Home > Panasonic > Air Conditioner > Panasonic Cu 3ke19nbucu Technical Service Manual

Panasonic Cu 3ke19nbucu Technical Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Cu 3ke19nbucu Technical Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							8-2.  Trouble Diagnosis by Error Monitor Lamps
    8-2-1.  Location of the Error Monitor Lamps
    Remove the top plate of outdoor unit and the cover of Electrical Component Box.
    The Power Lamp and Error Monitor Lamps are located on the P.C.Board of Electrical Component Box. (Fig.1)
    8-2-2.  Display of the Error Monitor Lamps
    If a protective device has activated or there is a sensor failure in the outdoor unit, the 4 error monitor lamps on the 
    outdoor control circuit board will indicate the nature of the trouble.
    Heat Exchanger Rear side P.C.Board of Electrical Component Box.
    Error Monitor Lamps
    Front side
    Fig.1 View from top
    ERR0
    ERR1
    ERR2
    ERR3Power Lamp
    Error Monitor Lamp
    Error Contents
    ERR0 ERR1 ERR2 ERR3
    Sensor for compressor discharge temp
    Sensor for heat excharge temp
    Sensor for branch pipe A (Narrow tube)
    Sensor for branch pipe B (Narrow tube)
    Sensor for branch pipe C (Narrow tube)
    Sensor for branch pipe D (Narrow tube)
    Sensor for branch pipe A (Wide tube)
    Sensor for branch pipe B (Wide tube)
    Sensor for branch pipe C (Wide tube)
    Sensor for branch pipe D (Wide tube)
    HIC circuit trouble (current, temp)
    Actuation of comp over load relay
    Actuation of freeze protection function
    Outdoor unit error. Detail of error message indicate on indoor LED Outdoor temp sensor
    : ON : OFF
    To prevent electric shock, do not inspect or repair until the Power Lamp on 
    the P.C.Board is turned off.Warning
    81 
    						
    							8-3-1.  Checking the outdoor unit
    8-3.  Checking the Outdoor System
    8-3-2.  Checking the defrost operation
    Work procedure
    Apply 220 V AC between terminals L1 and L2 on the 
    outdoor unit terminal plate. •
    Short-circuit the T-RUN terminal to the COM terminal 
    of TEST/T-RUN terminals. •The LED (red) on the control board must illuminate. •
    The compressor, fan motor, 4-way valve, and solenoid 
    valve (for the hot gas bypass) must turn ON.
    (They turn ON about (70) seconds later after the power 
    is turned ON.) •
    No.
    1
    2Check items (unit operation)
    Work procedure
    Connect a dummy resistor of 39 k ohm to the outdoor
    coil temperature sensor connector. •Non-stop defrost
    The maximum length of defrost operation is 12 
    minutes.
    Defrost can also be released based on the below
    conditions for the outdoor heat exchanger sensor.
    *1  However, the condition is (68 °F) or higher when
          the outdoor air temperature is below 32 °F.Less than 2 minutes     Not released
    2 minutes or more     57.2 °F or higher (*1) •
    No.
    1Check items (unit operation)
    Indoor fan
    Outdoor fanCM
    Solenoid valve
    (for hot gas
    bypass)30 sec.
    10 sec. 5 sec.(80 Hz)
    ON
    ON OFF OFF
    OFF ON
    Defrost start ReleaseON Setting Setting
    LLStop
    NOTEIf the above check items are okay, but the outdoor unit does not operate, there may be a faulty 
    connection between the indoor unit and the outdoor unit.
    Using forced defrost operation to check this  function.
    82 
    						
    							8-4.  Trouble Diagnosis of Each Part
    8-4-1.  Problems of Each Part and Inspection Points
    For details about the inspection points, refer to the Inspection Points for Each Part.
    Problems
    Inspection
    pointsIndoor unit
    Indoor unit does not operate.
    Self-Diagnostics check
    Indoor controller 
    (control unit)
    Indoor fan motor
    Room temperature 
    sensor
    Heat exchanger 
    temperature sensor
    Inter-unit cable
    Switch circuit board
    Outdoor control circuit 
    board
    Diode module
    HIC
    Electrolytic capacitor
    Fuse
    Compressor
    Compressor protective 
    sensor
    Outdoor fan motor
    4-way valve
    Coil thermistor
    Electric expansion valve
    Branch tubing 
    temperature sensor
    (1)
    (2)
    (3)
    (4)
    (5)
    (6)
    (7)
    (8)
    Operation lamp blinking.
    Operation lamp does not illuminate.
    Indoor fan dose not turn.
    Outdoor unit does not operate.
    Outdoor fan dose not turn.
    4-way valve does not operate.
    The compressor (only) does not 
    operate.
    The compressor stops on occasion.
    The compressor speed does not
    increase.
    The outdoor air temperature is high,
    however defrost operation occurs.
    Defrost operation does not occur.
    The electric expansion valve does
    not operate.
    Does not cool or cooling
    performance is inadequate.
    Does not heat or heating
    performance is inadequate.
    Outdoor unit Others
    No. of 
    Inspection
    Points for
    Each part
    Indoor unit Outdoor unit
    83 
    						
