Page 51
INSTALLATION OF SUPER ALLERU-BUSTER FILTER 1. Open the front panel. 2. Remove the air filter. 3. Remove Supersonic air purifyin g device. 4. Open the Supersonic air purifyin g device frame. 5. Insert the super alleru-buster filter and close the Supersonic air purifyin g device frame as show in illustration at right. HOW TO TAKE OUT FRONT GRILLE Whenreinstalling the front grille, first set the vertical airflow direction louver to the horizontal position and then carry out above steps 2 - 3 in the...
Page 52
10.3.2. INSTALL THE OUTDOOR UNIT • After selecting the best location , start installation according to Indoor/Outdoo r Unit Installation Diagram. 1. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut. (ø10 mm). 2. When installin g at roof, please conside r strong wind and earthquake. Please fasten the installation stand firmly with bolt or nails. CUTTING AND FLARING THE PIPING 1. Please cut using pipe cutter and then remove the burrs. 2. Remove the burrs by using reamer. If...
Page 53
10.3.4. EVACUATION OF THE EQUIPMENT WHENINSTAL LING AN AIR CONDITIONER, BE SURE TO EVACU ATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the followin g procedure. 1. Connec t a charging hose with a push pin to the Low and High side of a charging set and the service port of the 3-way valve. • Be sure to connect the end of the charging hose with the push pin to the service port. 2. Connec t the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and vacuum pump adaptor. 3....
Page 54
DISPOSAL OF OUTDOOR UNITDRAIN WATER • If a drain elbow is used, the unit should be placed on a stand which is taller than 3 cm. • If the unit is used in an area where temperature falls below 0°C for 2 or 3 days in succession, it isrecommended not to use a drain elbow, for the drain water freezes and the fan will not rotate. CHECK THE DRAINAGE • Open front panel and remove air filters. (Drainage checking can be carried out without removing the front grille.) • Pour a glass of water into the drain...
Page 55
11 Installation And Servicing Air Conditioner Using R410A 11.1. Outline 11.1.1. About R410ARefrigerant 1. Converting air conditio ners to R410A Since it was declared in1974 that chlorofluoroca rbons (CFC), hydro chlorofluoroca rbons (HCFC) and other substances pose a destructive danger to the ozone layer in the earth´s upper stratosphere (20 to 40 km above the earth), measures have been taken around the world to prevent this destruction. The R22 refrigerant which has conventionally been used in ACs is...
Page 56
d. R410A refrigerating machine oil Conventionally , mineral oil or a synthet ic oil such as alkylbe nzene has been used for R22 refrigerating machine oil. Becaus e of the poor compatibility between R410A and conventional oils like mineral oil, however, there is a tendency for the refrigerating machine oil to collect in the refrigerating cycle. For this reason, polyest er and other synthet ic oils which have a high compatibility with R410A are used as refrigerating machine oil. Becaus e of the high...
Page 57
11.2.2. R410ATools 1. Copper tube gauge for clearance adjustment (used when flaring with the conventional flaring tool (clutch type)) • This gauge makes iteasy to set the clearance for the copper tube to 1.0-1.5 mm from the clamp bar of the flaring tool. 2. Flaring tool (clutch type) • In the R410A flaring tool, the receiving hole for the clamp bar is enlarged so the clearance from the clamp bar can be set to 0-0.5 mm, and the spring inside the tool is strengthened to increase the strength of the...
Page 58
5. Charging hose • The pressure resistance of the charging hose has been raised to match the higher pressure of R410A . The hose material has also been changed to suit HFC use, and the size of the fitting has been changed to match the manifold ports. 6. Vacuum pump adaptor • W hen using a vacuum pump for R410A , it is necessary to install an electromagnetic valve to prevent the vacuum pump oil from flowing back into the charging hose. The vacuum pump adaptor is installed for that purpose. if the...
Page 59
8. Electronic scale for refrigerant charging • Because of the high pressure and fast vaporizing speed of R410A , the refrigerant cannot be held in a liquid phase inside the charging cylinde r when charging is done using the charging cylinde r method, causing bubble s to form in the measurement scale glass and making it difficult to see the reading. (Naturally, the conventional R22 charging cylinde r cannot be used because of the differen ces in the pressure resistance, scale gradation, connecting port...
Page 60
11.3. Refrigerant Piping Work Whenworking with refrigerant piping, the followin g points must be carefully observed: no moisture od dust must be allowed to enter the piping, and there must be no refrigerant leaks. 1. Procedure and precautions for flaring work a. Cut the pipe Use a pipe cutter, and cutslowly so the pipe will not be deformed. b. Remove burrs and clean shavings from the cut surface If the shape of the pipe end is poor after removing burrs, or if shavings adhere to the flared area, it may...