Samsung Ht As700 User Manual
Have a look at the manual Samsung Ht As700 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1705 Samsung manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
51 BCD (Binary Coded Decimal) BCD is used to express a decimal digit (0 to 9) using 4 bits. Conversion of BCD values can be done in hexadecimal calculations. Flash ROM It refers to a ROM (EEPROM) that stores programs. Since its contents can be deleted periodically, it is frequently used for equipments that deals with programs such as a PLC. How to use a register R (Relay) register (Can be bit, word or double word) Indicates the external I/O register that directly connects to the general I/O module M (Memory) register (Can be bit, word or double word) An internal bit memory address which supports the relay of logical operations. It is used as a word or double-word variable for general calculations and programs. When the power of the PLC is turned off or the CPU has stopped, the register value is reset to 0. W (Word) register (Can be bit, word or double word) Same usage as M registers. The value is preserved after the power is turned off, but can be cleared by program downloads or special command words. Not used as a bit (register only for word use) K (Keep) register (Can be bit, word or double word) Used for general calculation programs. The value is preserved after the power is turned off. F (Flag) register (Only process bit) These bit registers provide special application specific functions to the programmer of the PLC. They are also used as system control bits, providing Run/Stop control of the PLC. When a calculation or input value exceeds 65,535 (FFFF) Use a double word instruction that can store and calculate values over 65,535 in the K, M, R, and W registers. When a double word instruction is used, it can represent values up to 4,294,967,295 (2 32). When you want to reload the contents or values that you worked today Use the K and W area. These are preserved unless specifically erased. The W area is erased by special instructions or program downloads. When you need numerical expressions such as A+B=C, 34 × 45=D, A1>C1. Use the R, M, W, and K area. If you use the R area, you can refer to and output calculated values in I/O modules. NOTE Example: 59 (BCD) = 59 (HEX), 32 (BCD) = 32 (HEX)
52 For bit operations, such as setting, resetting, shifting, or rotating Use the M, K, and R area. You cannot perform bit operations in the W area. When you want to refer to or modify the set value of the timer or counter. Refer to or modify W2048 to W2303 or SV0 to SV255. When you want to refer to or modify the present value of the timer or counter. Refer to or modify the address area from W2304 to W2559 or from PV0 to PV255. The value holds true in STOP (PROG.) state in this area. The present value (PV) of the counter is maintained even after the power is off. Processor Operation Mode What is the Processor operation mode? The processor has an external RUN/REMOTE/PROG switch. The PLC performs a system check that determines the position of the switch. The switch position determines which operating mode the PLC is in. It can set to RUN, STOP, REMOTE, or ERROR mode. The PLC reads the external contact signals in Run mode and executes the user program stored in RAM. The external outputs are updated every scan according to program results. The user program is stopped and the external outputs are turned Off. In the Stop mode, you may correct, delete or transfer the program.(This is the only mode in which you can save a program in flash memory.) A user program is operated at every scan and the I/O and result value is maintained. This mode is used when checking and debugging a program at every scan. This mode is similar to the Stop mode, but it does not initialize data. It occurs when the CPU module finds internal defects after running the self-diagnoses. Functions are not executed normally in this mode. When an error occurs, the CPU stops all programs and turns all output off. When an Error mode occurs, the user should check the error code and take appropriate measures. Then turn the power on or put the mode conversion switch in Prog and press the Initialize Key to clear the error. RUN Mode (operating) STOP Mode PAUSE Mode ERROR Mode
53 Allowed Functions in Operation Modes 5=On, ◑=Flashing, ●=Off When the PROG.LED is on, you can change the user program. The INITIALIZE switch clears errors when the mode switch is set to PROG. When the mode switch is set to REMOTE and power is switched from Off to On, the previous mode of operation is restored. When debugging the user program, the mode switch should be set to REMOTE. Processor Processing Procedure Program processing procedure Program analysis Executes the program from its first step to its final step and stores the internal/external output in the working RAM. Peripheral device signal processing Stores data from the communication module or peripheral device to the internal memory. Forced I/O processing Turns on/off forced I/O bits, if any. I/O processing Preserves the On/Off state of the external I/O and uses it as an input in the next scan. (For accurate processing, input should continue for more than 1 scan time.) The processed program outputs are sent from internal memory to the external memory. Operation mode selector switchOperation modeLED status RUN LED PROG LEDProgram chang eData ch a n g eInitialize switch is enabledMode at power off-on RUNRUN 5 ●Disallowed Allowed ○Run STOP ● 5Allowed Allowed ○Run REMOTERUN 5 5Allowed Allowed ○Run PA U S E ◑ 5Allowed Allowed ○Pause PROG STOP ● 5Allowed Allowed ○Stop Program analysis The diagram indicates the PLC program processing procedure. The CPU regularly repeats procedure 1 through 5. This cycle is called 1 scan time. 1 scan timePeripheral device signal processing Forced I/O Process I/O Watchdog time -> 0
