Panasonic Cu 3ke19nbucu Technical Service Manual
Have a look at the manual Panasonic Cu 3ke19nbucu Technical Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
7. FUNCTIONS 7-1. Explanation of Functions The numerical values such as temperature, frequency, time and current in parentheses are an example of CU-4KE31NBU and the values are different from the other models. Control/conditions INITIAL Breaker is ON. Power is supplied to the indoor and outdoor unit control circuits, however the unit remains stopped. Positioning of the outdoor unit electric expansion valve is performed. The ON/OFF operation button on the remote controller is pressed.If automatic operation mode has been selected with the remote controller, operation begins in HEAT, SENSOR DRY, or COOL mode depending on the room temperature and outdoor temperature at the time operation starts. Depending on the operational mode, refer to the HEAT, SENSOR DRY, or COOL item.This applies in the case of automatic HEAT/COOL operation. HEAT Unit operation Explanation The ON/OFF operation button on the remote controller is pressed.The unit is forced to stop for 3 minutes after the power is turned ON, or 3 minutes after the compressor stops, in order to protect the compressor. The frequency is increased at the rate of 1 Hz every 0.5 seconds. Operation lamp illuminates. Indoor fan is stopped to prevent cold air from being emitted. Outdoor unit begins operating after forced-stop is canceled. This is in order to stabilize the return of oil to the compressor. When the frequency reaches Hz,frequency increases are stopped for a period of seconds. (Refor to Table 2 "Freguency control".) If the indoor and outdoor temperatures are high, the current peak cut-off activates, stopping any increases in frequency. The frequency then increases. The thermostat turns OFF.The outdoor unit stops. (It does not stop if the thermostat for another indoor unit is ON.) Approximately 30 seconds after the thermostat turns OFF, the indoor fan is stopped.The indoor fan is stopped. The indoor and outdoor temperatures are high.The outdoor unit starts automatically after 3 minutes. During these 3 minutes, a low-pressure pressure balance is achieved, allowing the compressor to start more easily.In order to protect the compressor, the outdoor unit will not operate for 3 minutes after the thermostat turns OFF, even if the room temperature drops below the desired temperature. The room temperature has reached the desired temperature.Operating frequency is stabilized in order to maintain a comfortable environment. The indoor temperature and the remote controller temperature setting are approximately equal. Depending on the relationship between the remote controller temperature setting and the room temperature, the compressor may stop temporarily (in other words, the thermostat may turn OFF). When the indoor coil temperature rises, the compressor starts, the outdoor fan starts, and the indoor fan changes from "LL" to the set fan speed. The amount of heat pump exceeds the amount of heat radiation from the room. Therefore, there is no need to further increase the compressor capacity, and the frequency is stabilized or lowered.The frequency is not increased, even if there is a difference between the room temperature and the desired temperature. In some cases, the frequency may be decreased. NOTE 71
Control/conditions HEAT When defrost operation begins, frost has formed on the outdoor unit (when the ambient air temperature is low).Defrost operation begins based on outdoor heat exchanger temperature and outdoor air temperature conditions. Non-stop defrost (Refer to Fig. 1) 1. After HEAT operation begins, the temperature of the outdoor heat exchanger is at or below the L1 line for 35 minutes. (If outdoor air temperature is less than 26.6 °F, the time is 48 minutes) 2. After HEAT operation begins, the temperature of the outdoor heat exchanger is at or below the L2 line for 120 minutes. The 4-way valve remains ON during defrost. Non-stop defrost Unit operation Explanation The outdoor fan stops and the solenoid valve turns ON, allowing the refrigerant to bypass the indoor unit. Indoor fan : Stopped Outdoor fan : Stopped Compressor : 80 Hz Solenoid valve (for hot gas bypass): ON 4-way valve : Remains ON Operation lamp : Red and orange ON alternately Defrost release Indoor fan turns ON. After 10 seconds, the solenoid valve (for hot gas bypass) turns OFF. When the cold air feel has disappeared, the indoor fan starts and gradually increases speed