Panasonic Cu 3ke19nbucu Technical Service Manual
Have a look at the manual Panasonic Cu 3ke19nbucu Technical Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
15 2-6.Diagram of Outdoor Unit Installation Never install only a single indoor unit. Be sure to connect indoor and outdoor units only in combinations that are listed in the catalog or in the combination table that was provided with the outdoor unit. (Use caution. Connecting any other model may result in operation failure and malfunction.) The dimensions indicated by in the figure below are spaces that are required in order to maintain performance. Install in a location where the dimensions indicated by are ensured, and where 2 or more faces of the unit are unobstructed. In principle, the top direction should be unobstructed. Indoor unit D Wall-mounted types Ceiling-mounted cassette types Indoor unit C Indoor unit B Indoor unit A Indoor unit D Indoor unit C Indoor unit B Indoor unit A Service space Power breaker Ground wire (not provided) Ensure 6"(15cm) of space if a drain hose is to be used. Base (not provided) (concrete or similar material) Fasten with anchor bolts (not provided) (3/8" or M10, 4 locations) A B C D Access panel C Over 10"(25cm) Over 8"(20cm) Over 4"(10cm) Over 1'8"(50cm) Fig. 7
16 3. Installation Process 3-1.Embedding the Tubing and Wiring Do not connect tubes to locations that are embedded. Be sure to bind refrigerant tubing and inter-unit cables together with vinyl tape. The power cable must be obtained on-site. (#12: Less than 85 ft.) # ... AWG (American Wire Gauge) Be sure to apply the provided labels to both ends of the inter-unit cables to prevent miswiring. Securely seal the end of embedded tubing with vinyl tape in order to prevent dirt or moisture entry. In order to prevent insulation breakdown and ground faults, do not allow the wire ends to come in contact with rainwater, or be subject to dew condensation. Deburring BeforeAfter Fig. 8 3-2. Use of the Flaring Method Many of the conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts. 3-3. Flaring Procedure with a Flare Tool (1) Cut the copper tube to the required length with a tube cutter. It is recommended to cut approx. 12 to 20 (30 to 50 cm) longer than the tubing length you estimate. (2) Remove burrs at the end of the copper tube with a tube reamer or file. This process is important and should be done carefully to make a good flare. (Fig. 8)
17 When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 9) (3) Remove the flare nut from the unit and be sure to mount it on the copper tube. (4) Make a flare at the end of copper tube with a flare tool.* (Figs. 10 and 11) (*Use “RIDGID” or equivalent.) A good flare should have the following characteristics: inside surface is glossy and smooth. edge is smooth. tapered sides are of uniform length. 3-4. Caution before Connecting Tubes Tightly a) Be sure to apply a sealing cap or water-proof tape to prevent dust or water from getting into the tubes before they are used. b) Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks. (Fig. 12) c) For proper connection, align the union tube and flare tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match. (Fig. 13) 3-5. Tubing Connections a) Temporary connection: Screw in 3 – 5 turns by hand. (Fig.14) b) To fasten the flare nuts, apply specified torque as: Table 4 NOTE NOTE Reamer Copper tubing Fig. 9 Flare toolFlare nut Copper tubing Fig. 11 Fig. 10 Apply refrigerant lubricant here and here Fig. 12 Flare nut Union Fig. 13 0 to 0.0196" (0 to 0.5 mm) If the special R410A flare tool is used: 0.0472" (1.2 mm) If the previous flare tool (clutch-type) is used: Adjust so that the amount of tube protrusion is as shown in the figure. Apply the provided labels to the indoor and outdoor unit tubing connectors to prevent errors in connections. Service valve on narrow tube side Service valve on wide tube side A B C D Fig. 14 Tube Dia. Nut Tightening Torque 1/4 (6.35 mm) 21/32 (17 mm) Approx. 120 – 160 lbs· in (140 – 180 kgf· cm) 3/8 (9.52 mm) 7/8 (22 mm) Approx. 300 – 360 lbs· in (340 – 420 kgf· cm) 1/2 (12.70 mm) 1-1/32 (26 mm) Approx. 430 – 480 lbs· in (490 – 550 kgf· cm) 5/8 (15.88 mm) 1-5/32 (29 mm) Approx. 590 – 710 lbs· in (680 – 820 kgf· cm)
