Home > Panasonic > Air Conditioner > Panasonic Cu 3ke19nbucu Technical Service Manual

Panasonic Cu 3ke19nbucu Technical Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Cu 3ke19nbucu Technical Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							7.  FUNCTIONS
    7-1.  Explanation of Functions
    The numerical values such as temperature, frequency, time and current in parentheses are an example 
    of CU-4KE31NBU and the values are different from the other models.
    Control/conditions
    INITIAL
    Breaker is ON. Power is supplied to the indoor and outdoor unit 
    control circuits, however the unit remains stopped.
    Positioning of the outdoor unit electric expansion 
    valve is performed.
    The ON/OFF operation 
    button on the remote 
    controller is pressed.If automatic operation mode has been selected 
    with the remote controller, operation begins in 
    HEAT, SENSOR DRY, or COOL mode 
    depending on the room temperature and 
    outdoor temperature at the time operation starts.
    Depending on the operational mode, refer to the HEAT, SENSOR DRY, or COOL item.This applies in the case of automatic 
    HEAT/COOL operation.
    HEAT
    Unit operation Explanation
    The ON/OFF operation 
    button on the remote 
    controller is pressed.The unit is forced to stop for 3 minutes after 
    the power is turned ON, or 3 minutes after the 
    compressor stops, in order to protect the 
    compressor.
    The frequency is increased at the rate of 1 Hz 
    every 0.5 seconds. Operation lamp illuminates.
    Indoor fan is stopped to prevent cold air from 
    being emitted.
    Outdoor unit begins operating after 
    forced-stop is canceled.
    This is in order to stabilize the return of oil to the 
    compressor. When the frequency reaches    Hz,frequency 
    increases are stopped for a period of    seconds. 
    (Refor to Table 2 "Freguency control".)
    If the indoor and outdoor temperatures are high, 
    the current peak cut-off activates, stopping any 
    increases in frequency. The frequency then increases.
    The thermostat turns 
    OFF.The outdoor unit stops. (It does not stop if the 
    thermostat for another indoor unit is ON.)
    Approximately 30 seconds after the 
    thermostat turns OFF, the indoor fan is 
    stopped.The indoor fan is stopped.
    The indoor and outdoor 
    temperatures are high.The outdoor unit starts automatically after 3 
    minutes.
    During these 3 minutes, a low-pressure 
    pressure balance is achieved, allowing the 
    compressor to start more easily.In order to protect the compressor, the outdoor 
    unit will not operate for 3 minutes after the 
    thermostat turns OFF, even if the room 
    temperature drops below the desired 
    temperature. The room temperature 
    has reached the desired 
    temperature.Operating frequency is stabilized in order to 
    maintain a comfortable environment. The indoor temperature and the remote 
    controller temperature setting are 
    approximately equal.
    Depending on the relationship between the 
    remote controller temperature setting and the 
    room temperature, the compressor may stop 
    temporarily (in other words, the thermostat 
    may turn OFF). When the indoor coil temperature rises,
    the compressor starts,
    the outdoor fan starts,
    and the indoor fan changes from "LL" 
    to the set fan speed.
    The amount of heat pump exceeds the amount 
    of heat radiation from the room.
    Therefore, there is no need to further increase 
    the compressor capacity, and the frequency is 
    stabilized or lowered.The frequency is not increased, even if 
    there is a difference between the room 
    temperature and the desired temperature.
    In some cases, the frequency may be 
    decreased.
    NOTE
    71 
    						
