Page 81
9-3. Tools Specifically for R410A For servicing, use the following tools for R410A Gauge manifold Charging hose Gas leak detector Refrigerant cylinder Charging cylinder Refrigerant recovery unit Vacuum pump with anti-reverse flow (*1) (Solenoid valve-installed type, which prevents oil from flowing back into the unit when the power is off, is recommended.) Vacuum pump (*2)...can be used if the following adapter is attached. Vacuum pump adapter (reverse-flow prevention adapter) (*3). (Solenoid...
Page 82
9-5. In Case of Compressor Malfunction CAUTIONShould the compressor malfunction, be sure to make the switch to a replacement compressor as quickly as possible. Use only the tools indicated exclusively for R410A. See "9-3. Tools Specifically for R410A." 9-5-1. Procedure for Replacing Compressor (1) Recovering refrigerant Any remaining refrigerant inside the unit should not be released to the atmosphere, but recovered using the refrigerant recovery unit for R410A. Do not reuse the...
Page 83
Valve Single valve Charge liquid refrigerant with cylinder in up-side-down position. Single valve (with siphon tube) Charge with cylinder in normal position.Liquid Valve Liquid Charging cylinder Open Refrigerant cylinder Liquid NO! CAUTIONNever charge a large amount of liquid refrigerant at once to the unit. This may cause damage to the compressor. CAUTIONTo prevent the composition of R410A from changing, never bleed the refrigerant gas into the atmosphere while transferring the refrigerant....
Page 84
Length of tubing Evacuation timeLess than 33 ft. (10 m) More than 10 minutesMore than 33 ft. (10 m) More than 15 minutes 9-6. In Case Refrigerant is Leaking CAUTIONNever attempt to charge additional refrigerant when refrigerant has been leaking from the unit. Follow the procedure described below to locate points of leaks and carry out repairs, then recharge the refrigerant. (1) Detecting Leaks Use the detector for R410A to locate refrigerant leak points. (2) Recovering refrigerant Never release the...
Page 85
9-7. Charging Additional Refrigerant 9-7-1. When Tubes are Extended Observe the proper amount of refrigerant as stated in this service manual or the installation manual that came with the indoor unit. Charge additional refrigerant in liquid state only. 9-8. Retro-Fitting Existing Systems 9-8-1. Use of Existing Units Never use new refrigerant R410A for existing units which use R22. This will cause the air conditioner to operate improperly and may result in a hazardous condition. 9-8-2. Use of...
Page 86
INSTALLATION INSTRUCTIONS CU-3KS19NBU CU-4KS24NBU CU-4KS31NBU (852-6-4190-581-00-1) APPENDIX A A-1
Page 87
For Outdoor Unit This air conditioner uses the refrigerant R410A. External diameter of service port R410A: 5/16" Split System Air Conditioner 85264190581001 2011 CV6233187761 INSTALLATION INSTRUCTIONS NOTE Contents Page IMPORTANT! Please Read Before Starting..................................2 1. GENERAL..........................................................4 1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Optional Copper Tubing Kit 1-4. Type of...
Page 88
IMPORTANT! Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes. Pay close...
Page 90
4 1-2. Accessories Supplied with Unit Table 1 1-3. Optional Copper Tubing Kit Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing, fittings and insulation. Consult your nearest sales outlet or air conditioning workshop. 1-4. Type of Copper Tube and Insulation Material If you wish to purchase these materials separately from a local source, you will need: 1. Deoxidized annealed copper tube for refrigerant tub- ing as detailed in...