18 3-6. Insulation of Refrigerant Tubing To prevent heat loss and wet floors due to dripping of con- densation,both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a minimum 5/16 (8 mm). (Fig. 16) For wall-mounted units After connecting the refrigerant tubing to the outdoor unit and performing a leak test on the connecting part, insulate it with the tubing insulation. (Fig 17a) For ceiling-mounted cassette units Wind the insulation tape around the flare nuts at the tube connections. Secondly cover up the tubing connections with the flare insulation (1/8 (T3, supplied)). Then wind the other flare insulation (3/16 (T5, supplied)). Finally, fasten the insulation at both ends with the supplied vinyl ties. (Fig. 17b) Insulation material The material used for insulation must have good insulation characteristics, be easy to use, be age resistant, and must not easily absorb moisture. IMPORTANT Indoor unit Outdoor unitSpanner Torque wrench Fig. 15 Insulation Min. 5/16 (8 mm) Thickness: min. 5/16 (8 mm) Fig. 16 Insulation Fig. 17a CAUTIONBe sure to match refrigerant tubing and electric wiring between indoor and outdoor units. Fig. 17b Fig. 17c Never grasp the drain or refrigerant connecting out- lets when moving the unit. Insulation tape (supplied) Flare insulation (3/16(T5, supplied) ) Flare insulation (1/8(T3, supplied) ) Tube insulation (not supplied) Vinyl tie (supplied) Flare nut The procedure used for installing the insulation for both wide and narrow tubes are the same. Flare insulation (supplied)Vinyl tie (supplied)Insulation tape (supplied)Refrigerant tubing and insulation (not supplied) Drain pipe and insulation (not supplied) Drain hose insulation and vinyl tie (supplied) Drain hose and hose band (supplied)
19 4. Air Purging Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely. pressure in the system rises operating current rises cooling efficiency drops moisture in the air may freeze and block capillary tubing water may lead to corrosion of parts in the refrigerant system Air Purging with a Vacuum Pump (for Test Run) In order to protect the earth’s environment, be sure to use a vacuum pump to perform the air purge. (Never perform an air purge by using the refrigerant gas cylinder or other external gas, or by using the gas inside the outdoor unit.) Fig. 20 CAUTION In order to prevent charging errors with the air conditioner that uses R410A, the screw diameter at the service valve charging port has been changed. When recharging or performing other servicing, use the special charging hose and manifold gauge. Service valve on wide tube side Service valve on narrow tube side A B C D Vacuum pump Vacuum pump adapter (for preventing reverse flow) (special for R410A) High-pressure valve Manifold gauge (special for R410A) Low-pressure valve Leave the valve open. Open Charging hose (special for R410A) Hex wrench With push-pin Hi Lo 3-7. Taping the Tubes (1) At this time, the 2 refrigerant tubes (and electrical wire if local codes permit) should be taped together with armoring tape. The drain hose may also be included and taped together as 1 bundle with the tubing. (2) Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn. (Fig. 18) (3) Clamp the tubing bundle to wall, using 1 clamp approx. every 47 (120 cm). Do not wind the armoring tape too tightly, since this will decrease the heat insulation effect. Also, be sure the con- densation drain hose splits away from the bundle and drips clear of the unit and the tubing. 3-8. Finishing the Installation After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering. (Fig. 19) NOTE Fig. 18 Clamp Insulated tubes Apply putty here Tubing Fig. 19 CAUTION After a tube has been insulated, never try to bend it into a narrow curve, as this may cause the tube to break or crack.
