-HZ TERMINAL NOTE: TO APPROVED GROUND LOCATED NEAREST THE TELEPHONE COMPANY OWNED PROTECTOR GROUND BLOCK AT THE BUILDING ENTRANCE FACILITY POWER CORD 10 FEET 115-VOLT 60-HZ COUPLED BONDING CONDUCTOR 10 AWGWIRE TOCOUPLED BONDING CONDUCTOR 10 AWG 20 AMP SERVICE 15 OR 20 AMP SERVICE 15 OR MANAGER I NEMA 5-15 OR NEMA 5-20 (SEE NOTE)(SEE NOTE) GROUND (SEE NOTE) OFF ON OFF ONSINGLE-POINT GROUND BLOCKCIRCUIT BREAKER CIRCUIT BREAKERPOWER SUPPLY15-AMP PLUG OFF ONOFF ONPOWER SUPPLY PROCESSOR PORT NETWORK CONTROL CABINET A 15-AMP PLUG REAR CONTROL CABINET A EXPANSION PORT NETWORK RECEPTACLE, OR EQUIVALENT 6 AWG GROUND APPROVED WIRE TO GROUND (SEE NOTE) FIGURE 20. Typical Single-Carrier AC Power and Grounding Layout (Remotely Located EPN) 121
POWER AND GROUNDINGaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa DC Power Requirements Multi-Carrier Cabinet System A DC power plant may be used to power the multi-carrier system cabinets. Figure 21 shows a typical power and grounding layout for a DC-powered multi-carrier cabinet. GROUND DISCHARGE BARAPPROVED GROUND (SEE NOTE) NOTE: 10 AWG COUPLED BONDING CONDUCTOR (CBC) REAR -48 V BATTERY PLANT REAR CABINET GROUND BLOCK SYSTEM SINGLE POINT GROUND UNIT DISTRIBUTIONFRONT EXPANSION PORT -48 V-48 V RTN UNIT DISTRIBUTIONFRONT -48 V-48 V RTN NETWORK (EPN) CABINETPROCESSOR PORT NETWORK (PPN) CABINET 1 GAUGE UP TO 50 FEET OR ENGINEERED THAN 1% VOLTAGE DROP FOR LESS DC POWERDC POWER USE APPROVED GROUND LOCATED NEAREST THE TELEPHONE COMPANY OWNED PROTECTOR GROUND BLOCK AT THE BUILDING ENTRANCE FACILITY(75A(75A CABINET GROUND BLOCK FIGURE 21. Typical Multi-Carrier Cabinet System DC Power and Grounding Layout (EPN Colocated) 122
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaPOWER AND GROUNDING Table Q provides the requirements for input DC power. TABLE Q. -48 Volt DC Input Power Requirements bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Parameter Requirements bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Static Voltage -48 V DC nominal, -42.5 V DC minimum, -52.5 V DC maximum (measured at input to system cabinet) bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Dynamic Voltage Transient change in voltage (+/- 5% of steady state voltage) Allowed transient duration (up to 200 milliseconds) bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb AC Ripple Voltage Maximum wideband AC ripple (450 mvpp in the 3 kHZ-to-20 MHZ band) bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Low Voltage Disconnect Automatic disconnect occurs when input voltage becomes less than -42.5 V DC (control provided with battery plant). bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Overvoltage Protection Input voltage shall not exceed -52.5 V DC. bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Voltage Drop Maximum drop must not exceed 0.5 V DC one-way on feeder cable between the power board and the system cabinet. Feeders must be UL approved and CSA certified. Feeder gauge must be no smaller than 6 AWG and no larger than 1/0 gauge. Recommended -48 V DC feeder cableÐ Royal Electric #4905 or equivalent 1-AWG is required for distances up to 50 feet. Cable resistance must be equal to or less than 0.1290 ohms per 1000 feet. bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Current Draw The battery plant rectifiers must be capable of providing current for the system, including current required for system holdover and for charging the batteries. In addition, this may include DC current required for an inverter that provides AC power to peripheral equip- ment, if it is installed, and for future growth. bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Circuit Breaker A UL-listed and CSA-certified circuit breaker must be provided at the battery plant power board for each system cabinet feeder. The recommended circuit breakers are 75 ampere Airpax UPLI-1- REC2-52-753 or Heinemann AM1-B2-A-75-2 . bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c 123
