Trane Rtaaiom3 Manual
Here you can view all the pages of manual Trane Rtaaiom3 Manual. The Trane manuals for Cooler are available online for free. You can easily download all the documents as PDF.
Page 111
111RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE NONE Outdoor Air Temperature None All Open or Short Sensor (Both Outdoor Air a. Display dashes e.g. 14 - - - - -”, Reset or Low Ambient Lockout Not Selected) Ab Evap. Leaving Water Temp. Sensor MMR All Open or Short bA Overload Trip - Compressor A CMR Compressor Energized Compressor current exceeded overload time vs. trip characteristic. bb Overload Trip - Compressor B CMR...
Page 112
112RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE d8 Under Voltage MAR Pre-start and a. Line voltage below -10% of nominal Any Circuit(s) Energized the Under/Over transformer is not connected. (Must hold = -10% of nominal Must trip = -15% of nominal). Ed Chilled Water Flow Interlock MAR All Modes Except a. The chilled water flow switch input STOP (00) and was open for more than 6 seconds. EXTERNAL STOP (100) F5 High Pressure...
Page 113
113RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE 190 Low Superheat Circuit 1 CMR All Running Modes a. A low superheat condition existed for an extended period of time. If a superheat less than or equal to 2 F is detected for more than 2400 F seconds, the circuit shall be shut down. The integrated area (2400 F seconds) shall be only below 2 F superheat. 191 Low Superheat - Circuit 2 CMR All Running Modes Same as diagnostic...
Page 114
114RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE 1A4 Remote Communications Loss IFW All AUTO/REMOTE Modes a. While the chiller switch was in the AUTO/REMOTE the communication between the CSR and the connected remote device, e.g. a Tracer or Remote Display, had either never been established for more than 15 minutes after power up or was lost for more than 15 minutes after it had been established; use the Front Panel...
Page 115
115RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE 1Ad Memory Error Type I IFW UCM Power Up or a. On UCM power up or following a Following a Type II Type II Memory Error a NOVRAM Memory Error memory error was detected. The UCM is operating on all Engineering ROM defaults for all setup parameters. Check all I setup parameters and continue to run chiller. Replace the Chiller Module as soon as a replacement is available. 1AE...
Page 116
116RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE 1bE Winding Temp.- Compressor A CMR All a. The motor winding temperature thermostat opened; nominally 221 F. b. The motor temperature thermostat or wiring is open. c. Time to trip from input open to compressor shutdown shall be 0.5 to 2.0 seconds. 1bF Winding Temp.- Compressor B CMR All Same as diagnostic 1bE. 1C0 Winding Temp.- Compressor C CMR All Same as diagnostic...
Page 117
117RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE 1d3 Comp. Suction Temp. Sensor - CMR All a . Open or Short in sensor electrical Circuit 1 circuitry. 1d4 Comp. Suction Temp. Sensor - CMR All a. Open or Short in sensor electrical Circuit 2 circuitry. 1d7 Phase Reversal Protection Lost - CMR Compressor Energized to a. The phase reversal protection Compressor A To Transition Command Compressor A has become inoperative. The...
Page 118
118RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE 435 1U3 Indicating CMR All The 1U3 Module has detected a loss of 1U5 Communications inter-processor communications from the 1U5 Module. 436 1U3 Indicating CMR All The 1U3 Module has detected a loss of 1U6 Communications inter-processor communications from the 1U6 Module. 437 1U3 Indicating CMR All The 1U3 Module has detected a loss of 1U7 Communications. inter-processor...
Page 119
119RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE 481 1U8 Indicating MMR All The 1U8 Module has detected a loss of 1U1 Communications inter-processor communications from the 1U1 Module. 483 1U8 Indicating CMR* All The 1U8 Module has detected a loss of 1U3 Communications inter-processor communications from the 1U3 Module. 484 1U8 Indicating CMR All The 1U8 Module has detected a loss of 1U4 Communications inter-processor...