    							Problems
    Inspection
    pointsIndoor unit
    Indoor unit does not operate.
    Breaker
    Refrigerant gas pressure(9)
    (10)
    Operation lamp blinking.
    Operation lamp does not illuminate.
    Indoor fan dose not turn.
    Outdoor unit does not operate.
    Outdoor fan dose not turn.
    4-way valve does not operate.
    The compressor (only) does not
    operate.
    The compressor stops on occasion.
    The compressor speed does not
    increase.
    The outdoor air temperature is high,
    however defrost operation occurs.
    Defrost operation does not occur.
    The electric expansion valve does
    not operate.
    Does not cool or cooling
    performance is inadequate.
    Does not heat or heating
    performance is inadequate.
    Outdoor unit Others
    No. of 
    Inspection
    Points for
    Each part
    Others
    8-4-2.  Inspection Points for Each Part
    (1) Outdoor control circuit board
    Refer to "8-3-1. Checking the outdoor unit".
    (2) Fuse
    Check it visually or the continuity with a tester.
    (3) Compressor
    Check for an open circuit in the compressor coil winding.
    (4) Compressor protective sensor (compressor discharge temperature thermistor)
    Check that the senseor is securely contained in the thermostart holder.
    (5) 4-way valve
    Short-circuit the T-RUN terminal to the COM terminal of TEST/T-RUN terminals. Perfrom a test run of the unit 
    alone, and check whether the 4-way valve inside the outdoor unit produces a click sound.
    (6) Coil thermistor
    Check that the sensor is securely contained in the thermostat holder.Do not remove or insert the outdoor control circuit board connector when power is being supplied to it.
    (The controller will be damaged.)
    NOTE
    84 
    						
    							No voltage on circuit board
    (7) Electric expansion valve
    When replacing the electric expansion valve and coil, be sure to attach the connectors in the correct positions. 
    Labels are applied to the valve body and coil, corresponding to the connector colors, to identify them.
    Controller check
    Voltage varies
    0 ohm
    No temperature change Temperature changes Replace the coil.
    Open and close the 
    electric expansion valve 
    by hand to check it.
    Replace the electric 
    expansion valve.This part is normal.
    Check elsewhere. Check the illumination 
    of the red Power Lamp.
    Replace the controller.Check the coil resistance.Use a multi-meter to measure the voltage (12 V).
    Model No. Sequence
    CU-3KE19NBU
    CU-4KE24NBU
    CU-4KE31NBUMV0 MV1 When the power is turned ON, the needle will move in the 
    following seguence in approximately 10 to 20 seconds for 
    each point.
    Check the resistance between the gray lead 
    wire and the other wires.
    Resistance is OK if it is 46 + / – 4ohm at 68 °F
    Cool the main unit with 
    a damp cloth or other 
    means while welding.
    When applying 
    vacuum, use the 
    special service magnet 
    and rotate at least 5 
    revolutions 
    counterclockwise to 
    fully open the electric 
    expansion valve.
    Use the special service magnet and 
    rotate 5 revolutions clockwise to fully 
    close the valve.
    Then start the unit and measure the 
    temperature at the inlet and outlet 
    tubes of the electric expansion valve.
    If the temperature difference is large, 
    the valve is closed.
    Then rotate 5 revolutions 
    counterclockwise to open the valve. 
    Operation is normal if the temperature 
    difference between the 2 tubes drops.*1
    Approx. 46 +/– 4 ohm
    NOTE
    *1 If you have manually checked the electric expansion valve, be sure to reapply the outdoor power after you have
         replaced the wiring. (The position of the elecric expansion valve will changed.)
    MV2
    MV0 MV1MV2MV3
    85 
    						
