Sanyo Denki Py 2 Manual
Have a look at the manual Sanyo Denki Py 2 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 550 Sanyo manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
9. SPECIFICATIONS 9-9 9.1.4 Precautions on Load (1) Negative load The Servo Amplifier cannot perform such negative load operation as causes the motor to rotate continuously. (Examples) • Downward motor drive (when no counterweight is provided). • Use like a generator, for example, the wind-out spindle of a winder. When applying the amplifier to a negative load, consult us. (2) Load inertia (JL) When the Servo Amplifier is used with a load inertia exceeding the allowable load inertia calculated in terms of the motor shaft, a main circuit power overvoltage detection or regenerative error function may be activated at the time of deceleration. In this case, the following measures must be taken. ① Lower the current limit. ② Make the acceleration/deceleration time longer (slow down). ③ Reduce the maximum motor speed to be used. ④ Install an external regenerative resistor (optional). For details, ask us for information.
9. SPECIFICATIONS 9-10 9.1.5 CN1 Input/Output Interface Circuit Configuration Input circuit configuration (1) Type 1 (photocoupler input) This type of input circuit is a contactless circuit like the one shown on the right. The input signals of type 1 are Servo ON, alarm reset, forward revolution inhibit, backward revolution inhibit, current limit permit deviation clear, proportional control, command multiplier, command pulse inhibit (zero clamp) and encoder clear (for absolute encoder). The applicable power supply is 5 V to 24 V. The user must prepare this power supply. Required power specifications: 5 to 24 VDC±10%, 100 mA minimum. (2) Type 2 (line driver input) This type of input circuit is like the one shown on the right. The applicable line receiver is equivalent to the 26LS32. This type permits only command pulse input of the position control type. This type can be connected to an open collector output. (3) Type 3 (analog input 1) This type of input circuit is like the one shown on the right. Type 3 permits only analog velocity and torque commands (torque compensation) as input signals. (4) Type 4 (analog input 2) This type of input circuit is like the one shown on the right. This type permits only current limit for both forward and backward revolution as input signals. (5) Type 5 (through input) This type of input circuit is like the one shown on the right. This type permits only battery power (for absolute encoder) as input signals. 0.01μF 6.8K 3.3K SG SG- + Forward revolution pulse Backward revolution pulse Connection example 3.3K1.8K 5.75K0.047μF -5V SG SG5V - + 5V -5V 5V to 24VDC 5mA 3.9K 2.2K 26LS32 or equivalent 100Ω 100Ω SG SG1K 3905V 5V 1.5K 1K CN2 CN1 1 2 + -
9. SPECIFICATIONS 9-11 Output circuit configuration (1) Type 6 (open collector output 1) This type of output circuit is an isolated contactless circuit like the one shown on the right. The signals of type 6 are current limit status, low velocity (deviation zero), start ready complete, holding brake excitation timing signal and alarm code. One of the two power supplies of 5 V and 12 V to 24 V can be selected (excluding input pins). The user must prepare these power supplies. Applicable power supply specifications: 5 VDC±10%, 20 mA minimum or 12 to 24 VDC±10%, 20 mA minimum. (2) Type 7 (open collector output 2) This type of output circuit is like the one shown on the right. This type permits only the C-phase encoder signal as output signals. (3) Type 8 (line driver output) This type of output circuit is like the one shown on the right. The line driver in use is equivalent to the 26LS31. The output signals of type 8 are A-, B- and C-phase encoder and absolute serial signals. (4) Type 9 (analog output) This type of output circuit is like the one shown on the right. The output signals of type 9 are monitor 1 and monitor 2. 