101RTAA-IOM-3 Menu 2 - Service #2 Display 20 - Compressor Mode: The current compressor operating status, as shown in Figure 53, will be displayed when this menu item is selected. 21 - Compressor Suction Rfgt. Temperature: Temperature as read by the suction temperature sensor (see Figure 40). 22 - Saturated Evaporator Rfgt Temperature: Temperature as read by the saturated evaporator temperature sensor (see Figure 40). 23 - Evaporator Refrigerant Pressure: The pressure displayed is the evaporator...
Page 102
102RTAA-IOM-3 Menu 4 – Factory Display #1 40 - Leaving Water Temp. Cutout Setpoint: Establishes a leaving chilled water temperature, below which the UCM will begin unloading compressors and, if necessary, terminate unit operation. See discussion in “Leaving Water Temperature Cutout”. See Table 15 for proper settings.41 - Low Refrigerant Temp. Cutout Setpoint: Establishes a saturated evaporator refrigerant temperature, below which the UCM will begin unloading compressors and, if necessary, terminate unit...
Page 103
103RTAA-IOM-3 42 - Condenser Limit Setpoint: Establishes a percentage of the condenser high pressure cutout, above which the UCM will begin unloading compressors and, if necessary, terminate unit operation. 43 - Lead Lag: Enables or disables the Auto Lead/Lag feature. See discussion in “Auto Lead/Lag”. 44 - SI Display Units: When set to “Enable”, the display units are converted from OF to IC and PSIG to Kilopascals Gauge. 45 -Unit Line Voltage (Optional): Establishes the line voltage coming into the unit...
Page 104
104RTAA-IOM-3 Menu 5 – Factory Display #2 50 - Number of Compressors: Set to the number of compressor installed in the unit. 51 - Compressor Tons: Set to the rating in tons, of the each installed compressor. See Table 2. 52 - Low Water Temperature EXV Gain Compensation: Set to “E” if the unit will ever operate with a leaving chilled water temperature of 40 F or less. 53 - Fan Control: Set to “E”. 54 - Fans Per Circuit: Establishes the number of fans installed on each circuit. See Figures 45 and 46. 55 -...
Page 105
105RTAA-IOM-3 Table 17 Compressor(s) Current Limit Setpoint vs Chiller Current Limit Setpoint (CLS) Number of Compressors on a UnitTwo (130-215) Three (240-300) Four (340-400)Number of Number of Number of compressors compressors compressors System in operation in operation in operation CLS One Two One Two Three One Two Three Four120% 120 120 120 120 120 120 120 120 120 100% 120 100 120 120 100 120 120 120 100 80% 120 80 120 120 80 120 120 107 80 60% 120 60 120 90 60 120 120 80 60 40% 80 40 120 60 40 120...
Page 106
106RTAA-IOM-3 Chilled Water Reset (CWR) As an option, the UCM will reset the chilled water temperature setpoint, based on either the return water temperature, zone air temperature, or outdoor air temperature. The following are selectable: 1. One of four RESET TYPEs, from top to bottom in order of reset: no CWR RETURN WATER TEMPERATURE RESET ZONE TEMPERATURE RESET OUTDOOR AIR TEMPERATURE RESET The UCM will not permit more than one type of reset to be selected in Menu 3. 2. RESET RATIO Setpoints. For...
Page 107
107RTAA-IOM-3 Leaving Water Temperature Cutout This temperature cutout provides protection against freezing caused by low leaving water temperature. The setpoint is both factory set and adjustable from Menu 4. Temperatures below the setpoint will cause the UCM to accelerate reduction of chiller capacity, even to the point of compressor shutdown. A non-latching diagnostic will be generated if the LWT is below the cutout for more than 30 degree F seconds. There must be a minimum of 5 F between the cutout...
Page 108
108RTAA-IOM-3 Auto Lead/Lag This feature is enabled/disabled in code 43, menu 4. When enabled, the UCM will start the compressor with the fewest starts and stop the compressor with the greatest hours, as determined by the “Compressor Starts” accumulator (code 29, menu 2) and the “Compressor Hours” (code 2A, menu 2). (Display is optional). This will tend to balance out hours and starts equally over all compressors. For efficiency improvement, when there are 2 compressors operating, they will be on...
Page 109
109RTAA-IOM-3 2. The display will flash the Current Operating Code “A”, followed by a fully blank display for all other diagnostics (CMR, CAR, and IFW diagnostics). This is to call attention to the detection of some type of failure. Depressing the Display Down key will advance the display to the “Last (most recent) Diagnostic Code”. The display will “flash” if any diagnostic exists that requires a manual reset to restore full unit operation. The display will be continuous if no manual reset is required...
Page 110
110RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart In the table below, a “LATCHING” diagnostic is a condition which shall cause the machine or a portion of the machine as noted to shut down and shall require a manual reset to restore operation. A diagnostic that is non-latching shall reset automatically when the condition causing the diagnostic goes away. A non-latching diagnostic shall shut down the machine or a part of the machine if so indicated. If a diagnostic is informative only, no...