Home > Tone Commander > Telephone > Tone Commander 1030/1560 Installation Instructions

Tone Commander 1030/1560 Installation Instructions

    Download as PDF Print this page Share this page

    Have a look at the manual Tone Commander 1030/1560 Installation Instructions online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 24 Tone Commander manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Wall
    Jack
    PinoutWall Jack
    Typical
    Wire ColorConsole #1
    Designation
    (connector 1)Console #2
    Designation
    (connector 1)Typical 3 Pair
    Console Cable
    Wire Color(actual
    wire color)
    1 WHT 1C+ (YEL-BRN) 2C+ (VIO-GRN) WHT-GRN
    2 BLK 1C+ (YEL-GRN) 2C+ (VIO-ORN) WHT-ORN
    3 RED 1C- (ORN-YEL) 2C- (BLU-VIO) BLU-WHT
    4 GRN 1C+ (YEL-ORN) 2C+ (VIO-BLU) WHT-BLU
    5 YEL 1C- (GRN-YEL) 2C- (ORN-VIO) ORN-WHT
    6 BLU 1C- (BRN-YEL) 2C- (GRN-VIO) GRN-WHT
    Table 5 –Console “Power” Jack Pinout
    The total console cable length, including line cord and equipment room cross connects, must not exceed
    500 feet.
    1. Install two 6 position, 6 contact modular telephone jacks within 6 feet of the console.
    2. Label the jacks 1560 voice/data and 1560 power (or 1030).
    3. Connect a 3 pair cable to each jack and run them to the equipment room.
    IMPORTANT– Whenever nonkey adapters are used in conjunction with existing multipair cable, verify
    that the adapters conform to Tables 4 and 5 above.
    4.Only if the colors of your cables differ from the typical colors:fill out Tables 4 and 5 with the actual wire
    colors of the cables for each connection.
    5. Punch down the voice/data cable on the right side of CPU block #1, to the pins listed in the Console
    #1 Designation column in Table 4.
    6. Punch down the power cable on the left side of CPU block #2, to the pins listed in the Console #1
    Designation column in Table 5.
    7. If the system has two consoles (two attendant positions), punch down the second consoles cables to
    the pins listed in the Console #2 Designation columns of Tables 4 and 5.
    13-102360 Rev. HPage 21
    Tone Commander 1030/1560 Installation Instructions 
    						
    							Console Installation
    Preliminary Testing
    At this time, you should have completed the following:
    
    Mounted the CPU and blocks
    
    Installed the cables from the CPU to the blocks
    
    Connected Tip and Ring from each line to the block
    
    Connected Tip and Ring from each monitored station to the block
    
    Installed the console cables and jacks
    
    Assembled and connected the console(s)
    It is a good idea to briefly test the operation of the 1030/1560 before proceeding with installation or
    programming.
    1. Plug the CPU into a power outlet.
    A. The heartbeat indicator at the bottom of the CPU main circuit board should flash.
    If no heartbeat is present, check that the power outlet is live. A blown fuse on the circuit
    board may indicate a defective CPU.
    Page 2213-102360 Rev. H
    Tone Commander 1030/1560 Installation Instructions
    Figure 7
    1. Install the handset cradle on the console
    using the screws provided. The cradle may
    be installed on either side of the console.
    2. Plug the handsets cable into the jack
    beneath the front left edge of the console.
    3. Plug one end of each supplied 6 conductor
    modular line cord into the voice/data and
    power jacks at the back of the console.
    If either line cord must be replaced, be sure
    to use one with 6 conductors. Many line
    cords with 6 position plugs have only 4
    conductors.
    4. Plug the cables into their associated wall
    jacks, or into the test jacks located on the
    CPU main circuit board (refer to Figure 5).
    CAUTION–Do notinterchange these two
    cables! The cable nearest the
    handset jack must connect to
    the voice/data wall jack or
    CPU jack.
    5. Fill out the keycap labels with line numbers,
    station names or numbers, and autodial
    numbers (refer to the configuration sheets).
    Place the labels beneath the clear plastic key
    caps, then snap the keycaps onto the DSS
    and line keys.
    (bottom view) 
    						