20 Cap tightening torque: 170 – 215 lbs·in (200 – 250 kgf·cm) (Tighten by hand, then use a wrench to turn approximately 45°.) Stopper Spindle Service port Screw diameter: 1/2 UNF 20 threads Valve core Cap nut tightening torque: 60 – 95 lbs·in (70 – 110 kgf·cm) (Tighten by hand, then use a wrench to turn approximately 30 .) External diameter of service port R410A: 5/16 NOTE Fig. 21 When using a hex wrench to open the spindle, an extremely small amount of refrigerant may leak. This does not indicate a problem. Use a hex wrench of a type to which force can be easily applied. (4) With the “Lo” knob of the manifold valve open and high-pressure valve (“Hi”) closed completely, run the vacuum pump. Run the pump until the pressure is –101 kPa (–76 cmHg). The operation time for the vacuum pump varies with tubing length and the capacity of the pump. The following table shows the amount of time required for evacuation: Table 5 (5) With the vacuum pump still running, close the “Lo” knob of the manifold valve. Then stop the vacuum pump. Fully close the low-pressure valve and stop the vacuum pump. (Wait 1 – 2 minutes and check that the manifold gauge pointer does not return. If it does return, find and repair the leak, then apply the vacuum again.) (6) With a hex wrench, turn the valve stem on the narrow tube service valve counter-clockwise by 90 degrees (1/4 turn) for 10 seconds, and then turn the stem clockwise to close it again. (7) With a standard screwdriver, turn the wide tube service valve stem counterclockwise to fully open the valve. (8) Turn the narrow tube service valve stem counter-clockwise to fully open the valve. (9) Loosen the vacuum hose connected to the wide tube service port slightly to release the pressure. Then, remove the hose. (10) Leak test all joints at the tubing (both indoor and outdoors) with liquid soap. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth. CAUTIONBe sure to completely insert the hex wrench before attempting to turn the valve. Required time for evacuation when capacity of 100 liter/h vacuum pump is used 20 min. or moreThe required time in Table 5 is calculated based on the assumption that the ideal (or target) vacuum condition is around 10 mmHg abs. NOTE CAUTIONIf a CFC gas detector is used, use a special detector for HFC refrigerant (such as R410A and R134a). Perform the air purge for tubes A, B, C, and D. Use the same procedures for all tubes. (1) Check that each tube (both narrow and wide tubes) between the indoor and outdoor units have been proper- ly connected and all wiring for the test run has been completed. Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage. (2) Using an adjustable wrench or box wrench, remove the valve caps from the service valve on both narrow and wide tubes. (3) Connect a vacuum pump and a manifold valve (with pressure gauges) to the service port on the wide tube service valve. (Fig. 20). CAUTIONBe sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The “Hi” knob of the manifold valve must always be kept closed. CAUTIONBefore using the vacuum pump adapter, read the vacuum pump adapter manual, and use the adapter correctly.
