Home > Samsung > Home Theater System > Samsung Ht As700 User Manual

Samsung Ht As700 User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Samsung Ht As700 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1705 Samsung manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							81
    I / O  ch e ck  f l ow  ch a r t
    This page presents an example of a 
    troubleshooting procedure based 
    on the right circuit. 
     
    						
    							82
    External environment check flow chart
     
    						
    							83
    Inspection and Maintenance
    Inspection and maintenance
    Input module
    SymptomPossible causeAction
    Power supply LED will not 
    illuminate. Fuse blows Replace the fuse
    Fuse blows frequently. Short circuit or defective partReplace the power supply or the 
    CPU module
    Run LED will not illuminate.Program errors Correct the program
    Power line defect Replace the CPU module
    Output will not turn to On state 
    during Run.Short or open circuit Replace the CPU module
    I/O modules above a certain 
    address will not operate.I/O bus error Replace the backplane module
    Input or output module of only 
    certain address will turn to On 
    state.I/O bus error Replace the backplane module
    Not all contacts on an output 
    module operate properly.I/O bus error Replace the backplane module
    SymptomPossible causeAction
    No inputs on an input module will 
    turn On (LEDs are not illuminated).No external input power Supply power
    Low external input voltage Supply rated load power
    Loose terminal screw or defective 
    contactTighten the screw and reconnect 
    the module
    Inputs will not turn to On state 
    (LEDs are illuminated).Defective input circuit Replace the input module
    Inputs will not turn to Off state. Defective input circuit Replace the input module
    One or more inputs on an I/O 
    module will not turn On.Device connected to the input 
    module is defective.Replace the input device
    Loose input wiring Reconnect the input wiring
    External input time is too short. Adjust the input module
    Loose terminal screw or defective 
    contactTighten the screw and reconnect 
    the module
    One or more inputs on an I/O 
    module will not turn Off.Defective input circuit Replace the input module
    Input changes On/Off state 
    erratically.Low external input voltage Supply rated input voltage 
    Noise error  Troubleshoot for noise
    Loose terminal screw or defective 
    contactTighten the screw and reconnect 
    the module
    Input display LED will not 
    illuminate (input is On in PLC). LED error  Replace the input module
     
    						
    							84
    Output module
    SymptomPossible causeAction
    No outputs on an output module 
    will turn On.No external input power Supply power
    Low external input voltage Supply rated load power 
    Loose terminal screw or defective 
    contactTighten the screw and reconnect 
    the module
    Defective I/O connector contacts Replace the output module
    Defective output circuit Reconnect the output module
    No outputs on an output module 
    will turn Off.Defective output circuit Replace the output module
    One or more inputs on an I/O 
    module will not change to On state 
    (LED is illuminated).Output time too short Correct the program
    Defective output circuit Replace the output module 
    One or more inputs on an I/O 
    module will not change to On state 
    (LED is not illuminated).Incorrect output load Replace the output load
    Short output wiring Reconnect the output wiring
    Loose terminal screw or defective 
    contact Tighten screw and reconnect the 
    module
    Defective output contact  Replace the output module or relay 
    Defective output circuit Replace the output module 
    One or more outputs on an I/O 
    module will not change to On state 
    (LED is illuminated).Defective output circuit Replace the output module or relay
    Error caused by leak or residual 
    currentReplace the external load 
    One or more outputs on an I/O 
    module will not turn Off (LED is not 
    illuminated).Defective output circuit Replace the output module
    Output changes On/Off state 
    erratically.Low external input voltage Supply rated load power
    Noise error  Countermeasure against noise 
    Loose terminal screw or defective 
    contact Tighten the screw and reconnect 
    the module
    A set of 8 points on an I/O module 
    operate incorrectly or identically. Loose common terminal screw Tighten the screw and reconnect 
    the module
    Defective terminal connectorTighten the screw and reconnect 
    the module
    CPU module error  Replace the CPU module
    Output display LED is not 
    illuminated.LED error Replace the output module
     