    							B. The console should emit two triple beeps, then briefly display 1030 OK or 1560 OK.
    If these indications are not observed, check both voice/data and power cabling.
    2. Repeat step 1 at attendant position #2, if the system is so equipped.
    C.O. Line Testing
    Perform the following tests on each telco/PABX line. Repeat at attendant position #2, if the system is so
    equipped.
    Line Access and Imbalance Testing
    1. Press the key representing the line to be tested.
    The associated line lamp (telephone symbol) should flicker while the line is accessed.
    NOTE– Open circuit voltage must be approximately 48 volts.
    2. Listen for audible hum or excessive noise.
    PA S S– Such noise or hum is not present.
    FAILURE– Such noise or hum is present.
    3. Listen for dial tone.
    PA S S– Dial tone is heard.
    FAILURE– Dial tone is not heard.
    4. Break dial tone by dialing a digit.
    PA S S- Dial tone is broken and no audible hum or excessive noise is heard.
    FAILURE- Dial tone cannot be broken; audible hum or excessive noise is heard.
    5. Press the RELEASE key.
    IMPORTANT– Upon the detection of any failure during the foregoing testing, disconnect the affected
    equipment from the telephone line to determine if such equipment is the cause of
    failure. Any equipment determined to be malfunctioning must remain disconnected, and
    use discontinued until the malfunction has been corrected.
    Hold and Autohold Testing
    1. Access the line to be tested and establish call to another station.
    2. Place the call on hold by depressing the red HOLD key.
    The associatedHindicator will wink slowly.
    3. Reseize the call by depressing the line key.
    The associatedHindicator goes out.
    The line lamp flickers while the line is accessed.
    4. Place the call on autohold by depressing another idle line key.
    The line accessed draws dial tone.
    The line under test goes to autohold.
    5. Release the line drawing dial tone and reseize, then release the line under test.
    13-102360 Rev. HPage 23
    Tone Commander 1030/1560 Installation Instructions 
    						
    							Ring Trip and Imbalance Testing
    1. Dial the number of the line to be tested from another station.
    The associated line lamp will flash slowly.
    or
    The associated line lamp will flash quickly, if the line has been optioned for ring delay.
    2. Press the line key to answer the call.
    The line lamp changes from flashing to flickering.
    3. Listen for audible hum or excessive noise.
    PA S S– Such noise or hum is not present.
    FAILURE– Such noise or hum is present.
    IMPORTANT– Upon detection of audible hum or excessive noise, disconnect the affected equipment
    to determine if such equipment is the cause of failure. Any equipment determined to be
    malfunctioning must remain disconnected, and use discontinued until the malfunction
    has been corrected.
    4. Press the RELEASE key.
    Page 2413-102360 Rev. H
    Tone Commander 1030/1560 Installation Instructions 
    						
    							CPU Option Switches
    Switches on the CPU control system programming and Night Service options. The switches are ON when
    set towards the right side of the CPU. When a programming option is locked, programming changes are
    not allowed. The switch location is shown in the figure below and on page 16.
    SWITCH FUNCTION
    1OFF – Autodial Program unlocked
    ON – Autodial Program locked
    2OFF – Configuration Program unlocked
    ON – Configuration Program locked
    3OFF – Name Program unlocked
    ON – Name Program locked
    4OFF – night transfer
    ON – night ringing
    5must be OFF!
    6, 7not used
    8OFF – retain new programming
    ON – restore defaults
    (when power is cycled off & on)
    Table 6 – CPU Option Switches
    13-102360 Rev. HPage 25
    Tone Commander 1030/1560 Installation Instructions
    Figure 8– CPU Option Switches and Fuses 
    						
    							Optional Equipment Installation
    The following options require system programming for proper operation. Refer to the Configuration
    Programmingsection.
    Night Service
    The console may either switch the telephone system to night transfer, or ring a night bell during incoming
    ringing when the attendant selects Night Service mode. Only one of these options may be installed.
    Option switch #4 on the CPU selects the Night Service mode. Set this switchOFFfor night transfer, orON
    for night ringing.
    Night Ringing
    Night ringing is switched on and off during ringing of either lines only, or lines and stations. One of these
    options must be selected during configuration programming.
    Tone Commanders PA-24 Paging/Chime Module provides a chime tone that can announce ringing calls
    over a paging system. This unit is powered from the 1030/1560 CPU. Refer to the PA-24 Paging/Chime
    Module Installation Instructions, doc. #13-102595.
    An external bell may be used in place of ringing over a paging system, as shown below.
    Page 2613-102360 Rev. H
    Tone Commander 1030/1560 Installation Instructions
    1. Install the night bell in the location desired by
    the customer.
    2. Run a two conductor cable from the night bell
    to the equipment room.
    3. Connect the cable to the bell.
    4. Mount a suitable bell power supply in the
    equipment room.
    5. Connect one output terminal of the power
    supply toNTCO(common) on the right side
    of CPU block #1.
    6. Connect one wire in the bell cable to the
    other output terminal of the power supply.
    7. Connect the remaining wire in the bell cable
    toNTNO(normally open).
    Figure 9 
    						
