Panasonic Cu 3ks19nbucu 4ksxxnbu Technical Service Manual
Have a look at the manual Panasonic Cu 3ks19nbucu 4ksxxnbu Technical Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
25 123 123123 123 Indoor unit B Indoor unit A Ground Power: Single-phase, 230/208VAC 60HZ Power breaker (not provided) Outdoor unit Terminal board Label A Inter-unit cables #14 (not provided) Terminal board Inter-unit cables #14 (not provided) Terminal board Label B Label C Inter-unit cables #14 (not provided) Inter-unit cables #14 (not provided)Terminal board Terminal board Label D A BC D Power cable (not provided) (#12: Less than 85 ft.) Be sure to perform grounding. Attach a ground wire to either the outdoor unit or indoor unit. If there is a grounding terminal inside the room, use the grounding screw inside the indoor unit.Be sure to apply the provided labels to both ends of the inter-unit cables to prevent mis- wiring. The units will not function if the wiring connections are incorrect. A is the indoor unit with refrigerant tubing that is connected to service valve A (bottom) of the outdoor unit. refrigerant tubing that is connected to service valve B (second from the bottom) of the outdoor unit. B is the indoor unit with Indoor unit C refrigerant tubing that is connected to service valve C (third from the bottom) of the outdoor unit. C is the indoor unit with Indoor unit D refrigerant tubing that is connected to service valve D (top) of the outdoor unit. D is the indoor unit with 1 2 1 2 3 4 5 6 7 8 9 10 11 12 Power supply (conduit) Inter Unit (conduit)Inter Unit (conduit) # ... AWG (American Wire Gauge) 5-5. Wiring Instructions for the Outdoor Unit Be sure to correctly align inter-unit cables A, B, C and D. Use a dedicated air conditioner circuit for power. To make connections to the outdoor unit, remove the inspection panel and tubing panel. Do not bring the inter-unit cables or power cable into contact with tubing or service valves. Use outdoor unit cable fasteners and fasten the inter-unit cables at the location where the cables are double- sheathed. Arrange the wiring so that the inter-unit cables are contained in the inspection panel and tubing panel, as shown in Fig. 31. CAUTION Fig. 31
26 Regulations on wire size differ from locality to locality. For field wiring requirements, please refer to your local electri- cal codes. Make sure that the installation fully complies with all local and national regulations. (1) Remove access panel “C”. (Fig. 32) (2) Connect the inter-unit and power supply line accord- ing to the drawing on the panel side. (3) Be sure to size each wire allowing approx. 4 (10 cm) longer than the required length for wiring. Store excess wiring inside the cabinet. (4) When connections are completed, check that all con- nections are correct as shown in the wiring system diagram on panel side. (5) Be sure to ground the unit according to your local codes. Fig. 32 Lock nut Conduit plate Plug Inter unit (Conduit)Power supply (Conduit) Cabinet Terminal block Access panel “C” Fig. 33 Conduit plate Make sure there is no gap between access panel “C” and the conduit plate. Access panel C CAUTION 6. Test Run Performing a test run Refer to the test run procedures in the indoor unit installation manual. Perform the test run separately for each connected indoor unit. If 2 units are operated simultaneously, it is not possible to correctly check for errors in tubing and wiring. Checking tubing and wiring Perform the test run and check that operation is normal. If there is an error in tubing or wiring, the refrigerant may flow to indoor unit B when indoor unit A is operated (for example). Stop operation immediately if there is an error in tubing or wiring. Turn the power (breaker) to OFF, and check whether the inter-unit cables are connected incorrectly, or whether the narrow tubes A and B are connected in reverse. Correct the connections. If there is an error in tubing, pump-down must be per- formed. Be sure to perform pump-down. After making corrections, again purge the air from the tubes. CAUTION
27 7. Connecting a Home Automation Device The HA (white) 4P terminal is located on the indoor unit PCB. If a HA device will be used, connect it to this terminal. 8. Installation Check Sheet The strength of the installation location is sufficient to support the air conditioner weight. The indoor and outdoor units are installed level and vertically. The power and voltage are as specified. Inter-unit cables are securely fastened to the terminal board. Inter-unit cables are securely fixed. The power cable and inter-unit cables are not connected anywhere along their paths. The ground wire is securely connected. An air purge of the refrigerant circuit has been conducted. A leak test of the tubing connections has been performed. Thermal insulation has been applied to the tubing connections. Drain connections are secure and water drains properly. Putty has been used to close the hole in the wall. All service valves are fully open. Remote controller signals are being positively received.