    							Control/conditions
    HEAT
    When defrost operation 
    begins, frost has formed 
    on the outdoor unit 
    (when the ambient air 
    temperature is low).Defrost operation begins based on outdoor 
    heat exchanger temperature and outdoor 
    air temperature conditions.
    Non-stop defrost (Refer to Fig. 1)
    1. After HEAT operation begins, the temperature 
    of the outdoor heat exchanger is at or below the 
    L1 line for 35 minutes.
    (If outdoor air temperature is less than 26.6 °F,
    the time is 48 minutes) 
    2. After HEAT operation begins, the temperature 
    of the outdoor heat exchanger is at or below the 
    L2 line for 120 minutes.
    The 4-way valve remains ON during defrost. Non-stop defrost
    Unit operation Explanation
    The outdoor fan stops and the solenoid 
    valve turns ON, allowing the refrigerant to
    bypass the indoor unit. Indoor fan : Stopped
    Outdoor fan : Stopped
    Compressor : 80 Hz
    Solenoid valve (for hot gas bypass): ON
    4-way valve : Remains ON
    Operation lamp : Red and orange ON 
                                alternately
    Defrost release Indoor fan turns ON.
    After 10 seconds, the solenoid valve 
    (for hot gas bypass) turns OFF.
    When the cold air feel has disappeared, 
    the indoor fan starts and gradually increases 
    speed until it reaches the set speed.
    STOP
    [Clean defrost]
    Defrost is performed 
    when the outdoor unit is 
    stopped, and the 
    temperature of the 
    outdoor unit coil is at or 
    below the L1 line. 
    (Refer to Fig. 1.)All indicator lamps turn OFF. The indoor and 
    outdoor units stop.
    The operating frequency during defrost is 
    80 Hz. (Frequency is lowered if the current 
    peak cut-off function is activated.)
    The maximum length of a single defrost 
    operation is 12 minutes.
    For the outdoor heat exchanger temperature 
    conditions for ending defrost, refer to Table 1.
    Operation is restarted 
    within 4 hours (only when 
    AUTO mode is selected 
    with the remote 
    controller).Within 4 hours after operation was stopped, it is 
    assumed that there has been no significant 
    change in the indoor and outdoor temperatures, 
    and the previous conditions (HEAT) are stored. Starts operating in the same operating mode 
    (HEAT) and with the same temperature 
    settings as before operation was stopped.
    Operation starts after 4 
    hours or more have 
    passed.New operation begins based on the 
    temperature conditions at the time the 
    ON/OFF button is pressed.
    The thermostat turns ON. The unit operated before, and the temperature of 
    the indoor heat exchanger is relatively warm.
    Therefore,the fan speed may start at the set fan 
    speed at the same time that the thermostat turns 
    ON. The indoor unit is stopped.
    72 
    						