POWER AND GROUNDINGaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa TABLE Q (continued). -48 Volt DC Input Power Requirements bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Parameter Requirements bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Redundancy Redundancy of the battery chargers/rectifiers should be considered. This would also provide the additional current necessary to recharge the batteries after being fully discharged. bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Electrical Noise Voice band noise from the battery plant to the system must be less than 32dBmC. bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Grounding A single point ground must be maintained. A ground conductor must be installed from the isolated Ground Discharge Bar* to the closest Approved Ground via the shortest route as required by the NEC/REC. The gauge must be no smaller than the largest conductor in the system and larger than 6 AWG. The Ground Discharge Bar shall not be connected electrically to the chassis of the battery plant chargers, power board, or inverter(s). All output power shall be isolated from the input power. bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb Lightning Protection There must be adequate lightning protection in the battery plant to ensure that the system will not be damaged. bbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbbb c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c As shown in Figure 21, the size of the wire required for the -48 V DC and -48 V return must be engineered so that the -48 V DC supplied by the battery plant to the G1 cabinets will be maintained between -42.5 and -52.5 V DC at all times to ensure proper operation and to prevent hardware damage. aaaaaaaaaaaaaaaaaaa * Refer to DEFINITYÒCommunications System Generic 1 and Generic 3ÐInstallation and Test, 555-230-104, for parts and location information. 124
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaPOWER AND GROUNDING Figures 17 and 18 provide a power and grounding layout for mixed AC-/DC-powered multi-carrier cabinet configurations. GROUND BARDISCHARGE REAR TELEPHONE COMPANY OWNED PROTECTOR GROUND BLOCK -48 V BATTERY PLANT CABINET GROUND BLOCK CABINET APPROVED GROUND (SEE NOTE)6 AWG 10 AWG COUPLED BONDING CONDUCTOR (CBC) GROUND BLOCK USE APPROVED GROUND LOCATED NEAREST THE -48 V-48 V RTN PROVIDED POWER PANEL OR EQUIVALENT CUSTOMERUNIT REAR . ..60-HZ 50-AMP DISTRIBUTION NOTE: AC POWER CORD 10 FEET CABINET 115-VOLT NEMA 5-50 OR SERVICE 60-HZ 30-AMP AT THE BUILDING ENTRANCE FACILITYFRONT NETWORK CABINETEXPANSION PORT FRONTPROCESSOR PORT NETWORK (PPN) CABINET DC POWER DISTRIBUTION UNIT AC POWER (75A OR L6-30R RECEPTACLE, 1 GAUGE UP ENGINEERED FOR LESS THAN 1% VOLTAGE DROP TO 50 FEET OR OR 208-VOLT TO AUXILIARY GROUND BLOCK FIGURE 22. Typical Multi-Carrier Mixed AC/DC Power and Grounding Layout (EPN Colocated) 125
POWER AND GROUNDINGaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa USE APPROVED GROUND LOCATED NEAREST THE GROUND BATTERY PLANT APPROVED GROUND (SEE NOTE) DISCHARGE 10 AWG COUPLED BONDING CONDUCTOR (CBC)CUSTOMER . ..60-HZ 50-AMP RECEPTACLE, AC POWER CORD 10 FEET OR EQUIVALENT115-VOLT NEMA 5-50 L6-30R PROVIDED POWERCOUPLED BONDING 6 AWGCONDUCTOR 10 AWG OR 208-VOLT 60-HZ 30-AMP SERVICE REAR CABINET GROUND BLOCKOR PANEL TELEPHONE COMPANY OWNED PROTECTOR GROUND BLOCK AT THE BUILDING ENTRANCE FACILITYFRONT NOTE:EXPANSION PORT REARFRONT PROCESSOR PORT NETWORK (PPN) CABINET 1 GAUGE UP TO 50 FEET OR -48 V-48 V RTN -48 VBAR TO AUXILIARY CABINET GROUND BLOCK DISTRIBUTION UNITDC POWER AC POWER DISTRIBUTION UNIT SINGLE POINT CABINET GROUND 6 AWG TO APPROVED GROUND (SEE NOTE) NETWORK (EPN) CABINET (75A ENGINEERED FOR LESS THAN 1% VOLTAGE DROP FIGURE 23. Typical Multi-Carrier Mixed AC/DC Power and Grounding Layout (Remotely Located EPN) For DC-powered systems, a ground wire must be installed from the isolated Ground Discharge Bar on the battery plant to the Approved Ground. (See ``Grounding.) The size of the wire must be no smaller than the largest wire in the system and must be larger than 6 AWG. The approved ground connection must be identified with a Form 15657NR or equivalent grounding tag. The Ground Discharge Bar shall not be connected electrically to the chassis of the chargers, power board, or inverters. All output power must be isolated from the input power. A 6-AWG ground wire must be connected to the ground block in the bottom of each cabinet (Figure 21). The ground wire is routed out of the cabinet and terminated on the battery plant. 126