Panasonic Cu 3ks19nbucu 4ksxxnbu Technical Service Manual
Have a look at the manual Panasonic Cu 3ks19nbucu 4ksxxnbu Technical Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
9-3. Tools Specifically for R410A For servicing, use the following tools for R410A Gauge manifold Charging hose Gas leak detector Refrigerant cylinder Charging cylinder Refrigerant recovery unit Vacuum pump with anti-reverse flow (*1) (Solenoid valve-installed type, which prevents oil from flowing back into the unit when the power is off, is recommended.) Vacuum pump (*2)...can be used if the following adapter is attached. Vacuum pump adapter (reverse-flow prevention adapter) (*3). (Solenoid valve-installed adapter attached to a conventional vacuum pump.) Electronic scale for charging refrigerant Flare tool Bender Torque wrench Cutter, reamer Welding tool, nitrogen gas cylinder Tools specifically for R410ATool Distinction Tool Name Tools which can be com- monly used for R22, R407C, and R410A CAUTIONThe above tools specifically for R410A must not be used for R22 and R407C. Doing so will cause malfunction of the unit. For the above vacuum pump (*1, *2) and vacuum pump adapter (*3), those for R22-type units can be used for R410A-type. However, they must be used exclusively for R410A and never alternately with R22 and R407C. For details on tubing installation procedures, refer to the installation manuals attached to the indoor unit and outdoor unit. To prevent other refrigerants (R22, R407C) from being mistakenly charged to this unit, shape and external diameter of the service port screw has been altered. R410A : 5/16" R22, R407C : 1/4" 9-4. Tubing Installation Procedures When the tubes are connected, always apply HAB oil on the flare portions to improve the sealing of tubing. The following is the HAB oil generally used: Esso: ZERICE S32 NOTE 81
9-5. In Case of Compressor Malfunction CAUTIONShould the compressor malfunction, be sure to make the switch to a replacement compressor as quickly as possible. Use only the tools indicated exclusively for R410A. See "9-3. Tools Specifically for R410A." 9-5-1. Procedure for Replacing Compressor (1) Recovering refrigerant Any remaining refrigerant inside the unit should not be released to the atmosphere, but recovered using the refrigerant recovery unit for R410A. Do not reuse the recovered refrigerant, since it will contain impurities. (2) Replacing Compressor Soon after removing seals of both discharge and suction tubes of the new compressor, replace it quickly. (3) Checking for sealing Use nitrogen gas for the pressurized gas, and never use a refrigerant other than R410A. Also do not use oxygen or any flammable gas. (4) Evacuation Use a solenoid valve-installed vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption, the valve will prevent the pump oil from flowing back. The equipment may be damaged if moisture remains in the tubing, thus carry out the evacuation thoroughly. When using a vacuum pump with exhaust air volume more than 0.883 cu.ft./min. and ultimate vacuum pressure rate of 50 micron Hg. Standard time for evacuation (1) Recover refrigerant OK (2) Replace compressor OK (3) Check for sealing OK (4) Evacuation OK (5) Recharge Length of tubing Evacuation timeLess than 33 ft. (10 m) More than 10 minutesMore than 33 ft. (10 m) More than 15 minutes 82
Valve Single valve Charge liquid refrigerant with cylinder in up-side-down position. Single valve (with siphon tube) Charge with cylinder in normal position.Liquid Valve Liquid Charging cylinder Open Refrigerant cylinder Liquid NO! CAUTIONNever charge a large amount of liquid refrigerant at once to the unit. This may cause damage to the compressor. CAUTIONTo prevent the composition of R410A from changing, never bleed the refrigerant gas into the atmosphere while transferring the refrigerant. (Fig. 3) (5) Recharging Be sure to charge the specified amount of refrigerant in liquid state using the service port of the wide tube service valve. The proper amount is listed on the unit's nameplate. When the entire amount cannot be charged all at once, charge gradually while operating the unit in Cooling Operation. When charging with a refrigerant cylinder, use an electronic scale for charging refrigerant. In this case, if the volume of refrigerant in the cylinder becomes less than 20% of the fully-charged amount, the composition of the refrigerant starts to change. Thus, do not use the refrigerant if the amount in the