Home > Panasonic > Air Conditioner > Panasonic Cu 3ke19nbucu Technical Service Manual

Panasonic Cu 3ke19nbucu Technical Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Cu 3ke19nbucu Technical Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							9-5.  In Case of Compressor Malfunction 
    CAUTIONShould the compressor malfunction, be sure to make the switch to a replacement 
    compressor as quickly as possible.
    Use only the tools indicated exclusively for R410A.     See "9-3. Tools Specifically 
    for R410A."
    9-5-1.  Procedure for Replacing Compressor
    (1) Recovering refrigerant
    Any remaining refrigerant inside the unit should not be 
    released to the atmosphere, but recovered using the 
    refrigerant recovery unit for R410A. 
    Do not reuse the recovered refrigerant, since it will contain 
    impurities. 
    (2) Replacing Compressor
    Soon after removing seals of both discharge and suction 
    tubes of the new compressor, replace it quickly.
    (3) Checking for sealing
    Use nitrogen gas for the pressurized gas, and never use a 
    refrigerant other than R410A. Also do not use oxygen or 
    any flammable gas.
    (4) Evacuation
    Use a solenoid valve-installed vacuum pump so that 
    even if power is cut off in the middle of evacuation of air 
    due to a power interruption, the valve will prevent the 
    pump oil from flowing back.
    The equipment may be damaged if moisture remains in 
    the tubing, thus carry out the evacuation thoroughly.
    When using a vacuum pump with exhaust air volume more 
    than 0.883 cu.ft./min. and ultimate vacuum pressure rate 
    of 50 micron Hg.
    Standard time for evacuation
    (1) Recover refrigerant
    OK
    (2) Replace compressor
    OK
    (3) Check for sealing
    OK
    (4) Evacuation
    OK
    (5) Recharge
    Length of tubing
    Evacuation timeLess than 33 ft. (10 m)
    More than 10 minutesMore than 33 ft. (10 m)
    More than 15 minutes
    91 
    						
    							Valve
    Single valve
    Charge liquid refrigerant with 
    cylinder in up-side-down position.
    Single valve (with siphon tube)
    Charge with cylinder in normal position.Liquid
    Valve
    Liquid
    Charging
    cylinder
    Open
    Refrigerant
    cylinder
    Liquid
    NO!
    CAUTIONNever charge a large amount 
    of liquid refrigerant at once to 
    the unit. This may cause 
    damage to the compressor.
    CAUTIONTo prevent the composition 
    of R410A from changing, 
    never bleed the refrigerant 
    gas into the atmosphere 
    while transferring the 
    refrigerant. (Fig. 3) (5) Recharging
    Be sure to charge the specified amount of 
    refrigerant in liquid state using the service port 
    of the wide tube service valve. The proper 
    amount is listed on the unit's nameplate. 
    When the entire amount cannot be charged all at 
    once, charge gradually while operating the unit in 
    Cooling Operation.
    When charging with a refrigerant cylinder, use an 
    electronic scale for charging refrigerant. In this 
    case, if the volume of refrigerant in the cylinder 
    becomes less than 20% of the fully-charged 
    amount, the composition of the refrigerant starts 
    to change. Thus, do not use the refrigerant if 
    the amount in the charging cylinder is less 
    than 20%.
    Also, charge the minimum necessary amount to 
    the charging cylinder before using it to charge 
    the air conditioning unit.
    Example:
    In case of charging refrigerant to a unit requiring 
    1.68 lb. (0.76 Kg) using a capacity of a 22 lb. (10 
    Kg) cylinder, the minimum necessary amount for 
    the cylinder is: 
    1.68 + 22    0.20 = 6.08 lb.
    (0.76 + 10    0.20 = 2.76 Kg)
    For the remaining refrigerant, refer to the 
    instructions of the refrigerant manufacturer.
    If using a charging cylinder, transfer the specified 
    amount of liquid refrigerant from the refrigerant 
    cylinder to the charging cylinder. 
    Prepare an evacuated charging cylinder 
    beforehand.
    Do not use the refrigerant if the amount in the 
    charging cylinder is less than 20%.
    Configuration and characteristics of cylinders
    Fig. 1
    Fig. 2
    Fig. 3
    92 
    						