    						
    							85
    Periodic inspection and maintenance items
    The NX-CPU700p controller requires periodic inspection and 
    maintenance for proper operation. The following items should be 
    checked every six months, but the period can be shortened according 
    to the operational environment. 
    Precautions when troubleshooting
    • Always turn off the power whenever installing or removing modules.
     Check the module once more before replacing the defective part.
     Return the defective module for repair with any detailed information 
    about its problems. 
     When a contact is defective, clean the contact with a clean cotton and 
    alcohol and then retest the module. 
     Do not use thinner to clean since it might cause discoloration on the 
    module’s case.
    ItemCheck itemRequirementRemarks
    Supplied powerDoes the voltage measured within the 
    power terminal fall within the specified 
    range?Voltage must be within the 
    power module input voltage 
    specifications. Vo l t m e t e r
    EnvironmentDoes the temperature fall within the 
    specified range?0 to 55 °C Thermometer
    Does the humidity fall within the 
    specified range? 35 to 85%RH Hygrometer
    Is there any dust present? No dust Visual
    I/O powerDoes the control voltage supplied to the I/
    O modules fall within the specified limit? Control voltage must be 
    within the input and output 
    modules specifications. Vo l t m e t e r
    Module 
    mounting and 
    wiring Are all modules firmly mounted?
    All should be firmly secured. Screwdriver Is the connection cable firmly wired?
    Is the external wiring screw tight? 
    Life expectancy 
    of partsContact relayElectric lifetime: 
    100,000 to 300,000 operations 
    Battery 3 years at 25 °C
     
    						
    							87
    6
    Programming Instructions
    Refer to the NX7/NX70/NX700 Instruction Set Reference Manual for detailed 
    information on the NX7, NX70, and NX700 instruction set and for application 
    examples to show the instruction set in use.
    Basic Sequence Instructions
    MnemonicNameLadder SymbolDescription
    STR Start Starts contact A.
    STN Start Not Starts contact B.
    AND And Contact A series circuit
    ANN And Not Contact B series circuit
    OR Or Contact A parallel circuit
    ORN Or Not Contact B parallel circuit
    OUT Out Arithmetic result output
    SET Set Sets output and retains On.
    RST Reset Resets output and retains Off.
    NOT Not Inverts circuit.
    STR DIF Start Differential Starts rising edge contact             .
    STR DFN Start Dif. Not Starts falling edge contact  .
    AND DIF And Dif. Rising edge series connection 
    AND DFN And Dif. Not Falling edge series connection 
    OR DIF Or Dif Rising edge parallel connection 
    OR DFN Or Dif. Not Falling edge parallel connection 
    ANB And Block Circuit blocks series connection.
    ORB Or Block Circuit blocks parallel connection.
    MS Master block SetStarts master block.
    (for processor version 2.0 or higher)
    MR Master block ResetEnds master block.
    (for processor version 2.0 or higher)
    MCS Master Control Set Starts circuit branch.
    MCR Master Control Reset     Ends circuit branch.
    - ExtensionExtension (Used in pairs with AND condition 
    when extending. Exclusive for WinGPC, 
    GPC5, etc)
     (    )
    (    )
     (    )
    (    )
    (    )
    (OUT) 
    (SET) 
    (RST)
    R
    F
    R
    F
    R
    F
    (MS) 
    (MR)
    >>
    IMPORTANT
    (    )
     
    						
    							88
    Input
    Output
    Timer, Counter and Shift Register 
    Instructions
    MnemonicNameLadder 
    SymbolDescriptionRemarks
    TIM On Delay TimerTurns on after set delay 
    time from input on
     Time base: Ch 0 to 63 = 0.01s
    Ch 64 to 255 = 0.1s
    Setting range: SV = 0 to 65535
    Contact indicator: TC + channel 
    number
    TOF Off Delay TimerTurns off after set delay 
    time from input offTime base: Ch 0 to 63 = 0.01s
    Ch 64 to 255 = 0.1s
    Setting range: SV = 0 to 65535
    Contact indicator: TC + channel 
    number
    SSTSingle Shot 
    TimerTurns off after set delay 
    time from input onTime base: Ch 0 to 63 = 0.01s
    Ch 64 to 255 = 0.1s
    Setting range: SV = 0 to 65535
    Contact indicator: TC + channel 
    number
    UCUp CounterUp counter
    Channel range: Ch 0 to 255 
                       (Shared with timer)
    Setting range: SV = 0 to 65535
    Contact indicator: TC + channel 
    number
    DC Down CounterDown counter
    Channel range: Ch 0 to 255 
                       (Shared with timer)
    Setting range: SV = 0 to 65535
    Contact indicator: TC + channel 
    number
    RCT Ring CounterRing counter
    Channel range: Ch 0 to 255 
                       (Shared with timer)
    Setting range: SV = 0 to 65535
    Contact indicator: TC + channel 
    number
    UDCUp-Down 
    CounterUp-Down counterChannel range: Ch 0 to 255 
                       (Shared with timer)
    Setting range: SV = 0 to 65535
    Contact indicator: TC + channel 
    number
    SR Shift RegisterShift RegisterUsable address areas for Sb and 
    Eb : M, K
    1 bit shift on each p input.
    Stores the status value I in Sb for 
    every P input.
    Max. number of instructions: 256 
     SST 
    Ch=00100
    SV=00005Input
    Output
     TIM 
    Ch=00010
    SV=00050Input
    Output
     TOF 
    Ch=00064
    SV=00005
     UC 
    U Ch=020 
    SV=004 
     