    							(8) Branch tubing temperature sensor
    Check that the sensor is securely contained in the thermostat holder.
    (9) Breaker
    Check whether or not the breaker has been tripped.
    Check that the breakers and fuses used are of the specified capacity.
    Check that the breaker and its line are exclusive for A/C use.
    (10) Refrigerant gas pressure
    Start a COOL test run, and messure the temperatures of the A/C intake air and discharge air. Compare the values 
    with the performance charts.
    If the values are higher than the performance charts:
    Check for refrigerant shortage or blockage of the refrigerant circuit.
        < Assessment of refrigerant shortage >
            1. The pressure in the low-pressure section is 5 MPa or more below the value in the performance charts.
            2. There is little condensation on the indoor heart exchanger, which overall appears dry.
        < Distinguishing between refrigerant shortage and refrigerant circuit blockage >
           If the pressure in the low-pressure section does not change when the circuit is charged 2 to 3 times with
           refrigerant gas (0.44 lbs each time), or if the change is small, then the problem may not be 
           refrigerant shortage. 
          The problem may be a blockage of the refrigerant circuit.
            1. Check that there is no internal leakage inside the 4-way valve:
            At the low-pressure side tubing, check that there is no temperature difference between the intake and
            discharge of the 4-way valve.
            2. Check that the electric expansion valve is not blocked. Check as described on the preceding page.
    86 
    						
    							8-5.  Trouble Diagnosis of Fan Motor
    This outdoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil 
    resistance, and the following procedure should be used to check the motor.
    Perform the trouble diagnosis by Test Run mode described on Installation Instructions of indoor unit.
    [Trouble symptom 1] The fan does not stop when the outdoor unit stops.    Outdoor unit controller trouble
    [Trouble symptom 2]  The fan motor does not rotate when the outdoor unit is operating.
    (Diagnostic procedure)
    * Disconnect the motor connectors and measure the voltage at the DC motor connectors on the outdoor 
    unit controller (3 locations).
    (Diagnostic results)
    All of the above measured values are normal.     Fan motor trouble (Replace the motor.)
    Any one of the above measured values is not normal.     Outdoor unit controller trouble 
    (Replace the controller .)
    (Reference) DC motor connector pin arrangement
    [Trouble symptom 3] Motor rotates for some time (several seconds), but then quickly stops, when the outdoor 
    unit operates.
    (There is trouble in the system that provides feedback of motor rotation speed from the 
    motor to the outdoor unit controller.)
    [Trouble symptom 4] Fan motor rotation speed does not change during outdoor unit operation.
    [Trouble symptom 5] Fan motor rotation speed varies excessively during outdoor unit operation.
    (Remedy for symptom 3 to 5)
    It is not possible to identify whether the trouble is outdoor unit controller trouble or motor trouble. 
    Therefore, first replace the outdoor unit controller, then (if necessary) replace the DC motor.
    Important:(A) Turn OFF the power before connecting or disconnecting the motor connectors.
    (B) When performing voltage measurement at the outdoor controller connector for (3) in the table 
    below, the DC motor will trip and voltage output will stop approximately 10 seconds after 
    operation is started. For this reason, to measure the voltage again, first turn OFF the outdoor 
    unit power, then, measure the voltage in Test Run mode.
    (1) Vm-Gnd: Between pin 1 and pin 4
    (2) Vcc-Gnd: Between pin 5 and pin 4
    (3) Vsp-Gnd: Between pin 7 and pin 4Measurement location
    DC 230V or more
    DC 14V or more
    After fluctuating 4 times between DC 1.7 to 6.1V
    (1 sec. ON) and DC 0 V (1 sec. OFF), the DC
    motor trips.Normal value
    Pin 1: Vm (red)
    Pin 2: Not used
    Pin 3: Not used
    Pin 4: Gnd (blue)
    Pin 5: Vcc (brown)
    Pin 6: PG (white)
    Pin 7: Vsp (orange)
    87 
    						
