Page 91
Key Telephone System 500.3 SYSTEM GROUNDING To ensure that the system will operate properly, a good earth ground is required. Use of the Telco ground (source not demark) or a metallic COLD water pipe usually provides a reliable ground path. Carefully check that the pipe does not contain insul- ated joints that could isolate the ground. In the absence of the COLD water pipe, a ground rod or other source may be used. A no. 8 AWG copper wire should be used between the ground source and the KSU...
Page 92
, STAFif’u.@ 96Ex Key Telephone System 21.75*,-b/k- 15.125n -4 1 F I 17.8” 13.5. BASIC KSU EXPANSION KSLJ -~- --- --- ---- CL I I 13.5. DEPTH: 13.3” 13.1. 10.8T POWER SUPPLY HOUSING2 (EPH2) 0 DEPTH: 12.8. Figure 500-2 Mounting Dimensions Issue 1, June 1991 So-3
Page 93
!~TARPLUS@ 96EX Key Telephone System BASIC KSU CCCK K K K K K U”““, , , , , , FBBBB B B 6 B B P u, L;; 2 2 4 5 R. . CO LINES 01-24 POWER FAILURE- TRANSFER LOUD BELL -7 CONTROL GROUND - TERMINAL Illllll Illu ~lllll #IlUll Illll COVERT0 - CONNECTION ON EXPANSION KSU CABLE RACEWAY STATIONS 100-l 47 EXPANSION KSU LEm SIDE OF BASIC KSU lllll lllll lllll lllll Ill IIII lllll lllll lllll III STATIONS 148-195 CO LINES ’ 25-40 lllll lllll lllll III III gj p-fq-) CABLE RACEWAY...
Page 94
sTARPLUS@ 96EX Key Telephone System A. insert 4 (#iO o: larger) screws into the back- board and tighten enough to hold the weight of the KSU. Lift the KSU and place it onto the screws. When the KSU is in position, the screws can be tightened and the KSU is se- curely mounted. 500.5 LIGHTNING PROTECTION The Starplus 96EX Hybrid Key Telephone System should have Central Office lines and OPX stations protected with proper lightning surge arrestors. This will provide protection from damaging surges...
Page 95
%AFIPLUS@ 96EX Key Telephone System PS 1 PSiij I RG SC Ll @ l-l II El 4c 0 x0 ON WGO OFI 96EX Power Supply (PS) MODEL GPS-7A %k? 1OAMA.X External Power Housing2 - Right Sii - SHORTING STFW CAUTION: Remove the shorting stra from the battew connecting teminals on t rt e tight side of the EPH2,,before connecting batteries. Figure 500-4 Ext. Power Housing2 (EPH2) 81 Power Supply
Page 96
sTARPLus@ 96EX Key Telephone System Before installing the Battery Charging Unit (BC) turn off the AC power switch on the front of the EPS. To install the BC, remove the cover of the External Power Supply Housing 2 (EPH2). Locate the BC card slot and remove the Battery Bypass Board. Table 50&l Battery Back Up Duration Battery Amp Configuration Hour Rating 16x32 24x48 40x96 7AH 1 1/2HR. 1 HR. 2OMlN. 14AH 21/2 HR. 2 HR. 1 HR. 4oAH 7 HR. 5 l/2 HR. 3 HR. The BC unit provides a Tone Emitter...
Page 97
STARPLUS@ 96EX Key Telephone System ~ 12 VOLT BATrEFIlES (2) STRAIN RELIEF CABLE ASSY CABLE ASSY AND SEPAFiATOR -+* MARKER % + BA-ITERY CONNECTOR TERMINAL =-* MARKER EXTERNAL POWER HOUSING2 (EPH2) Figure 500-6 Typical Battery Interconnection Layout 500.9 PRINTED CIRCUIT BOARD INSTAL- LATION The Printed Circuit Boards (PCB’s) used to configure the system contain static sensitive components that will require a few simple handling precautions to avoid damage. Keep all PCB’s in their...
Page 98
. sTARPLUS@ 96EX Key Telephone System COLORED TABS c37 TEST - m +14 cl+s @ GND f8 c3 ADJUSTMENTS BGM VOLUME BACKGROUND MUSIC CONNECTIONS Figure 500-7 DC/DC Converter Unit (DC/DC) issue 1, June 1991 500-g
Page 99
sARPLUS@ 96EX Key Tiephone System DIP SWlTCHES SW2 l-WRlTE MEMORY (Enable=ON; kable=OFF) 2-CLEAR TO SEND (EnabkON; DiiabledIFF) 3-TRACE OUTPUT (EnabkON; DiiabhOFF) 4-SOR RESTART (EnabkON; DisabkOFF) 5-SMDR (EnabledIN; Dhble=OFF) 6-29 CHARACTER=OFF; 80 CHARACTEkON XMDR: CPB=OFF; APL=ON 8-INlTlAllZE (EnablezON; DidhOFF) BAT- YELLOW COLORED r7 PROCESS0 Figure 500-B Central Processing Board (CPB) 500-10 Issue 1, June 1991
Page 100
500.10 COPBX CONNECTIONS An FCC approved RJ2iX connector should be sup- plied by the Telco at the demarcation point. The RJ2iX should be located within 25 ft. of the KSU. All CO/PBX line connections are made on the Pl and P2 cables. The PI connector is located in the Basic KSU and the P2 connector in the Expansion KSU. A COB or COA card must be installed in the associ- ated KSU card slot in order for the CO/PBX line interface connections to be established (Refer to Tables 500-3 and 500-4)....