21 Pump Down When relocating or disposing of the air conditioner, request this service from the dealer where the unit was purchased, or from an appropriate agent. Perform pump-down as described below. What is pump-down? Pump-down refers to recovering the refrigerant gas from the refrig- erant cycle at the outdoor unit. This work must be performed dur- ing cooling operation. The refrigerant gas cannot be recovered during heating operation. During winter, or if the temperature sensor prevents cooling opera- tion, perform “forced cooling operation.” Pump-down procedure (1) Fully close the spindles at the valves on the narrow tube side of tubes A, B, C and D. (Refer to Fig. 22.) (2) Connect the manifold gauge to the charging port at the valve on the wide tube side of tube D. Purge the air from the charging hose. (Refer to Fig. 23.) (3) Perform cooling operation or forced cooling operation. When the pressure at the low-pressure side is 0.05 – 0.1 MPaG (0.5 – 1 kg/cm 2G), fully close the spindles at the valves on the wide tube side of tubes A, B, C, and D, and immediately stop operation. (Refer to Fig. 23.) In the winter, the outdoor unit may stop after 5 - 10 minutes of operation. This is in order to protect the indoor unit heat exchanger from freezing and does not indicate a problem. (4) Disconnect the manifold gauge and the inter-unit tubes, and attach the caps and flare nuts. At this point, pump-down is com- pleted. (If the caps and flare nuts are not reattached, there is the danger of gas leakage.) (Refer to Fig. 24.) If pump-down is not possible If the air conditioner cannot be operated because of a malfunction or other cause, use a refrigerant recovery device to recover the refrigerant. In order to protect the earth’s environment, be sure to perform pump-down to recover refrigerant gas without releasing it into the atmosphere. Fig. 22 (11) Replace the flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench. Next, mount the valve cap and tighten it with a torque wrench (the cap needs to be tightened with the torque of 180 lbs·in (200 kgf·cm)). This process is very important to prevent gas from leaking from the system. (12) Test run the air conditioner. (See page 26.) (13) While the air conditioner is running, apply liquid soap to check for any gas leaks around the service valves or caps. (14) If there is no leakage, stop the air conditioner. (15) Wipe off the soap on the tubing. This completes air purging with a vacuum pump and the air conditioner is ready for actual operation. Fig. 23 C D B A Manifold gauge Wide tube side Charging hose Cap Cap Cap CapAfter disconnecting the inter-unit tubes, attach the flare nuts with flare bonnets. Fig. 24 D C B A Charging port Narrow tube sideClose Close Close Close
22 5. Wiring Instructions 5-1. General Precautions on Wiring (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2) Provide a power outlet to be used exclusively for each unit, with a power supply disconnect and circuit break- er for overcurrent protection provided in the exclusive line. (3) To prevent possible hazard due to insulation failure, the unit must be grounded. (4) Each wiring connection must be done tightly and in accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged. (5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan. (6) Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes. 5-2. Recommended Wire Length and Diameter Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local elec- trical codes. Carefully observe these regulations when car- rying out the installation. Table 6 shows maximum wire lengths for control line and power line and fuse or circuit capacity. Refer to the wiring system diagram (Fig. 25a or 25b) for the meaning of (A), (B), and (C) in Table 6. Refer to your local codes or in the absence of local codes see the National Electric Code: ANSI/NFPA70. NOTE Table 6 AWG Max. Power Line Length (ft.) (A)Max. Control Line Length (ft.) (B) (C) Fuse or Circuit Capacity Model (#12) (#14) CU-3KE19NBU 85 (Max.) 82 (Max.) 15 A CU-4KE24NBU 85 (Max.) 82 (Max.) 20 A CU-4KE31NBU 85 (Max.) 100 (Max.) 20 A # ... AWG (American Wire Gau ge)