    							9.  REFRIGERANT R410A: 
    SPECIAL PRECAUTIONS WHEN SERVICING UNIT
    9-1.  Characteristics of New Refrigerant R410A
    9-1-1.  What is New Refrigerant R410A?
    R410A is a new refrigerant that contains two types of pseudo-non-azeotropic refrigerant mixture. Its 
    refrigeration capacity and energy efficiency are about the same level as the conventional refrigerant, R22.
    9-1-2.  Components (mixing proportions)
    HFC32 (50%) / HFC125 (50%)
    9-1-3.  Characteristics
    Less toxic, more chemically stable refrigerant
    The composition of refrigerant R410A changes whether it is in a gaseous phase or liquid phase. Thus, when 
    there is a refrigerant leak the basic performance of the air conditioner may be degraded because of a change in 
    composition of the remaining refrigerant. Therefore, do not add new refrigerant. Instead, recover the 
    remaining refrigerant with the refrigerant recovery unit. Then, after evacuation, totally recharge the specified 
    amount of refrigerant with the new refrigerant at its normal mixed composition state (in liquid phase).
    When refrigerant R410A is used, the composition will differ depending on whether it is in gaseous or liquid 
    phase, and the basic performance of the air conditioner will be degraded if it is charged while the refrigerant is in 
    gaseous state. Thus, always charge the refrigerant while it is in liquid phase. 
    Ether-type oil is used for compressor oil for R410A-type units, which is different 
    from the mineral oil used for R22. Thus more attention to moisture prevention and 
    faster replacement work compared with conventional models are required. 
    CAUTION
    88 
    						
    							Tubing precautions
    Refrigerant R410A is more easily affected by dust or moisture compared with R22, thus be sure to temporarily 
    cover the ends of the tubing with caps or tape prior to installation.
    Never use 0.0276" (0.7 mm)-thick copper tubing or tubing which is less than 0.0315" (0.8 mm) in thickness, since 
    air conditioners with R410A are subject to higher pressure than those using R22 and R407C.
    No addition of compressor oil for R410A
    No additional charge of compressor oil is permitted.
    No use of refrigerant other than R410A
    Never use a refrigerant other than R410A.
    If refrigerant R410A is exposed to fire
    Through welding, etc., toxic gas may be released when R410A refrigerant is exposed to fire. Therefore, be sure 
    to provide ample ventilation during installation work.
    Caution in case of R410A leak
    Check for possible leak points with the special leak detector for R410A. If a leak occurs inside the room, 
    immediately provide thorough ventilation.
    A D
    Flare tool for R410AA D
    Conventional flare tool (R22)
    Spacer
    9-2.  Checklist before Servicing
    Use a clutch-type flare tool for R410A or the conventional flare tool. Note that sizes of the resultant flares differ 
    between these two tools. Where a conventional flare tool is used, make sure to observe A Specification (amount of 
    extrusion) by using the flare spacer.
    Size of flare
    Specification A
    Diameter of tube D
    Dia.1/4" (6.35 mm)
    Dia.3/8" (9.52 mm)
    Dia.1/2" (12.7 mm)
    Dia.5/8" (15.88 mm)Flare tool for R410A Conventional flare tool (for R22)
    0 to 0.0196"
    (0 to 0.5 mm)0.0472"
    (1.2 mm)
    89 
    						
    							9-3.  Tools Specifically for R410A 
    For servicing, use the following tools for R410A
    Gauge manifold
    Charging hose
    Gas leak detector
    Refrigerant cylinder
    Charging cylinder
    Refrigerant recovery unit
    Vacuum pump with anti-reverse flow (*1)
    (Solenoid valve-installed type, which prevents oil from flowing back into the 
    unit when the power is off, is recommended.)
    Vacuum pump (*2)...can be used if the following adapter is attached.
    Vacuum pump adapter (reverse-flow prevention adapter) (*3).
    (Solenoid valve-installed adapter attached to a conventional vacuum pump.)
    Electronic scale for charging refrigerant
    Flare tool
    Bender
    Torque wrench 
    Cutter, reamer
    Welding tool, nitrogen gas cylinder
    Tools specifically for R410ATool Distinction Tool Name
    Tools which can be com-
    monly used for R22,
    R407C, and R410A
    CAUTIONThe above tools specifically for R410A must not be used for R22 and R407C. 
    Doing so will cause malfunction of the unit.
    For the above vacuum pump (*1, *2) and vacuum pump adapter (*3), those for 
    R22-type units can be used for R410A-type. However, they must be used 
    exclusively for R410A and never alternately with R22 and R407C.
    For details on tubing installation procedures, refer to the installation manuals attached to the indoor 
    unit and outdoor unit. To prevent other refrigerants (R22, R407C) from being mistakenly charged to this unit, shape and external 
    diameter of the service port screw has been altered.
         R410A : 5/16"
         R22, R407C : 1/4"
    9-4.  Tubing Installation Procedures
    When the tubes are connected, always apply HAB oil on the flare portions to improve the sealing of tubing.
    The following is the HAB oil generally used:
    Esso:  ZERICE S32
    NOTE
    90 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Cu 3ke19nbucu Technical Service Manual