    							Control/conditions
    COOL
    The ON/OFF operation 
    button on the remote 
    controller is pressed.
    The room temperature 
    has reached the 
    desired temperature.The outdoor unit does not operate for 3 minutes 
    even after the breaker is turned ON.
    This is in order to stabilize the return of oil to the 
    compressor. The outdoor unit starts.
    (Compressor and the outdoor fan start.)
    When the frequency reaches    Hz, 
    frequency increases are stopped for a period 
    of    seconds. (Refer to Table 2.)
    If the indoor and outdoor temperatures are high, 
    the current peak cut-off activates, stopping 
    any increases in frequency. The frequency then increases.
    Operating frequency is stabilized in order to 
    maintain a comfortable environment. The indoor temperature and the desired 
    temperature are approximately equal.
    The thermostat turns 
    ON again. After 3 minutes, the outdoor unit begins operating 
    automatically.
    During these 3 minutes, a pressure balance is 
    achieved, allowing the compressor to start 
    more easily. After the thermostat turns ON again, the 
    outdoor unit will not operate for 3 minutes, 
    even if the room temperature increases 
    above the desired temperature.
    Operation is restarted 
    within 4 hours (only when 
    AUTO mode is selected 
    with the remote 
    controller).Within 4 hours after operation was stopped, it is 
    assumed that there has been no significant 
    change in the indoor and outdoor temperatures, 
    and the previous conditions (COOL) are stored. Starts operating in the same operating mode 
    (COOL) and with the same temperature 
    settings as before operation was stopped.
    Operation starts after 4 
    hours or more have 
    passed.New operating mode is determined based on 
    the temperature conditions at the time the 
    ON/OFF operation button is pressed.
    Stop All indicator lamps turn OFF. The indoor and 
    outdoor units stop.
    Freeze prevention In order to protect against freezing, the 
    compressor stops temporarily, until the 
    temperature of the indoor heat exchanger has 
    risen.
    The thermostat turns
    OFF.The outdoor unit stops. (It does not stop if the
    thermostart for another indoor unit is ON.)
    Unit operation Explanation
    The operation lamp illuminates.
    The indoor fan operates at the set fan speed.
    The outdoor unit stops.
    When the temperature of the indoor heat 
    exchanger drops to approximately 35.6 °F 
    or below, the compressor turns OFF, the 
    outdoor fan turns OFF, and the indoor fan 
    continues operating with no changes.
    Approximately 3 minutes later, if the 
    temperature of the indoor heat exchanger 
    is adove 46.4 °F, the system returns to its 
    original conditions.
    The frequency is increased at the rate of 0.5 
    Hz every 1 seconds.
    Table 1
    Outdoor heat
    exchanger temperature (°F)
    Fig. 1
    Outdoor air
    temperature (°F) (- 4) 0
    (21.2)
    (19.4)
    (-11.2)
    (-13.0) L2
    L1
    Temperature of releasing
    *1 The temperature for releasing of defrosting is (68 °F) or higher when the 
    outdoor air temperature is less than 32 °F. Defrost operation time
    Heat exchanger
    temperature for 
    releasing defrosting
    Less than 2 minutes 2 minutes or more
    No releasing 57.2 °F or higher (*1)
    73 
    						
    							Control/conditions
    SENSOR 
    DRY
    (1/f fluctuation fan)
    The ON/OFF operation 
    button on the remote 
    controller is pressed.The outdoor unit does not operate for 3 minutes 
    even after the breaker is turned ON.
    This is in order to stabilize the return of oil to the 
    compressor. The outdoor unit starts.
    (Compressor and the outdoor fan start.)
    When the frequency reaches    Hz, 
    frequency increases are stopped for a period 
    of    seconds. (Refer to Table 2.)
    DRY B operation
    If the indoor and outdoor temperatures are high, 
    the current peak cut-off activates, stopping 
    any increases in frequency. The frequency then increases.
    Unit operation Explanation
    The operation lamp illuminates.
    The indoor fan operates at the set fan speed.
    The outdoor unit stops.
    The room temperature 
    reaches the desired 
    temperature, and there 
    is no need for further 
    cooling.Operating frequency is stabilized in order to 
    maintain a comfortable environment.
    The room temperature is 
    59 °F or higher, and is 
    slightly too cold.
    The compressor operates on a 3-minutes ON, 
    6-minutes OFF cycle, to prevent the room 
    temperature from dropping too much. DRY operation starts
    DRY A operation
    The room temperature is 
    below 59 °F.When monitoring operation begins, the 
    compressor stops, and the indoor fan operates at 
    "LL" (very low) speed. Monitoring operation begins.
    The indoor fan changes between "Low" 
    and "LL" (very low) over a 6-minute cycle. 
    This is 1/f fluctuation fan operation. 
    (Refer to Fig. 2.)
    The indoor fan changes between "Low" 
    and "LL" (very low) over a 6-minute cycle. 
    This is 1/f fluctuation fan operation.    
    After appoximately 3 minutes, the 
    compressor turns OFF, the outdoor fan 
    turns OFF, and the indoor fan turns OFF.
    After approximately 6 minutes, the 
    conditions return to (1). (1)
    (2)
    (3)
    The frequency is increased at the rate of 0.5 
    Hz every 1 seconds.
    Operates to effectively dehumidify the air while 
    not excessively reducing the indoor 
    temperature.
    The indoor unit operates at 1/f fluctuation fan 
    operation, at a fan speed that does not cause 
    a chilly feeling.
    Frequency control
        (Hz)
    (25) Hz
    (35) Hz
    (45) Hz
    (55) HzOutdoor air temperature is below 32 °F.
    (120) seconds
    (60) seconds
    (60) seconds
    (180) seconds
    Table 2
         (senconds)
    Outdoor air temperature is 32 °F or higher.
    (60) seconds
    (30) seconds
    (30) seconds
    (90) seconds
    74 
    						