charging cylinder is less than 20%. Also, charge the minimum necessary amount to the charging cylinder before using it to charge the air conditioning unit. Example: In case of charging refrigerant to a unit requiring 1.68 lb. (0.76 Kg) using a capacity of a 22 lb. (10 Kg) cylinder, the minimum necessary amount for the cylinder is: 1.68 + 22 0.20 = 6.08 lb. (0.76 + 10 0.20 = 2.76 Kg) For the remaining refrigerant, refer to the instructions of the refrigerant manufacturer. If using a charging cylinder, transfer the specified amount of liquid refrigerant from the refrigerant cylinder to the charging cylinder. Prepare an evacuated charging cylinder beforehand. Do not use the refrigerant if the amount in the charging cylinder is less than 20%. Configuration and characteristics of cylinders Fig. 1 Fig. 2 Fig. 3 83
Length of tubing Evacuation timeLess than 33 ft. (10 m) More than 10 minutesMore than 33 ft. (10 m) More than 15 minutes 9-6. In Case Refrigerant is Leaking CAUTIONNever attempt to charge additional refrigerant when refrigerant has been leaking from the unit. Follow the procedure described below to locate points of leaks and carry out repairs, then recharge the refrigerant. (1) Detecting Leaks Use the detector for R410A to locate refrigerant leak points. (2) Recovering refrigerant Never release the gas to the atmosphere; recover residual refrigerant using the refrigerant recovery unit for R410A, instead. Do not reuse the recovered refrigerant because its composition will have been altered. (3) Welding leaking points Confirm again that no residual refrigerant exists in the unit before starting welding. Weld securely using flux and wax for R410A. Prevent oxide film from forming inside the tubes utilizing substitution with nitrogen (N2) in the refrigerant circuit of the unit. Leave ends of tubes open during welding. (4) Checking for sealing Use nitrogen gas for the pressurized gas, and never use a refrigerant other than R410A. Also do not use oxygen or any flammable gas. (5) Evacuation Use a solenoid valve-installed vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption, the valve will prevent the pump oil from flowing back. The equipment may be damaged if moisture remains in the tubing, thus carry out the evacuation thoroughly. When using a vacuum pump with exhaust air volume more than 0.883 cu.ft./min. and ultimate vacuum pressure rate of 50 micron Hg. Standard time for evacuation (6) Recharging Recharge unit in the same manner explained on the previous page "(5) Recharging." (2) Recover refrigerant OK (3) Weld leaking points OK (4) Check for sealing OK (5) Evacuation OK (6) Recharge (1) Detect leaks OK 84
9-7. Charging Additional Refrigerant 9-7-1. When Tubes are Extended Observe the proper amount of refrigerant as stated in this service manual or the installation manual that came with the indoor unit. Charge additional refrigerant in liquid state only. 9-8. Retro-Fitting Existing Systems 9-8-1. Use of Existing Units Never use new refrigerant R410A for existing units which use R22. This will cause the air conditioner to operate improperly and may result in a hazardous condition. 9-8-2. Use of Existing Tubing If replacing an older unit that used refrigerant R22 with a R410A unit, do not use its existing tubing. Instead, completely new tubing must be used. CAUTIONNever charge additional refrigerant if refrigerant is leaking from the unit. Follow instructions given in "9-6. In Case Refrigerant is Leaking" and completely carry out repairs. Only then should you recharge the refrigerant. 85
INSTALLATION INSTRUCTIONS CU-3KS19NBU CU-4KS24NBU CU-4KS31NBU (852-6-4190-581-00-1) APPENDIX A A-1
For Outdoor Unit This air conditioner uses the refrigerant R410A. External diameter of service port R410A: 5/16" Split System Air Conditioner 85264190581001 2011 CV6233187761 INSTALLATION INSTRUCTIONS NOTE Contents Page IMPORTANT! Please Read Before Starting..................................2 1. GENERAL..........................................................4 1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Optional Copper Tubing Kit 1-4. Type of Copper Tube and Insulation Material 1-5. Additional Materials Required for Installation 2. INSTALLATION SITE SELECTION...................5 2-1. Indoor Unit 2-2. Connecting Indoor Units 2-3. Outdoor Unit 2-4. Baffle Plate for the Outdoor Unit 2-5. Outer Dimensions of Outdoor Unit 2-6. Diagram of Outdoor Unit Installation 3. INSTALLATION