26LS31 or equivalent 1KΩ SG SG- + Regulator +E12V to 24V max50mA(12 to 24V) max10mA(5V) 5V max 30V I O COM max 30V max10mA SG SG
9. SPECIFICATIONS 9-12 Type 1 Type 6 Type 2 Type 7 Type 3 Type 8 Type 4 Type 9 Type 5 Fig. 9-5 CN1 Circuit Type 26LS31 or equivalent 0.01μF 6.8K 3.3K SG SG - + 3.3K 1.8K 5.75K 0.047μF -5V SG SG 5V - + 5V -5V 5V to 24VDC 5mA 3.9K 2.2K 26LS32 or equivalent 100Ω 100Ω SG SG 1K 390 5V 5V 1.5K 1K 1KΩ SG SG- + 1 2 + - max50mA(12 to 24V) max10mA(5V) +E12V to 24VRegulator 5V max 30V I O COM max 30Vmax10mA SGSG
9. SPECIFICATIONS 9-13 9.1.6 Position Signal Output This section explains the position signal output specifications. Chapter Contents Relevant Sensors 9.1.6.1 Pulse output Fig. 9-6 Wiring-saved incremental encoder INC-E Request-signal unavailable absolute encoder ABS-E Request-signal available absolute sensor ABS-RⅡ Wiring-saved absolute sensor ABS-E.S1 9.1.6.2 Serial output (When absolute encoder ABS-E is used.) Fig. 9-7-1 Fig. 9-7-2 Fig. 9-7-3 Request-signal unavailable absolute encoder ABS-E 9.1.6.3 Serial output (When absolute sensor ABS-RⅡ is used.) Fig. 9-8-1 Fig. 9-8.2 Fig. 9-8-3 Request-signal available absolute sensor ABS-RⅡ 9.1.6.4 Serial output (When wiring-saved absolute sensor ABS-E.S1 is used.) Fig. 9-9-1 Fig. 9-9-2 Fig. 9-9-3 Wiring-saved absolute sensor ABS-E.S1 9.1.6.1 Pulse Output CN1-3 to 8 output 90° phase difference 2-phase pulses (A- and B-phases) and the home position (C-phase) pulse . Not specified for about 1s after the control power is turned on. 90° t Approx. 1s Not specified Not specified Not specified Control power supply A-phase B-phase C-phase B-phase leads A-phase by a phase angle of 90°.
9. SPECIFICATIONS 9-14 9.1.6.2 Serial Output (When the ABS-E Absolute Encoder Is Used) One of the two position signal outputs can be selected using the remote operator. When FUNC5 bit 7 on Page 6 in Mode 2 of the remote operator is set at 0, start-stop synchronization is selected. When bit 6 is set at 1, Manchester coding synchronization is selected. For details, refer to Func5 in 7.2.3 Parameter List. The specifications are as follows: (1) Output specifications (9600 bps • 1 Mbps) Table 9-2 (1) Start-stop Synchronization Output (9600 bps) Specifications Transmission system Start-stop synchronization Baud rate 9600 bps Number of transfer frames 6 frames (11 bits/frame) Transfer format See Fig. 9-7-1 Transmission error check (1 bit) even parity Transfer time 6.9 ms (Typ.) Transfer cycle 9.2 ms (See Fig. 9-7-3 (1).) Incremental direction Increased at forward revolution Table 9-2 (2) Manchester Coding Synchronization Output (1 Mbps) Specifications Transmission system Manchester coding synchronization Baud rate 1 Mbps Number of transfer frames 2 frames (25 bits/frame) Transfer format See Fig. 9-7-2. Transmission error check (3 bits) CRC error check Transfer time 66 µs (Typ.) Transfer cycle 84 µs±2 µs(See Fig. 9-7-3 (2).) Incremental direction Increase at forward revolution Forward revolution means counterclockwise rotation as viewed from the motor shaft. When the absolute value increases to the maximum, it returns to the minimum (0).