    							Night Transfer
    The night transfer leads from the telephone system remain connected together when the console is in Night
    Service mode, and during a power interruption at the CPU.
    Music On Hold
    An external music source is required for Music On Hold. It will be assigned to the lines during configuration
    programming. The music input may be connected to any type of compatible music source (refer to the
    Specifications
    section).
    The music source can be connected to the jack provided on the CPU, or punched down to the block.
    Jack Connections
    13-102360 Rev. HPage 27
    Tone Commander 1030/1560 Installation Instructions
    ConnectNTCO(common) andNTNC
    (normally closed) on the right side of CPU
    block #1 to the night control terminals on the
    telco/PABX block.
    Figure 10
    1. Connect an RCA-type phono plug to one end
    of a single conductor shielded cable, or
    obtain a cable with a plug attached. The
    center conductor connects to the pin of the
    plug.
    2. Plug the cable into the music input jack at the
    top of the CPU.
    3. Connect the other end of the cable to the
    output of the music source. A plug to fit the
    music source may be required.
    Figure 11 
    						
    							Block Connections
    Paging
    Tone Commanders PA-24 Paging/Chime module interfaces the 1030/1560 console to a paging system.
    The module includes a night ringing chime and switching for background music control. Power is derived
    from the 1030/1560 CPU.
    Paging can be connected to any spare line key on the 1030/1560. Refer to the PA-24 Paging/Chime
    Module Installation Instructions, doc. #13-102595.
    Page 2813-102360 Rev. H
    Tone Commander 1030/1560 Installation Instructions
    1. Connect a twisted wire pair toMH+andMH-
    on the right side of CPU block #1.
    2. Connect the other end of the wire pair to the
    output of the music source. A plug to fit the
    music source may be required.
    Figure 12 
    						
    							Configuration Programming
    Various network interface and operation parameters are programmable by the installer, allowing
    compatibility with a wide variety of central offices and PABXs. The system is pre-programmed at the
    factory; many installations will require few changes to these values. Programming is retained in the CPUs
    memory when power is disconnected.
    Systems with two attendant positions require programming at both consoles for recall rings and line privacy.
    The programming procedures for ring delays, the time of day clock, autodial numbers, and station names
    are described in their respective sections.
    The following features may be set from configuration programming mode by pressing the appropriate DSS
    key. The letters are printed on the console front panel beneath the DSS keys. Key numbers in parentheses
    represent the station ports assigned to the keys.
    System Programmable Features
    DSS Key
    Feature
    A (1) Abandoned Ring Time
    B (6) Recall Rings
    C (11) Pickup Code Sequence
    D (16) Dialing Speed
    E (21) Pause Time
    F (26) Hookflash Time
    G (2) Dial Tone Detect Time
    H (7) Hold Recall Time
    I (12) Hold Release Time
    J (17) Night Bell Mode
    * K (22) Queue Priority
    L (27) Alert Type
    * M (3) Ringing Type
    * N (8) Camp-On
    R (28) Assign Page Key
    T (9) Assign Night Key
    * U (14) Assign Quick Mode Key
    W (24) Unsupervised Call Transfer
    Line Programmable Features
    * O (13) Line Privacy
    * P (18) Answer Use
    Q (23) Assign Music On Hold to lines
    * Features marked with an asterisk have separate settings for each console position in a two-position
    system. They must be programmed individually at each console.
    13-102360 Rev. HPage 29
    Tone Commander 1030/1560 Installation Instructions 
    						
    							Using Configuration Programming Mode
    The configuration programming mode must be entered prior to attempting any of the following
    programming procedures.Enter this mode only when the console is idle, i.e., no calls are in progress or on
    hold and the time of day is displayed.
    The Configuration Program Lock Switch (switch #2) inside the CPU must beOFF(unlocked) before
    proceeding (see page 25).
    Toenterconfiguration programming mode:
    Press HOLD.
    Press TRANSFER.
    Press RELEASE.
    Press dial pad keyC(2).
    The display will indicate that configuration programming mode has been entered.
    Toexitconfiguration programming mode and store all programming:
    Press RELEASE.
    or
    The mode will be exited automatically 1 minute after the last keypress.
    When completed, set the Configuration Program Lock Switch inside the CPU toON(locked) to prevent
    inadvertent changes to the programmed settings.
    DSS keyson the console are used to select the feature to be programmed – letters identifying the keys are
    printed beneath the keys on the consoles front panel.
    Default Settings
    The default settings, as shipped from the factory, are listed with each feature on the following pages.
    Default settings may be recalled by setting CPU option switch #8 toON, then cycling the CPU power off
    and on (pull out the power plug for a few seconds).Set this switch back to OFF to prevent losing your
    programming during a power outage.
    The switch location is shown on page 25.
    Confirmation and Error Tones
    The speaker in the console signals correct or incorrect actions during programming. The consoles volume
    control adjusts the level of the tones – use the VOL keys above the dial pad.
    Confirmation Tone – double beep Error Tone – single beep
    Page 3013-102360 Rev. H
    Tone Commander 1030/1560 Installation Instructions 
    						
    All Tone Commander manuals Comments (0)

    Related Manuals for Tone Commander 1030/1560 Installation Instructions