9. SPECIFICATIONS 9-149 Table 9-26-2 Output when overload warning is ineffective (e.g. OLWL = 100%) (Alarm output sequence =BIT *²) CN-1 pin number for alarm output Estimated motor temperature 7-segment LED display 46 (ALM8)45 (ALM4)44 (ALM2)43 (ALM1)Abbreviation Alarm/Warning Name Up to 80% of overload alarm level 80% or above up to 100% of overload alarm level -- 0 0 0 0 -- No alarm No warning 100% or above of overload alarm level 1 1 1 1 OL Overload alarm...
Page 332
10. INTERNATIONAL STANDARDS 10-1 INTERNATIONAL STANDARDS 10.1 International Standard Compliance .............................................. 10-2 10.1.1 Working Environment...................................................... 10-2 10.1.2 Power Supply................................................................... 10-2 10.2 CE Marking .................................................................................. 10-3 10.2.1 The CE Marking Conformity...
Page 333
10. INTERNATIONAL STANDARDS 10-2 10.1 International Standard Compliance The PY2 Servo Amplifier complies with the following international standards. International standardStandard No. TÜV EN50178 UL UL508C CUL UL508C Low Voltage Directive EN50178 EMC Directive EN55011 10.1.1 Working Environment Since the working environment for the PY2 Servo Amplifiers must be pollution level 2 or above (i.e. level 1 or 2) as specified in EN50178, make sure to use them in a pollution level...
Page 334
10. INTERNATIONAL STANDARDS 10-3 10.2 CE Marking At Sanyo Denki, we are executing tests on the PY2 Servo Amplifier for compliance with the CE marking at qualifying institutions. The CE mark is required to be attached all end products sold in EU countries. Only products conforming to the safety standards are permitted to have them. Accordingly, customers are requested to perform the final conformity test on their machines or systems incorporating our amplifiers. 10.2.1 The CE...
Page 335
10. INTERNATIONAL STANDARDS 10-4 10.2.2 How to Install the EMC PY2A (Note 1) Noise filter (Note 2) Zero-phase reactor (Note 3) Cable clamp POWER SELECT COM W U V P S Tt R rN 感 電 注 意 UWV T N P COM 感 電 注 意 POWER SELECTRSt r CN D MotorSensor signal CN 2 L3 PEL1 L2L3T L2 L1 S RMC MC MCT S R r t(Note 1) (Note 2) Connect to CN1 Connect to the PE (protective earth) terminal ( ) (Note3) (Note3) (Note3) (Note3)
Page 336
10. INTERNATIONAL STANDARDS 10-5 10.2.3 Structure of the Control Panel 1. A metallic material is used for the control panel and its cover. 2. The joint of the roof and the side board shall be masked and welded. 3. The joint fixed with screws shall be welded to prevent noise from leaking from the gap in the joint. 4. In case of fixing with screws or spot welding, the welding space shall be within 10 cm. 5. Use an EMI gasket to prevent clearance between the cover and the control panel. 6....
Page 337
10. INTERNATIONAL STANDARDS 10-6 10.2.4 Installation Inside the Control Panel 1. Install the noise filter frame on the control panel. 2. Apply a coating mask on the control panel where the noise filter is installed. 3. The Servo Amplifier box must be grounded. 4. Perform coating mask on the control panel where the Servo Amplifier is installed. Control panel Control panel Servo Amplifier Coating mask Coating mask Noise filter
Page 338
10. INTERNATIONAL STANDARDS 10-7 10.2.5 Wiring 1. The motor power line shall be clamped on both the control panel and Servomotor sides. 2. The sensor signal line shall be clamped on both the control panel and the Servomotor sides. 3. Perform wiring of the motor power and sensor signal lines separately. 4. Install the clamp with a metal screw directly using a metal conductive P or U clip. 5. Do not clamp by soldering the power line to the shield....
Page 339
10. INTERNATIONAL STANDARDS 10-8 6. Wind the zero-phase reactor four turns around the primary side of the noise filter. 7. Perform wiring from the secondary side of the noise filter to the Servo Amplifier, keeping it as short as possible. 8. The wiring for the primary and secondary sides of the noise filter must keep a certain distance apart. Four turns Primary side Noise filter Secondary side Servo Amplifier
Page 340
10. INTERNATIONAL STANDARDS 10-9 10.2.6 Parts for EMC Countermeasures We recommend the following parts for EMC countermeasures. Noise filter Model Maker Specifications RF3020-DLC RASMI ELECTRONICS LTD. Rated voltage: Line-Line 440 - 550V Rated current: 20 A 3SUP-HK30-ER-6B Okaya Electric Industry Co., Ltd.Rated voltage: Line-Line 550V Rated current: 30 A Zero-phase reactor Model Maker Specifications RZR-6020N Okaya Electric Industry Co., Ltd.1 kHz - 100 kHz 6.9 to...