until it reaches the set speed. STOP [Clean defrost] Defrost is performed when the outdoor unit is stopped, and the temperature of the outdoor unit coil is at or below the L1 line. (Refer to Fig. 1.)All indicator lamps turn OFF. The indoor and outdoor units stop. The operating frequency during defrost is 80 Hz. (Frequency is lowered if the current peak cut-off function is activated.) The maximum length of a single defrost operation is 12 minutes. For the outdoor heat exchanger temperature conditions for ending defrost, refer to Table 1. Operation is restarted within 4 hours (only when AUTO mode is selected with the remote controller).Within 4 hours after operation was stopped, it is assumed that there has been no significant change in the indoor and outdoor temperatures, and the previous conditions (HEAT) are stored. Starts operating in the same operating mode (HEAT) and with the same temperature settings as before operation was stopped. Operation starts after 4 hours or more have passed.New operation begins based on the temperature conditions at the time the ON/OFF button is pressed. The thermostat turns ON. The unit operated before, and the temperature of the indoor heat exchanger is relatively warm. Therefore,the fan speed may start at the set fan speed at the same time that the thermostat turns ON. The indoor unit is stopped. 72
Control/conditions COOL The ON/OFF operation button on the remote controller is pressed. The room temperature has reached the desired temperature.The outdoor unit does not operate for 3 minutes even after the breaker is turned ON. This is in order to stabilize the return of oil to the compressor. The outdoor unit starts. (Compressor and the outdoor fan start.) When the frequency reaches Hz, frequency increases are stopped for a period of seconds. (Refer to Table 2.) If the indoor and outdoor temperatures are high, the current peak cut-off activates, stopping any increases in frequency. The frequency then increases. Operating frequency is stabilized in order to maintain a comfortable environment. The indoor temperature and the desired temperature are approximately equal. The thermostat turns ON again. After 3 minutes, the outdoor unit begins operating automatically. During these 3 minutes, a pressure balance is achieved, allowing the compressor to start more easily. After the thermostat turns ON again, the outdoor unit will not operate for 3 minutes, even if the room temperature increases above the desired temperature. Operation is restarted within 4 hours (only when AUTO mode is selected with the remote controller).Within 4 hours after operation was stopped, it is assumed that there has been no significant change in the indoor and outdoor temperatures, and the previous conditions (COOL) are stored. Starts operating in the same operating mode (COOL) and with the same temperature settings as before operation was stopped. Operation starts after 4 hours or more have passed.New operating mode is determined based on the temperature conditions at the time the ON/OFF operation button is pressed. Stop All indicator lamps turn OFF. The indoor and outdoor units stop. Freeze prevention In order to protect against freezing, the compressor stops temporarily, until the temperature of the indoor heat exchanger has risen. The thermostat turns OFF.The outdoor unit stops. (It does not stop if the thermostart for another indoor unit is ON.) Unit operation Explanation The operation lamp illuminates. The indoor fan operates at the set fan speed. The outdoor unit stops. When the temperature of the indoor heat exchanger drops to approximately 35.6 °F or below, the compressor turns OFF, the outdoor fan turns OFF, and the indoor fan continues operating with no changes. Approximately 3 minutes later, if the temperature of the indoor heat exchanger is adove 46.4 °F, the system returns to its original conditions. The frequency is increased at the rate of 0.5 Hz every 1 seconds. Table 1 Outdoor heat exchanger temperature (°F) Fig. 1 Outdoor air temperature (°F) (- 4) 0 (21.2) (19.4) (-11.2) (-13.0) L2 L1 Temperature of releasing *1 The temperature for releasing of defrosting is (68 °F) or higher when the outdoor air temperature is less than 32 °F. Defrost operation time Heat exchanger temperature for releasing defrosting Less than 2 minutes 2 minutes or more No releasing 57.2 °F or higher (*1) 73
