Panasonic Cs W7dke Cs W9dke Cs W12dke Repari Manual
Here you can view all the pages of manual Panasonic Cs W7dke Cs W9dke Cs W12dke Repari Manual. The Panasonic manuals for Air Conditioner are available online for free. You can easily download all the documents as PDF.
Page 21
8.2. Cooling Operation • Cooling operation can be set using remote control. • This operation is applied to cool down the room temperature reaches the setting temperature set on the remote control. • The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C to 30°C. • During cooling operation, the compressor will stop running and restart as shown in below figure. 8.2.1. Cooling Operation Time Diagram 21 CS-W7DKE CU-W7DKE / CS-W9DKE...
Page 22
8.3.1. Soft Dry Operation Time Diagram 8.3. Soft Dry Operation • Soft Dry operation can be set using remote control. • Soft Dry operation is applied to dehumidify and toperform a gentle cooling to the room. • This operation starts when the intake air temperature sensor reaches the setting temperature on the remote control. • W hen operation begins, Soft Dry will be switched“ON”for a maximum 10 minutes, then Soft Dry operation will be turned“OFF” for a minimum 6 minutes. After that, the Soft Dry...
Page 23
8.4. Automatic Operation • Automatic operation can be set using remote control. • This operation starts to operate with indoor fan at SLo speed for 25 seconds to judge the intake air temperature. • After judged the temperature, the operation mode is determined by referring to the below standard. • Then, the unit start to operate at determined operation mode, until it is switched off using remote control, with the setting temperature as shown in below table. • Operation mode will be determine again...
Page 24
• The operation mode judging temperature and standard setting temperature can be increased by 2°C permanently, by open the circuit of JX1 at indoor electronic controller. 8.5. Operation Control (For 8.5.1 to 8.5.7 information appliesonly toCooling and Soft Dry Operation) 8.5.1. Restart Control (Time Delay Safety Control) • W hen the thermo-off temperature (temperature which compressor stops to operate) is reached during:- − Cooling operation - the compressor stops for 3 minutes (minimum) before resume...
Page 25
8.5.4. Anti-Freezing Control • If the temperature of the indoor heat exchan ger falls below 2°C continuously for 4 minutes or more, the compressor turnsoff. The fan speed setting remains the same. • This phenomenon is to protect the indoor heat exchan gerfrom freezing and to prevent higher volume of refrigerant in liquidform returning to the compressor. • Compressor will restart again when the indoor heat exchan ger temperature rises to 10°C (Recovery). • Restart control (Time Delay Safety Control)...
Page 26
(For 8.5.8 to 8.5.16 information appliesonly toHeating Operation) 8.5.8. Restart Control (Time Delay Safety Control) • W hen the thermo-off temperature (temperature which compressor stops to operate) is reached during:- − Heating operation - the compressor stops for 3 minutes (minimum) before resume operation. • If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation stop, although the unit is turn on again within the period. •...
Page 27
8.5.11. Overload Protection Control Outdoor Fan Control • If the temperature of the indoor heat exchan ger rises to 51°C, outdoor fan stops. The outdoor fan restarts when the indoor heat exchan ger temperature falls to 49°C. Compressor high pressure protection • If the indoor heat exchan ger becomes 65°C or more, the compressor will stop and restart automatically. (Time Delay Safety Control - 4minutes waiting). • This is to reduce the pressure, as to reduce the indoor heat exchan ger temp....
Page 28
8.5.15. Anti ColdDraft Control • This operation is to prevent the Cold Draft during Heating mode operation. • The operation will start when compressor OFF (Thermo OFF) during Heating operation. • For the first 30 sec. from compressor OFF (Thermo OFF), Indoor fan speed will operate accordingly to the Indoor heat exchan ger temperature as shown below: • After 30 sec. from compressor OFF (thermo OFF), Indoor fan will run atSSLo speed only. • Anti Cold Draft Control will stop when: − Intake temperature...
Page 29
Normal Deicing Time Diagram Overload Deicing Time Diagram 29 CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE
Page 30
8.6. Indoor Fan Speed Control • Indoor Fan Speed can be set using remote control. 8.6.1. Fan Speed Rotation Chart Fan Speed (rpm)CS-W7DKECS-W9DKECS-W12DKE SHi122013101310 Hi107011601280 Me9409801120 HLo840840960 CLo780780880 Lo-750750850 SLo700700750 SS Lo300300300 QSHi112012101210 QHi97010601180 QMe8408801020 QHLo770770890 QLo680680780 8.6.2. Automatic Fan Speed Control • W hen set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table. − Fan speed...