    							1/f fluctuation fan
    250
    200
    6-minute cycle
    Fig. 2
    150
    100 (Step)
    50
    0
    75 
    						
    							< Low Ambient Cooling Operation >
    When the mode is switched from cooling opration to low ambient cooling operation,
    the compressor is stopped for 150 seconds temporarily.
    Outdoor fan speed [ rpm ]
    Outdoor air temperature32 °F ( °C )
    When the mode has been switched to low ambient cooling operation,
    the outdoor fan speed is lowered as the outdoor air temperature falls.
    When the outdoor air temperature reaches 57.2 °F (14 °C ) or less during the cooling operation,
    the operation mode is switched to low ambient cooling operation.
    The following protective actions are available to prevent the compressor from operating
    with abnormal loads.
    At that time, they initiate thermo-off ( stopping the outdoor unit ) of the air conditioner.
    When the outdoor air temperature reaches 62.6 °F (17 °C ) or more during the low ambient
    cooling operation, the operation mode is switched to cooling operation.
    8.6 (-13)14 (-10)
    Compressor
    Indoor fanOFF
    ON ON Outdoor air temp.
     °F ( °C )
    ON
    76 
    						
    							7-2.  Protective Functions
    7-2-1.  Defrost Detection and Release
    (2) Clean defrost
    If all indoor units are stopped during HEAT operation, and frost is detected at the L1 line, and the 
    conditions for defrost are met, then defrost operation occurs, and the unit stops after defrost is completed. (1) Non-stop defrosting
    Heating operation
    NOTEDefrost does not occur during HIGH POWER operation.
    If other stopped indoor units are started during defrost operation, they begin operating in 
    defrost mode.
    Frost detection
    Non-stop defrosting
    Releasing of defrosting
    Defrosting sequence 4-way valve ON
    Defrost detection occurs in either of the following cases:
    The temperature of the heat exchanger remains at or below 
    the L1 line for 35 minutes after the start of HEAT operation.
    Compressor
    Outdoor fan
    Solenoid valve 
    (for hot gas bypass)
    Temperature of the outdoor heat exchanger is at or above the 
    temperature shown in the table below.
    Temperature of releasing
    *1 The temperature for releasing of defrosting is (68 °F) or higher when the 
    outdoor air temperature is less than 32 °F. Defrost operation time
    Defrost operation has continued for 12 minutes (max. length). Indoor fan(80 Hz) operation (4-way valve ON)
    OFF
    ON
    OFF
    The temperature of the heat exchanger remains at or below 
    the L2 line for 120 minutes after the start of HEAT operation.
    Outdoor heat
    exchanger temperature (°F)
    Outdoor air
    temperature (°F) (- 4) 0
    ( 21.2)
    ( 19.4)
    (-11.2)
    (-13.0) L2
    L1
    Less than 2 minutes 2 minutes or more
    No releasing 57.2 °F or higher (*1)
    The numerical values such as temperature, frequency, time and current in parentheses are an example 
    of CU-4KE31NBU and the values are different from the other models.NOTE
    Heat exchanger
    temperature for 
    releasing defrosting
    77 
    						