Control/conditions SENSOR DRY (1/f fluctuation fan) The ON/OFF operation button on the remote controller is pressed.The outdoor unit does not operate for 3 minutes even after the breaker is turned ON. This is in order to stabilize the return of oil to the compressor. The outdoor unit starts. (Compressor and the outdoor fan start.) When the frequency reaches Hz, frequency increases are stopped for a period of seconds. (Refer to Table 2.) DRY B operation If the indoor and outdoor temperatures are high, the current peak cut-off activates, stopping any increases in frequency. The frequency then increases. Unit operation Explanation The operation lamp illuminates. The indoor fan operates at the set fan speed. The outdoor unit stops. The room temperature reaches the desired temperature, and there is no need for further cooling.Operating frequency is stabilized in order to maintain a comfortable environment. The room temperature is 59 °F or higher, and is slightly too cold. The compressor operates on a 3-minutes ON, 6-minutes OFF cycle, to prevent the room temperature from dropping too much. DRY operation starts DRY A operation The room temperature is below 59 °F.When monitoring operation begins, the compressor stops, and the indoor fan operates at "LL" (very low) speed. Monitoring operation begins. The indoor fan changes between "Low" and "LL" (very low) over a 6-minute cycle. This is 1/f fluctuation fan operation. (Refer to Fig. 2.) The indoor fan changes between "Low" and "LL" (very low) over a 6-minute cycle. This is 1/f fluctuation fan operation. After appoximately 3 minutes, the compressor turns OFF, the outdoor fan turns OFF, and the indoor fan turns OFF. After approximately 6 minutes, the conditions return to (1). (1) (2) (3) The frequency is increased at the rate of 0.5 Hz every 1 seconds. Operates to effectively dehumidify the air while not excessively reducing the indoor temperature. The indoor unit operates at 1/f fluctuation fan operation, at a fan speed that does not cause a chilly feeling. Frequency control (Hz) (25) Hz (35) Hz (45) Hz (55) HzOutdoor air temperature is below 32 °F. (120) seconds (60) seconds (60) seconds (180) seconds Table 2 (senconds) Outdoor air temperature is 32 °F or higher. (60) seconds (30) seconds (30) seconds (90) seconds 74
1/f fluctuation fan 250 200 6-minute cycle Fig. 2 150 100 (Step) 50 0 75
< Low Ambient Cooling Operation > When the mode is switched from cooling opration to low ambient cooling operation, the compressor is stopped for 150 seconds temporarily. Outdoor fan speed [ rpm ] Outdoor air temperature32 °F ( °C ) When the mode has been switched to low ambient cooling operation, the outdoor fan speed is lowered as the outdoor air temperature falls. When the outdoor air temperature reaches 57.2 °F (14 °C ) or less during the cooling operation, the operation mode is switched to low ambient cooling operation. The following protective actions are available to prevent the compressor from operating with abnormal loads. At that time, they initiate thermo-off ( stopping the outdoor unit ) of the air conditioner. When the outdoor air temperature reaches 62.6 °F (17 °C ) or more during the low ambient cooling operation, the operation mode is switched to cooling operation. 8.6 (-13)14 (-10) Compressor Indoor fanOFF ON ON Outdoor air temp. °F ( °C ) ON 76
7-2. Protective Functions 7-2-1. Defrost Detection and Release (2) Clean defrost If all indoor units are stopped during HEAT operation, and frost is detected at the L1 line, and the conditions for defrost are met, then defrost operation occurs, and the unit stops after defrost is completed. (1) Non-stop defrosting Heating operation NOTEDefrost does not occur during HIGH POWER operation. If other stopped indoor units are started during defrost operation, they begin operating in defrost mode. Frost detection Non-stop defrosting Releasing of defrosting Defrosting sequence 4-way valve ON Defrost detection occurs in either of the following cases: The temperature of the heat exchanger remains at or below the L1 line for 35 minutes after the start of HEAT operation. Compressor Outdoor fan Solenoid valve (for hot gas bypass) Temperature of the outdoor heat exchanger is at or above the temperature shown in the table below. Temperature of releasing *1 The temperature for releasing of defrosting is (68 °F) or higher when the outdoor air temperature is less than 32 °F. Defrost operation time Defrost operation has continued for 12 minutes (max. length). Indoor fan(80 Hz) operation (4-way valve ON) OFF ON OFF The temperature of the heat exchanger remains at or below the L2 line for 120 minutes after the start of HEAT operation. Outdoor heat exchanger temperature (°F) Outdoor air temperature (°F) (- 4) 0 ( 21.2) ( 19.4) (-11.2) (-13.0) L2 L1 Less than 2 minutes 2 minutes or more No releasing 57.2 °F or higher (*1) The numerical values such as temperature, frequency, time and current in parentheses are an example of CU-4KE31NBU and the values are different from the other models.NOTE Heat exchanger temperature for releasing defrosting 77