23 WARNING Be sure to comply with local codes on running the wire from the indoor unit to the outdoor unit (size of wire and wiring method, etc.). Each wire must be firmly connected. No wire should be allowed to touch refrigerant tubing, the compressor, or any moving part. Be sure to connect power wires correctly match- ing up numbers on terminals of the outdoor unit and respective indoor units A – D. CAUTION Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram. The indoor unit draws its power from the outdoor unit. Do not run wiring for antenna, signal, or power lines of television, radio, stereo, telephone, secu- rity system, or intercom any closer than 34 (1 m) from the power cable and wires between the indoor and outdoor units. Electrical noise may affect the operation. To avoid the risk of electric shock, each air conditioner unit must be grounded. For the installation of a grounding device, please observe local electrical codes. Grounding is necessary, especially for units using inverter circuits, in order to release charged electricity and electrical noise caused by high tension. Otherwise, electrical shock may occur. Place a dedicated ground more than 7 (2 m) away from other grounds and do not have it shared with other electric appliances. WARNING Fig. 25a Fig. 25b 4 indoor units with CU-4KE24NBU, CU-4KE31NBU 1 2 3Terminal INDOOR UNIT 1 2 3 INDOOR UNIT 1 2 3 1 UNIT B 2 3 4 UNIT C 5 6 7 8 9 1 2 Terminal Terminal L1 L2 INDOOR UNIT UNIT A (A) (B) (C) Terminal (2P) Terminal( 9P) OUTDOOR UNIT Disconnect switch* * * 230/208V 230/208V 230/208V 230/208V 230/208V 230/208V 230/208V 230/208V 230/208V Grounding line Grounding line Disconnect switchField supply Disconnect switch Field supply Field supply Power supply Single-phase 230/208VAC 60HZ Grounding line Grounding line (A) (B) (B) (B)(B) (B) (B) (C) (C) (C) 1 2 3Terminal1 UNIT B 2 3 4 UNIT C 5 6 7 UNIT D 8 9 10 11 12 1 2 L1 L2 INDOOR UNIT UNIT A (A) 1 2 3Terminal INDOOR UNIT (B) Terminal ( 2P) Terminal( 12P) OUTDOOR UNIT Disconnect switch 230/208V 230/208V 230/208V 230/208V 230/208V 230/208V Grounding line Grounding line Field supply 230/208V 230/208V 230/208V 230/208V1 2 3Terminal INDOOR UNIT (C) 1 2 3Terminal INDOOR UNIT (D)(Inter-unit) power line230/208V 230/208V Power supply Single-phase 230/208VAC 60HZ Grounding line Grounding line Grounding line Disconnect switch Field supply Disconnect switch Field supply Disconnect switch Field supply (A) (B) (B) (B) (B) (B) (B) (B) (B) (C) (C) (C) (C) * * * * 3 indoor units with CU-3KE19NBU 5-3. Wiring System Diagram * Disconnect switch may be required by national or local codes. Always comply with national and local code requirements. CAUTION NOTE
24 When connecting each power wire to the corresponding terminal, follow the instructions “How to connect wiring to the terminal” and fasten the wire securely tight with the fixing screw of the terminal plate. How to connect wiring to the terminal a) For Indoor Unit (1) Cut the wire end with a cutting pliers, then strip the insulation to expose the wire about 9/32 (7 mm). See the label (Fig. 26) near the terminal plate. (2) Using a screwdriver, loosen the terminal screw on the terminal plate. (3) Insert the wire and tighten the terminal screw com- pletely using a screwdriver. b) For Outdoor Unit For solid core wiring (or F-cable) (1) Cut the wire end with a cutting pliers, then strip the insulation to expose the solid wire about 15/16 (25 mm). (Fig. 27) (2) Using a screwdriver, remove the terminal screw(s) on the terminal plate. (3) Using the pliers, bend the solid wire to form a loop suitable for the terminal screw. (4) Shape the loop wire properly, place it on the termi- nal plate and fix it securely with the removed termi- nal screw using a screwdriver. For stranded wiring (1) Cut the wire end with a cutting pliers, then strip the insulation to expose the stranded wiring about 3/8 (10 mm) and tightly twist the wire ends. (Figs. 28 and 29) (2) Using a screwdriver, remove the terminal screw(s) on the terminal plate. (3) Using a ring connector fastener or pliers, securely clamp each stripped wire end with a ring connector. (Fig. 28) (4) Place the ring connector wire, and replace and tighten the removed terminal screw using a screw- driver. (Fig. 30) Solid wire Loop Insulation Strip 15/16 (25 mm) Fig. 27 STRIP SIZE9/32" (7 mm) (ACTUAL SIZE) Fig. 26 Stranded wire Ring connector Strip 3/8 (10 mm) Fig. 28 Screw Ring connector Terminal plate WireSpecial washer Fig. 30 Screw and special washer Ring connector Wire WARNINGLoose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. There- fore, be sure all wiring is tightly connected. Twist wire ends Fig. 29 5-4. How to Connect Wiring to the Terminal