    							7-2-2.  Current Control
    The operating current may rise as a result of causes including increasing heating or cooling loads or decreases in power 
    voltage. In these cases, the operating frequency is automatically reduced, or operation is stopped, in order to control 
    the operating current so that it is (20 A) or less.
    The operating frequency is reduced automatically, or operation is stopped, in order to control the operating 
    current so that it is at or below the values shown in the table below.
    (20A)
    HEAT Power breakers and fuses will not be tripped.
    Operation can continue during this period with somewhat reduced heating or cooling capacity.
    Operation at normal capacity is restored when the cause of the current rise is eliminated.
    Description of function
    •
    •
    •
    Example of operation for heating
    Current(A)
    Frequency (Hz) Trip
    Hz reduction
    Hz increase
    prohibitHz reduction
    Hz increase prohibit
    Hz reduction
    Hz increase prohibit
    (16)
    (15.6)
    0
    (30)Example of operation during cooling
    Frequency
    Frequency CurrentStops operation
    Approx.3 minutesPower Point C
    Point B
    Point A (20A)
    (17A)
    (16.6A)
    Target
    frequency
    Operates at the target frequency at Point A and below.
    Stops increases to the frequency between Points A and B.
    Reduces the frequency by 1 Hz per 0.5 seconds when Point B is exceeded.
    Stops operation, and restarts it appoximately 3 minutes later, if Point C is exceeded.
    (May operate when sudden voltage fluctuations occur.    Indicates trouble.) •
    •
    •
    •
    As a result:
    (1) Automatic frequency control
    The operating frequency upper limits shown in the figure below are established for frequency reduction and 
    increase-prohibit.
    (2) Current control
    NOTE
    During defrost operation, the COOL current setting value is used.
    COOL
    (20.0) (20.0)
    (17.0) (17.0)
    (16.6) Point C (peak cut trip)
    Point B (Hz reduction)
    Point A (Hz increase prohibit) (16.6)
    78 
    						
    							7-2-5.  Control at HEAT Start-up
    If HEAT operation is started when the outdoor air temperature is 59 °F or below, the unit operates at the HEAT start-up 
    frequency (70 Hz or above).
    Reset conditions
    The compressor frequency exceeds the start-up frequency of (70 Hz).
    The compressor thermostat is OFF.
    Frequency reduction for indoor high-load control has occurred.
    The outdoor air temperature is above 59 °F.
    The main-unit switch on one or more indoor units is set to TEST run. (1)
    (2)
    (3)
    (4)
    (5)
    (230)
    (223)
    (212)Trip
    5Hz every 30 sec. reduction
    2Hz every 30 sec. reduction
    No controlIncrease
    prohibit range
    (Hz reduction) (°F)
    Compressor discharge temperature(194)
    Within the increase-prohibit range, the range changes 
    to the Hz reduction range (2 Hz every 30 seconds) if 
    the compressor temperature rises by 4 °F. * Operation starts at (8 Hz), and the start current is less than the normal operating  current. This prevents the flickering 
    of fluorescent lights or television screens that occurs when ordinary A/C units start.
    7-2-3.  Low Start Current
    To protect the compressor coil from overheating, the operating frequency is controlled based on the compressor 
    discharge temperature.
    7-2-4.  Compressor Temperature Control
    79 
    						
    							8.  TROUBLESHOOTING (BEFORE CALLING FOR SERVICE)
    8-1.  Precautions before Performing Inspection or Repair
    Both the indoor unit and outdoor unit include electronic control circuits. 
    Be sure to pay attention to the following before inspecting or repairing the 
    outdoor-side electronic circuits.
    High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an 
    electrical charge (charging voltage DC 311 V) even after the power is turned OFF, and some time is required 
    for the charge to dissipate.
    Be careful not to touch any electrified parts before the control circuit board Power Lamp (red) turns OFF.
    If the outdoor control circuit board is normal, approximately 180 seconds will be required for the charge to 
    dissipate. However, allow at least 30 minutes for the charge to dissipate if it is thought there might be trouble 
    with the outdoor control circuit board.
    For example, if the outdoor control circuit board fuse has blown, approximately 30 minutes will be required to 
    discharge the high-capacity electrolytic capacitors.
    80 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Cu 3ke19nbucu Technical Service Manual