PROCESS..............................16 3-1. Embedding the Tubing and Wiring 3-2. Use of the Flaring Method 3-3. Flaring Procedure with a Flare Tool 3-4. Caution before Connecting Tubes Tightly 3-5. Tubing Connections 3-6. Insulation of Refrigerant Tubing 3-7. Taping the Tubes 3-8. Finishing the Installation 4. AIR PURGING...................................................19 Air Purging with a Vacuum Pump (for Test Run) Pump Down 5. WIRING INSTRUCTIONS................................22 5-1. General Precautions on Wiring 5-2. Recommended Wire Length and Diameter 5-3. Wiring System Diagram 5-4. How to Connect Wiring to the Terminal 5-5. Wiring Instructions for the Outdoor Unit 6. TEST RUN.........................................................26 7. CONNECTING A HOME AUTOMATION DEVICE.............................................................27 8. INSTALLATION CHECK SHEET......................27 Indoor unit AIndoor unit B Indoor unit C Indoor unit D Outdoor unit Combination example Model Combinations Combine indoor and outdoor units only as listed below. Model No. Indoor Unit Outdoor Unit CS-MKS7NKU CU-3KS19NBU CS-MKS9NKU CU-4KS24NBU CS-MKS12NKU CU-4KS31NBU CS-MKS18NKU CS-MKS24NKU CS-MKS9NB4U CS-MKS12NB4U CS-KS18NB4UW Power Source: 60 Hz, single-phase, 230 / 208 VAC
IMPORTANT! Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes. Pay close attention to all warning and caution notices given in this manual. This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death. This symbol refers to a hazard or unsafe practice which can result in personal injury or prod- uct or property damage. If Necessary, Get Help These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales / service outlet or your certified dealer for additional instructions. In Case of Improper Installation The manufacturer shall in no way be responsible for improp- er installation or maintenance service, including failure to follow the instructions in this document. SPECIAL PRECAUTIONS When Wiring ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
4 1-2. Accessories Supplied with Unit Table 1 1-3. Optional Copper Tubing Kit Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing, fittings and insulation. Consult your nearest sales outlet or air conditioning workshop. 1-4. Type of Copper Tube and Insulation Material If you wish to purchase these materials separately from a local source, you will need: 1. Deoxidized annealed copper tube for refrigerant tub- ing as detailed in Table 2. Cut each tube to the appropriate lengths 1 to 14 (30 cm to 40 cm) to dampen vibration between units.2. Foamed polyethylene insulation for the specified copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 5/16 (8 mm). 3. Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to 5. Wiring Instructions for details. 1. Refrigeration (armored) tape 2. Insulated staples or clamps for connecting wire (See local codes.)3. Putty 4. Refrigeration lubricant 5. Clamps or saddles to secure refrigerant tubing Reducer (3/8" 1/2")1Packed in the outdoor unit. 4 each Labels for inter-unit cable and tubeCushion rubber 4 Parts Figure Q’ty Parts Figure Q’ty Parts Figure Q’ty CU-3KS19NBUCU-4KS24NBU CU-4KS31NBU 2 1ABCDReducer (1/2" 3/8") CAUTIONCheck local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations. ModelNarrow Tube Wide TubeOuter Dia. Thickness Outer Dia. Thickness CS-MKS7NKU, CS-MKS9NKU, CS-MKS12NKU1/4 (6.35 mm) 0.0314 (0.8 mm) 3/8 (9.52 mm) 0.0314 (0.8 mm) CS-MKS18NKU1/4 (6.35 mm) 0.0314 (0.8 mm) 1/2 (12.70 mm) 0.0314 (0.8 mm) CS-MKS24NKU1/4 (6.35 mm) 0.0314 (0.8 mm) 5/8 (15.88 mm) 0.0393 (1.0 mm) CS-MKS9NB4U, CS-MKS12NB4U1/4 (6.35 mm) 0.0314 (0.8 mm) 3/8 (9.52 mm) 0.0314 (0.8 mm) CS-KS18NB4UW1/4 (6.35 mm) 0.0314 (0.8 mm) 1/2 (12.70 mm) 0.0314 (0.8 mm) Table 2 1-5. Additional Materials Required for Installation 1. General This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instruc- tions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning. If the electric wiring diagram does not appear in this manual, please check for the diagram on the indoor unit. 1-1. Tools Required for Installation (not supplied) 1. Standard screwdriver 2. Phillips head screwdriver 3. Knife or wire stripper 4. Tape measure 5. Carpenter’s level 6. Sabre saw or key hole saw7. Hacksaw 8. Core bits 9. Hammer 10. Drill 11. Tube cutter 12. Tube flaring tool13. Torque wrench 14. Adjustable wrench 15. Reamer (for deburring) 16. Vacuum pump (For R410A) 17. Manifold valve