Trane Rtaaiom3 Manual
Here you can view all the pages of manual Trane Rtaaiom3 Manual. The Trane manuals for Cooler are available online for free. You can easily download all the documents as PDF.
Page 91
91RTAA-IOM-3 Figure 50 RTAA Control Panel – 130 to 200 Tons with Remote Evaporator Option LEGEND: Device Designation Description 1F1-6 Fan Fuses, Circuit 1 1F7-12 Fan Fuses, Circuit 2 1F15 Control Circuit Fuse 1F16, 1F17 Primary Transformer Fuses 1K1, 1K5 Start Contactors 1K2, 1K6 Run Contactors 1K4, 1K8 Transition Contactors 1K5, 1K7 Shorting Contactors 1K9-12 Fan Contactors, Circuit 1 1K13-16 Fan Contactors, Circuit 2 1S1, 1S2 Non-fused Disconnect Switch 1T1 Control Power Transformer 1T2...
Page 93
93RTAA-IOM-3 Figure 52 Menu Formats OPERATING DISPLAY - MENU 0 Selected by setting the number 0 in the “P” menu item. Compressor/circuit indicators will be lit Continuously in this menu to indicate which compressors/ circuits are running. All items of Menu 0 are display only. Setpoint changes must be made in other menus. Display Code and Description P Menu Number A Operating Code b Last Diagnostic Code C Other Diagnostic Codes d Active Chilled Water Setpoint* E Evaporator Entering Water Temperature F...
Page 94
94RTAA-IOM-3 Figure 52 Menu Formats (Continued) SERVICE #1 DISPLAY – MENU 1 Selected by setting the number 1 in the “P” menu item. The compressor circuit indicators will not be lit continuously in this menu to indicate which compressors are running. As the menu is advanced, the appropriate compressor/circuit indicator will flash. UCM Based Setpoint Display Code and Description Defaults Range P Menu Number 10 Front Panel Chilled Water Setpoint 44 F 0 to 65 F 11 Design Delta Temperature Setpoint 10 F 4 to...
Page 95
95RTAA-IOM-3 Figure 52 Menu Formats (Continued) AUXILIARY OPTIONS – MENU 3 Selected by setting the number 3 in the “P” menu number position. Compressor/circuit indicators will not be lit continuously in this menu to indicate which compressors/circuits are running. UCM Based Setpoint Display Code and Description Defaults Range P Menu Number 30 External Chilled Water Setpoint - d/E d 31 External Current Limit Setpoint - d/E d 32 Ice Machine Control - d/E d 33 Active-Ice Termination Setpoint* 34 Front Panel...
Page 96
96RTAA-IOM-3 Figure 52 Menu Formats (Continued) FACTORY DISPLAY #1 - MENU 4 Caution: Do not leave unit unattended while in Menu 4 or 5. Inadvertent unit safety setpoint changes could occur. Selected by setting the number 4 in the “P” menu item. Unlike menus 0 through 3, the number 4 can only be set by entering a combination of numbers. This combination consists of a sequence of “P” menu numbers -0, 1, 2, 1, 2, 3, 2, 3. 4. Compressor/circuit indicators will not be lit continuously in this menu to indicate...
Page 97
97RTAA-IOM-3 Figure 52 Menu Formats (Continued) FACTORY DISPLAY #2 - MENU 5 Caution: Do not leave unit unattended while in Menu 4 or 5. Inadvertent unit safety setpoint changes could occur. Selected by setting the number 5 in the “P” menu item. Unlike menus 0 through 3, the number 5 can only be set after menu 4 has been selected, as described on the previous page. Compressor/circuit indicators will not be lit continuously in this menu to indicate which compressors are running. As the menu is advanced...
Page 98
98RTAA-IOM-3 Figure 53 Condition/Diagnostic Codes UNIT OPERATING STATUS COMPRESSOR OPERATING STATUSCODE DESCRIPTION CODE DESCRIPTION Blank UCM Power Off 00Compressor Stop 888888.8 UCM Paw Up 16 Compressor Lockout 00 Unit Stop 17 Cprsr Service Pumpdown 01 Auto-Local 70 Cprsr Restart Inhibit 02 Auto-Remote 72 Cprsr Start 17 Service Pumpdown 74 Run Normal 70 Unit Restart Inhibit 75 Run: Current Limit 72 Unit Start 76 Run: Condenser Limit 74 Run:Normal 77 Run: Evaporator Limit 75 Run:Current Limit 7E...
Page 99
99RTAA-IOM-3 Chiller Switch The chiller switch has three positions: Top Position AUTO REMOTE Middle Position AUTO LOCAL Bottom Position STOP/RESET With the switch in the AUTO REMOTE position, the chiller will operate normally using remote setpoints. Read and write remote communications may be performed. Any call for cooling based on Leaving Water Temperature (LWT) and the remote (e.g. Tracer) setpoints, will start the unit. The active chilled water setpoint (CWS) can be the remote CWS, a reset remote...
Page 100
100RTAA-IOM-3 Menu Function Descriptions and Selection Selecting Variables and Options All variables and options will be set by depressing the SET POINT UP and SET POINT DOWN keys. The setpoints will be increased or decreased by one least significant digit (1 F, 0. 1 C, or 1 integer value) with each key depression. If the key is held down, the setpoint will continue to be increased or decreased until the key is released. The minimum and maximum values of all setpoints are limited by system design and...