    							Length of tubing
    Evacuation timeLess than 33 ft. (10 m)
    More than 10 minutesMore than  33 ft. (10 m)
    More than 15 minutes
    9-6.  In Case Refrigerant is Leaking
    CAUTIONNever attempt to charge additional refrigerant when refrigerant has been leaking 
    from the unit. Follow the procedure described below to locate points of leaks and 
    carry out repairs, then recharge the refrigerant.
    (1) Detecting Leaks
    Use the detector for R410A to locate refrigerant leak 
    points. 
    (2) Recovering refrigerant
    Never release the gas to the atmosphere; recover 
    residual refrigerant using the refrigerant recovery unit for 
    R410A, instead.
    Do not reuse the recovered refrigerant because its 
    composition will have been altered.
    (3) Welding leaking points
    Confirm again that no residual refrigerant exists in the unit 
    before starting welding.
    Weld securely using flux and wax for R410A.
    Prevent oxide film from forming inside the tubes utilizing 
    substitution with nitrogen (N2) in the refrigerant circuit of 
    the unit. Leave ends of tubes open during welding.
    (4) Checking for sealing
    Use nitrogen gas for the pressurized gas, and never use 
    a refrigerant other than R410A. Also do not use oxygen or 
    any flammable gas.
    (5) Evacuation
    Use a solenoid valve-installed vacuum pump so that 
    even if power is cut off in the middle of evacuation of air 
    due to a power interruption, the valve will prevent the 
    pump oil from flowing back.
    The equipment may be damaged if moisture remains in 
    the tubing, thus carry out the evacuation thoroughly.
    When using a vacuum pump with exhaust air volume 
    more than 0.883 cu.ft./min. and ultimate vacuum pressure 
    rate of 50 micron Hg.
    Standard time for evacuation
    (6) Recharging
    Recharge unit in the same manner explained on the 
    previous page "(5) Recharging."
    (2) Recover refrigerant
    OK
    (3) Weld leaking points
    OK
    (4) Check for sealing
    OK
    (5) Evacuation
    OK
    (6) Recharge
    (1) Detect leaks
    OK
    93 
    						
    							9-7.  Charging Additional Refrigerant
    9-7-1.  When Tubes are Extended
    Observe the proper amount of refrigerant as stated in this service manual or the installation manual that came 
    with the indoor unit. Charge additional refrigerant in liquid state only. 
    9-8.  Retro-Fitting Existing Systems
    9-8-1.  Use of Existing Units
    Never use new refrigerant R410A for existing units which use R22. This will cause the air conditioner to 
    operate improperly and may result in a hazardous condition.
    9-8-2.  Use of Existing Tubing
    If replacing an older unit that used refrigerant R22 with a R410A unit, do not use its existing tubing. Instead, 
    completely new tubing must be used.
    CAUTIONNever charge additional refrigerant if refrigerant is leaking from the unit. Follow 
    instructions given in "9-6. In Case Refrigerant is Leaking" and completely carry out 
    repairs. Only then should you recharge the refrigerant.
    94 
    						
    							INSTALLATION INSTRUCTIONS
    CU-3KE19NBU
    CU-4KE24NBU
    CU-4KE31NBU
    (852-6-4190-584-00-2)
    APPENDIX A
    A-1 
    						
    							For Outdoor Unit
    This air conditioner uses the refrigerant R410A. 
    External diameter of service port R410A: 5/16" 
    Split System Air Conditioner 
    85264190584002 2011 CV6233187853
    INSTALLATION INSTRUCTIONS 
    NOTE
    Contents
    Page
    IMPORTANT!
    Please Read Before Starting..................................2
    1. GENERAL..........................................................4
    1-1. Tools Required for Installation (not supplied)
    1-2. Accessories Supplied with Unit
    1-3. Optional Copper Tubing Kit
    1-4. Type of Copper Tube and Insulation Material
    1-5. Additional Materials Required for Installation
    2. INSTALLATION SITE SELECTION...................5
    2-1. Indoor Unit
    2-2. Connecting Indoor Units
    2-3. Outdoor Unit
    2-4. Baffle Plate for the Outdoor Unit
    2-5. Outer Dimensions of Outdoor Unit
    2-6. Diagram of Outdoor Unit Installation
    3. INSTALLATION PROCESS..............................16
    3-1. Embedding the Tubing and Wiring
    3-2. Use of the Flaring Method
    3-3. Flaring Procedure with a Flare Tool
    3-4. Caution before Connecting Tubes Tightly
    3-5. Tubing Connections
    3-6. Insulation of Refrigerant Tubing
    3-7. Taping the Tubes
    3-8. Finishing the Installation
    4. AIR PURGING...................................................19
    Air Purging with a Vacuum Pump (for Test Run)
    Pump Down
    5. WIRING INSTRUCTIONS................................22
    5-1. General Precautions on Wiring
    5-2. Recommended Wire Length and Diameter
    5-3. Wiring System Diagram
    5-4. How to Connect Wiring to the Terminal
    5-5. Wiring Instructions for the Outdoor Unit
    6. TEST RUN.........................................................26
    7. CONNECTING A HOME AUTOMATION
    DEVICE.............................................................27
    8. INSTALLATION CHECK SHEET......................27
    Indoor unit AIndoor unit B
    Indoor unit C
    Indoor unit D Outdoor unit
    Combination example
    Model Combinations
    Combine indoor and outdoor units only as listed
    below.
    Model No.
    Indoor Unit Outdoor Unit
    CS-MKE7NKU CU-3KE19NBU
    CS-MKE9NKU CU-4KE24NBU
    CS-MKE12NKU CU-4KE31NBU
    CS-MKE18NKU
    CS-MKE24NKU
    CS-MKE9NB4U
    CS-MKE12NB4U
    CS-KE18NB4UW
    Power Source:
    60 Hz, single-phase, 230 / 208 VAC 
    						
