Panasonic Cu 3ks19nbucu 4ksxxnbu Technical Service Manual
Here you can view all the pages of manual Panasonic Cu 3ks19nbucu 4ksxxnbu Technical Service Manual. The Panasonic manuals for Air Conditioner are available online for free. You can easily download all the documents as PDF.
Page 101
15 2-6.Diagram of Outdoor Unit Installation Never install only a single indoor unit. Be sure to connect indoor and outdoor units only in combinations that are listed in the catalog or in the combination table that was provided with the outdoor unit. (Use caution. Connecting any other model may result in operation failure and malfunction.) The dimensions indicated by in the figure below are spaces that are required in order to maintain performance. Install in a location where the dimensions...
Page 102
16 3. Installation Process 3-1.Embedding the Tubing and Wiring Do not connect tubes to locations that are embedded. Be sure to bind refrigerant tubing and inter-unit cables together with vinyl tape. The power cable must be obtained on-site. (#12: Less than 85 ft.) # ... AWG (American Wire Gauge) Be sure to apply the provided labels to both ends of the inter-unit cables to prevent miswiring. Securely seal the end of embedded tubing with vinyl tape in order to prevent dirt or moisture entry. In...
Page 103
17 When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 9) (3) Remove the flare nut from the unit and be sure to mount it on the copper tube. (4) Make a flare at the end of copper tube with a flare tool.* (Figs. 10 and 11) (*Use “RIDGID” or equivalent.) A good flare should have the following characteristics: inside surface is glossy and smooth. edge is smooth. tapered sides are of uniform length. 3-4. Caution before Connecting Tubes Tightly a) Be sure...
Page 104
18 3-6. Insulation of Refrigerant Tubing To prevent heat loss and wet floors due to dripping of con- densation,both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a minimum 5/16 (8 mm). (Fig. 16) For wall-mounted units After connecting the refrigerant tubing to the outdoor unit and performing a leak test on the connecting part, insulate it with the tubing insulation. (Fig 17a) For ceiling-mounted cassette units Wind the insulation tape around...
Page 105
19 4. Air Purging Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely. pressure in the system rises operating current rises cooling efficiency drops moisture in the air may freeze and block capillary tubing water may lead to corrosion of parts in the refrigerant system Air Purging with a Vacuum Pump (for Test Run) In order to protect the earth’s environment, be sure to use a vacuum pump to perform the air...
Page 106
20 Cap tightening torque: 170 – 215 lbs·in (200 – 250 kgf·cm) (Tighten by hand, then use a wrench to turn approximately 45°.) Stopper Spindle Service port Screw diameter: 1/2 UNF 20 threads Valve core Cap nut tightening torque: 60 – 95 lbs·in (70 – 110 kgf·cm) (Tighten by hand, then use a wrench to turn approximately 30 .) External diameter of service port R410A: 5/16 NOTE Fig. 21 When using a hex wrench to open the spindle, an extremely small amount of refrigerant may leak. This does not...
Page 107
21 Pump Down When relocating or disposing of the air conditioner, request this service from the dealer where the unit was purchased, or from an appropriate agent. Perform pump-down as described below. What is pump-down? Pump-down refers to recovering the refrigerant gas from the refrig- erant cycle at the outdoor unit. This work must be performed dur- ing cooling operation. The refrigerant gas cannot be recovered during heating operation. During winter, or if the temperature sensor prevents cooling...
Page 108
22 5. Wiring Instructions 5-1. General Precautions on Wiring (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2) Provide a power outlet to be used exclusively for each unit, with a power supply disconnect and circuit break- er for overcurrent protection provided in the exclusive line. (3) To prevent possible hazard due to insulation failure, the unit must be grounded. (4) Each wiring connection must be...
Page 109
23 WARNING Be sure to comply with local codes on running the wire from the indoor unit to the outdoor unit (size of wire and wiring method, etc.). Each wire must be firmly connected. No wire should be allowed to touch refrigerant tubing, the compressor, or any moving part. Be sure to connect power wires correctly match- ing up numbers on terminals of the outdoor unit and respective indoor units A – D. CAUTION Be sure to connect the power supply line to the outdoor unit as shown in the wiring...
Page 110
24 When connecting each power wire to the corresponding terminal, follow the instructions “How to connect wiring to the terminal” and fasten the wire securely tight with the fixing screw of the terminal plate. How to connect wiring to the terminal a) For Indoor Unit (1) Cut the wire end with a cutting pliers, then strip the insulation to expose the wire about 9/32 (7 mm). See the label (Fig. 26) near the terminal plate. (2) Using a screwdriver, loosen the terminal screw on the terminal plate. (3) Insert...