9. SPECIFICATIONS 9-15 (2) Transfer format (9600 bps • 1 Mbps) (2-1) Start-stop synchronization (9600 bps) ① Configuration in a frame 1 frame (11 bits) ↑ ↑↑ Start signal Position signal Address signal Parity signalStop signal (1bit) (5bit) (3bit) (1bit) (1bit) Fig. 9-7-1 (1) Frame Configuration of Start-stop Synchronization (9600 bps)(ABS-E) ② Configuration in each frame Start signal Position signal Address signal Parity signal Stop signal ・Frame 1 0 D0 D1 D2 D3 D4 0 0 0 0/1 1 (LSB) ・Frame 2 0 D5 D6 D7 D8 D9 1 0 0 0/1 1 ・Frame 3 0 D10 D11 D12 D13 D14 0 1 0 0/1 1 ・Frame 4 0 D15 D16 D17 D18 D19 1 1 0 0/1 1 ・Frame 5 0 D20 D21 D22 D23 BATE 0 0 1 0/1 1 (MSB) ・Frame 6 0 SOT 0 WAR 0 0 1 0 1 0/1 1 Fig. 9-7-1 (2) Transfer Format of Start-stop Synchronization (9600 bps)(ABS-E) D0 to D10 ................One-revolution absolute value D11 to D23 ..............Multi-revolution absolute value BATE ....................... Battery alarm SOT ......................... Absolute value range over WAR ........................ Battery warning
9. SPECIFICATIONS 9-16 (2-2) Manchester coding synchronization (1 Mbps) ① Configuration in a frame 1 frame (25 bits) ↑ ↑ ↑ ↑ ↑ ↑ Start signal MODEM address signal Position signal Frame address signalCRC signalStop signal (3 bit) (2 bit) (15 bit) (1 bit) (3 bit) (1 bit) Fig. 9-7-2 (1) Frame Configuration of Manchester Coding Synchronization (1Mbps) (ABS-E) ② Configuration in each frame Fig. 9-7-2 (2) Transfer Format of Manchester Coding Synchronization (1 Mbps) (ABS-E) 1 The first 2 bits of the start signal are output as a high (1) signal of the whole bit section. The remaining 23 bits are all Manchester coded. 2 D0 to D10........... One-revolution absolute value D11 to D23......... Multi-revolution absolute value BATE.................. Battery alarm SOT.................... Absolute value range over WAR................... Battery warning Data “0” Data “1” 1 01 0 Manchester code 1 1 1 0 0 D0 D1 D2 D3 D4 D5 D6 D7 D8 D9 D10 D11 D12 D13 D14 (LSB) 0 0/1 0/1 0/1 0 D15 D16 D17 D18 D19 D20 D21 D22 D23 BATE SOT 0 WAR 0 0 1 • Frame 1 • Frame 2 Position signal Frame address signal Start signal MODEM address signal CRC signal Stop signal Position signal Frame address signal (MSB) The start signal, MODEM signal, CRC signal and stop signal are the same as those in frame 1. ( 1)
9. SPECIFICATIONS 9-17 (3) Transfer cycle (9600 bps • 1 Mbps) (3-1) Start-stop synchronization (9600 bps) Fig. 9-7-3 (1) Transfer Cycle of Start-stop synchronization (9600 bps) (ABS-E) (3-2) Manchester coding synchronization (1 Mbps) Fig. 9-7-3 (2) Transfer Cycle of Manchester Coding Synchronization (1 Mbps) (ABS-E) The serial output is not specified for about 1 sec after the power is turned on. Communication does not always start with frame 1 in 1 sec. Approx. 1s Control power supply Not specified Serial output Serial transfer H H H 1 23456 12345 6 Approx. 6.9 ms Approx. 9.2 ms Approx. 6.9 ms Approx. 1.1 ms Frame 1 Frame 2 Frame 3 Frame 4 Frame 5 Frame 6 Serial output Frame 2 Frame 1 Frame 2 25 µs 25 µs 16 µs 84 µs±2 µs Frame 1
9. SPECIFICATIONS 9-18 9.1.6.3 Serial Output (When the ABS-RⅡ Absolute Sensor Is Used) One of the two position signal outputs can be selected using the remote operator. When FUNC5 bit 7 on Page 6 in Mode 2 of the remote operator is set at 0, start-stop synchronization is selected. When bit 6 is set at 1, Manchester coding synchronization is selected. For details, refer to Func5 in 7.2.3 Parameter List. The specifications are as follows: (1) Serial output specifications Table 9-3 (1) Start-stop Synchronization Output (9600 bps) Specifications Transmission system Start-stop synchronization Baud rate 9600 bps Number of transfer frames 6 frames (11 bits/frame) Transfer format See Fig. 9-8-1. Transmission error check (1 bit) even parity Transfer time 6.9 ms (Typ.) Transfer cycle 9.2 ms (See Fig. 9-8-3 (1).) Incremental direction Increased at forward revolution Table 9-3 (2) Manchester Coding Synchronization Output (1 Mbps) Specifications Transmission system Manchester coding synchronization Baud rate 1 Mbps Number of transfer frames 2 frames (25 bits/frame) Transfer format See Fig. 9-8-2. Transmission error check (3 bits) CRC error check Transfer time 66 µs (Typ.) Transfer cycle 84 µs±2 µs(See Fig. 9-8-3 (2).) Incremental direction Increase at forward revolution Forward revolution means counterclockwise rotation as viewed from the motor shaft.