7-2-2. Current Control The operating current may rise as a result of causes including increasing heating or cooling loads or decreases in power voltage. In these cases, the operating frequency is automatically reduced, or operation is stopped, in order to control the operating current so that it is (20 A) or less. The operating frequency is reduced automatically, or operation is stopped, in order to control the operating current so that it is at or below the values shown in the table below. (20A) HEAT Power breakers and fuses will not be tripped. Operation can continue during this period with somewhat reduced heating or cooling capacity. Operation at normal capacity is restored when the cause of the current rise is eliminated. Description of function • • • Example of operation for heating Current(A) Frequency (Hz) Trip Hz reduction Hz increase prohibitHz reduction Hz increase prohibit Hz reduction Hz increase prohibit (16) (15.6) 0 (30)Example of operation during cooling Frequency Frequency CurrentStops operation Approx.3 minutesPower Point C Point B Point A (20A) (17A) (16.6A) Target frequency Operates at the target frequency at Point A and below. Stops increases to the frequency between Points A and B. Reduces the frequency by 1 Hz per 0.5 seconds when Point B is exceeded. Stops operation, and restarts it appoximately 3 minutes later, if Point C is exceeded. (May operate when sudden voltage fluctuations occur. Indicates trouble.) • • • • As a result: (1) Automatic frequency control The operating frequency upper limits shown in the figure below are established for frequency reduction and increase-prohibit. (2) Current control NOTE During defrost operation, the COOL current setting value is used. COOL (20.0) (20.0) (17.0) (17.0) (16.6) Point C (peak cut trip) Point B (Hz reduction) Point A (Hz increase prohibit) (16.6) 78
7-2-5. Control at HEAT Start-up If HEAT operation is started when the outdoor air temperature is 59 °F or below, the unit operates at the HEAT start-up frequency (70 Hz or above). Reset conditions The compressor frequency exceeds the start-up frequency of (70 Hz). The compressor thermostat is OFF. Frequency reduction for indoor high-load control has occurred. The outdoor air temperature is above 59 °F. The main-unit switch on one or more indoor units is set to TEST run. (1) (2) (3) (4) (5) (230) (223) (212)Trip 5Hz every 30 sec. reduction 2Hz every 30 sec. reduction No controlIncrease prohibit range (Hz reduction) (°F) Compressor discharge temperature(194) Within the increase-prohibit range, the range changes to the Hz reduction range (2 Hz every 30 seconds) if the compressor temperature rises by 4 °F. * Operation starts at (8 Hz), and the start current is less than the normal operating current. This prevents the flickering of fluorescent lights or television screens that occurs when ordinary A/C units start. 7-2-3. Low Start Current To protect the compressor coil from overheating, the operating frequency is controlled based on the compressor discharge temperature. 7-2-4. Compressor Temperature Control 79
8. TROUBLESHOOTING (BEFORE CALLING FOR SERVICE) 8-1. Precautions before Performing Inspection or Repair Both the indoor unit and outdoor unit include electronic control circuits. Be sure to pay attention to the following before inspecting or repairing the outdoor-side electronic circuits. High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an electrical charge (charging voltage DC 311 V) even after the power is turned OFF, and some time is required for the charge to dissipate. Be careful not to touch any electrified parts before the control circuit board Power Lamp (red) turns OFF. If the outdoor control circuit board is normal, approximately 180 seconds will be required for the charge to dissipate. However, allow at least 30 minutes for the charge to dissipate if it is thought there might be trouble with the outdoor control circuit board. For example, if the outdoor control circuit board fuse has blown, approximately 30 minutes will be required to discharge the high-capacity electrolytic capacitors. 80