54 Watchdog time initialization The watchdog elapsed time value is set to 0. (This value is the watchdog calculation point until the next scan.) The following illustration shows the difference between the relay board and PLC sequence processing. The relay carries out all sequences simultaneously while the PLC processes sequentially throughout the program. Processing of relay sequence (Parallel process)Processing of PLC program (Serial process)
55 4 Installation and Wiring Installation Installation space and environment External dimensions (mm) unit (mm) 3-slot type5-slot type8-slot type10-slot type12-slot type A (mm) 205.0 276.0 381.0 452.0 522.0 B (mm) 183.8 254.2 359.8 430.2 500.6
56 Installation location Be sure to maintain a sufficient distance from wiring ducts, and other machines below and above the module for proper ventilation. Do not install the modules stacked up or horizontally. Doing so will prevent proper cooling of the module and cause overheating inside the PLC (programmable controller). Do not install the module above devices which generate heat such as heaters, transistors or large scale resistors. In order to eliminate any effects from noise emission, power wires and electromagnetic devices should be kept at least 100 mm away from the surfaces of the module. When installing the module behind the doors of the operation panel, be especially careful to maintain these distances. Space for programming tool connection Leave a space of at least 180 mm from the mounting surface for programming tool connections and wiring. Duct 50mm or more Duct 50mm or more 50mm or more DuctPLC body Other equipmentsDoor of the panel 50mm or more 100mm or more Programming cable Approx. 180mmApprox. 110mm
57 Avoid installing the module in the following conditions Ambient temperature outside the range of 0 to 55 °C Ambient humidity outside the range of 30 to 85% RH Sudden temperature changes causing condensation Inflammable or corrosive gases Excessive airborne dust, metal particles, salinity Benzene, thinner, alcohol, other organic solvents or strong alkaline solutions such as ammonia or caustic soda Excessive vibration or shock Direct sunlight Location near high-tension wires, high-voltage devices, power cables, power devices, or other devices with generate large power surges or electronic fields when starting and stopping (esp. if within 100 mm) Power Supply Module Wiring Power supply module wiring The output voltage of a power supply should be within the allowed voltage Power supply unit terminal screw NUse M3.5 screw for terminal. NX700 POWER Use cables thicker than 2mm 2 and make them into twisted pair wires. Use insulation transformer when there is excessive noise. For grounding, use cables thicker than 2mm 2. Brake (NX-POWER) Service power (24V) Supplying 24V to I/O units. However, avoid parallel connection with another 24V source or other different ATTENTION Product nameRated input voltageAllowed voltage range NX-POWER11 0-220V AC85-264V AC
58 NIt is recommended that you use crimped terminal for wiring. Use 2mm2 twisted pair cable or larger Use power supply wire that is thicker than 2mm2 to minimize voltage drops. Use twisted pair cable to minimize noise effects. Proper compressed connection terminal Circular type terminal (O type Lug) Circular type terminal with insulation resistance Open type terminal (Y type Lug) Power supply system Use separate wiring systems for the PLC module, I/O module, and power supply module as shown in the following diagram. Use isolation transformer for noisy environments Use a low noise power supply. Use an isolation transformer to reduce the noise as illustrated above. NOpen type terminalNCircular terminal 7. 0 m m or less 7. 0 m m or less Φ3.7 to Φ4.3 hole Motor device External I/O device Insulation Insulation transformer Insulation transformer
59 Grounding Ground the PLC for noisy environments Connected to the metal part of backplane, the frame ground terminal is connected to a solid earth ground. Use ground wires with a minimum of 2mm 2 and the triple grounding connection which has a resistance of less than 100 Ω. The point of grounding should be as close to the PLC as possible and the ground wire should be as short as possible. If two devices share a single ground point, it may produce an adverse effect. Always use an exclusive ground for each device. Other devices including Other devices including
60 Input and Output Wiring Input wiring Checkpoints for input module wiring There can be limits on the number of points that can be simultaneously turned on, based on the module type. Check such limits in the specifications of each input module. In particular, be careful when using in high ambient temperature. The connection method for each type of input device including sensor is described below. Photoelectric sensors and proximity sensors Relay output type 2 wired type Internal CircuitInput terminal COM terminal Sensor Input Sensor powerSensor DC input unit Sensor DC input unitpower Input terminal COM terminal Input power Internal Circuit NPN open collector output type PNP open collector output type Sensor output Internal Circuit Sensor DC input unit Input terminal COM terminal Input power Sensor Internal Circuit DC input unit COM terminal Input terminal Input power Voltage output type Internal Circuit Sensor DC input unit Input terminal COM terminal Input power Sensor output