    							IMPORTANT! 
    Please Read Before Starting
    This air conditioning system meets strict safety and operating
    standards. As the installer or service person, it is an important
    part of your job to install or service the system so it operates
    safely and efficiently. 
    For safe installation and trouble-free operation, you
    must:
    Carefully read this instruction booklet before beginning.
    Follow each installation or repair step exactly as shown.
    Observe all local, state, and national electrical codes.
    Pay close attention to all warning and caution notices
    given in this manual.
    This symbol refers to a hazard
    or unsafe practice which can
    result in severe personal injury
    or death.
    This symbol refers to a hazard
    or unsafe practice which can
    result in personal injury or prod-
    uct or property damage.
    If Necessary, Get Help
    These instructions are all you need for most installation
    sites and maintenance conditions. If you require help for a
    special problem, contact our sales / service outlet or your
    certified dealer for additional instructions. 
    In Case of Improper Installation
    The manufacturer shall in no way be responsible for improp-
    er installation or maintenance service, including failure to
    follow the instructions in this document. 
    SPECIAL PRECAUTIONS
    When Wiring
    ELECTRICAL SHOCK CAN CAUSE SEVERE
    PERSONAL INJURY OR DEATH. ONLY A
    QUALIFIED, EXPERIENCED ELECTRICIAN
    SHOULD ATTEMPT TO WIRE THIS SYSTEM. 
    
    						
    							4
    1-2.  Accessories Supplied with Unit 
    Table 1
    1-3.  Optional Copper Tubing Kit
    Copper tubing for connecting the outdoor unit to the
    indoor unit is available in kits which contain the narrow
    and wide tubing, fittings and insulation. Consult your
    nearest sales outlet or air conditioning workshop.
    1-4.  Type of Copper Tube and Insulation Material
    If you wish to purchase these materials separately from
    a local source, you will need:
    1. Deoxidized annealed copper tube for refrigerant tub-
    ing as detailed in Table 2.
    Cut each tube to the appropriate lengths 1 to 14
    (30 cm to 40 cm) to dampen vibration between units.2. Foamed polyethylene insulation for the specified
    copper tubes as required to precise length of tubing.
    Wall thickness of the insulation should be not less
    than 5/16 (8 mm).
    3. Use insulated copper wire for field wiring. Wire size
    varies with the total length of wiring. 
    Refer to 5. Wiring Instructions for details.
    1. Refrigeration (armored) tape
    2. Insulated staples or clamps for connecting wire
    (See local codes.)3. Putty
    4. Refrigeration lubricant
    5. Clamps or saddles to secure refrigerant tubing
    1Packed in the outdoor unit.  4 each Labels for inter-unit
    cable and tubeCushion rubber  4  Parts Figure Q’ty Parts Figure Q’ty Parts Figure Q’ty 
    Reducer
    (3/8"    1/2")CU-3KE19NBUCU-4KE24NBU
    CU-4KE31NBU
    2 1ABCDReducer
    (1/2"    3/8")
    CAUTIONCheck local electrical codes
    and regulations before
    obtaining wire. Also, check
    any specified instructions or
    limitations.
    ModelNarrow Tube Wide TubeOuter Dia. Thickness Outer Dia. Thickness
    CS-MKE7NKU, CS-MKE9NKU, CS-MKE12NKU1/4 (6.35 mm) 0.0314 (0.8 mm) 3/8 (9.52 mm) 0.0314 (0.8 mm)
    CS-MKE18NKU1/4 (6.35 mm) 0.0314 (0.8 mm) 1/2 (12.70 mm) 0.0314 (0.8 mm)
    CS-MKE24NKU1/4 (6.35 mm) 0.0314 (0.8 mm) 5/8 (15.88 mm) 0.0393 (1.0 mm)
    CS-MKE9NB4U, CS-MKE12NB4U1/4 (6.35 mm) 0.0314 (0.8 mm) 3/8 (9.52 mm) 0.0314 (0.8 mm)
    CS-KE18NB4UW1/4 (6.35 mm) 0.0314 (0.8 mm) 1/2 (12.70 mm) 0.0314 (0.8 mm)
    Table 2
    1-5.  Additional Materials Required for Installation
    1.  General
    This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instruc-
    tions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
    If the electric wiring diagram does not appear in this manual, please check for the diagram on the indoor unit.
    1-1.  Tools Required for Installation (not supplied)
    1. Standard screwdriver
    2. Phillips head screwdriver
    3. Knife or wire stripper
    4. Tape measure
    5. Carpenter’s level
    6. Sabre saw or key hole saw7. Hacksaw
    8. Core bits
    9. Hammer
    10. Drill
    11. Tube cutter
    12. Tube flaring tool13. Torque wrench
    14. Adjustable wrench
    15. Reamer (for deburring)
    16. Vacuum pump (For R410A)
    17. Manifold valve 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Cu 3ke19nbucu Technical Service Manual