    R  
     DC 
    D Ch=021 
    SV=005 
     
    R  
     RCT 
    T Ch=022 
    SV=004 
     
    R  
     UDC 
    U Ch=023
    SV=003
    D  
     
    R 
     SR 
    I Sb=K1.4
    Eb=K2.5
    P  
     
    R 
    Input
    Current 
    value
    Output
    ResetSet 
    value
    Input
    Current 
    value
    Output
    ResetSet value
    Input
    Current 
    value
    Output
    ResetSet value
    U Input
    D Input
    Current 
    value
    ResetSet value
    value
     
    						
    							89
    Comparison Instructions
                  For double word comparison instructions, the letter D should precede the word comparison instructions in the 
    Mnemonic program.
    Substitution, Increment and Decrement 
    Instructions
    MnemonicNameWord ladder 
    symbolDouble word 
    ladder symbolDescription
    STR ==
    AND ==
    OR ==START ==
    AND ==
    OR ==On if A is equal to B.
    A and B are word/double word or 
    data value.
    STR 
    AND 
    OR START 
    AND 
    OR   On if A is not equal to B. 
     is same with 
    ≠.
    A and B are word/double word or 
    data value.
    STR >
    AND >
    OR >START >
    AND >
    OR >On if A is greater than B.
    STR >=
    AND >=
    OR >=START >=
    AND >=
    OR >=On if A is equal to or greater than B.
    STR 
    						
    							90
    Arithmetic Instructions
    MnemonicNameWord ladder 
    symbolDouble word 
    ladder symbolDescription
    ADD 
    (DADD)Decimal additionD = S1 + S2 
    (Decimal operation)
    ADDB 
    (DADDB)BCD additionD = S1 + S2 
    (BCD operation)
    SUB 
    (DSUB)Decimal 
    subtractionD = S1 - S2 
    (Decimal operation)
    SUBB 
    (DSUBB)BCD subtractionD = S1 - S2 
    (BCD operation)
    MUL 
    (DMUL)Decimal 
    multiplicationD = S1 x S2 
    (Decimal operation)
    MULB 
    (DMULB)BCD multiplicationD = S1 x S2
    (BCD operation)
    DIV
    (DDIV)Decimal divisionD = S1/S2  (Decimal operation), 
    Error when S2= 0
    DIVB 
    (DDIVB)BCD divisionD = S1/S2  (BCD operation)
    Error when S2 = 0
    ADC 
    (DADC)Decimal addition 
    with carryD = S1 + S2 + CY  
    (Decimal operation, include carry)
    ADCB 
    (DADCB)BCD addition with 
    carry D = S1 + S2 + CY  
    (BCD operation, include carry)
    SBC 
    (DSBC)Decimal 
    subtraction with 
    carry D = S1 - S2 – CY 
    (Decimal operation, include carry)
    SBCB 
    (DSBCB)BCD subtraction 
    with carry D = S1 - S2 - CY  
    (BCD operation, include carry)
    ABS 
    (DABS)Absolute valueD = |D|  
    (Absolute value operation)
    WNOT 
    (DNOT) NOT 
    (1’s complement)Store 1’s complement of D in D 
    NEG 
    (DNEG)Negative 
    (2’s complement)Store 2’s complement of D in D
    (1’s complement + 1) (- Result)
     
    						
    All Samsung manuals Comments (0)

    Related Manuals for Samsung Ht As700 User Manual