31 CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5
1. Vertical Airflow Direction • The louver swings up and down as shown above. • The louver does not swing when the Indoor Fan stops during operation at the upper limit. Heating Mode • W hen the intake air temp. reaches 38°C, the louver is changed from upper to lower limit.When theintake air temp falls to 35°C, the louver is changed from lower to upper limit. 2. Horizontal Airflow Direction • The louver can be selected between 14°-36°(as shown above) when pressing Manua l Airflow Direction Selection Button. • The louver can be selected between 0°-61°(as shown above) when pressing Manua l Airflow Direction Selection Button. 8.9. Airflow Direction Control Cooling, Ion and Soft Dry Mode • The left and right airflow direction louvers can be adjusted manually. 32 CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5
8.10. Powerful Mode Operation Purpose of this operation is to be obtain the setting temperature quickly. 1. Cooling and Soft Dry Mode • W hen the Powerful Mode is set, the set temperature will be automatically decreased 3°C against the present setting temperature (Lower temperature: 16°C). This operation automatically will be running under SHi Fan speed (cooling), Lo- Fan Speed (Soft Dry). • Vertical Airflow Direction:- In“Manual”setting, the vane will automatically shift down 10°lower than previous setting. In“Auto”setting, the vane will automatically swing up and down. However the upper and lower limit will be shifted 10° downward. 2. Heating Mode • W hen the Powerful Mode is set, the set temperature will be automatically increased 3°C against the present setting temperature (Higher temperature: 30°C). • The Fan Speed will shift as shown below: • Vertical Airflow Direction:- In“Manual”setting, the vane will automatically shift down 5°lower than previous setting. In“Auto”setting, the vane will automatically shift between upper and lower limit depend ing on the intake air temperature as Heating Mode, Airflow Direction Auto-Control. However the upper and lower limit will be shifted 5°downward. 3. Powerful modewilloperate for 15 minutes only. 4. Powerful Mode willstop if: • Powerful mode button is pressed again. • Stopped by ON / OFF switch. • Timer-off activates. • Quiet mode button is pressed. • Operating mode is changed. 33 CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5
8.11. Ionizer Operation Purpose To provide fresh air effect to user by producing minus ion in discharge air. Control Condition a. Ionizer Only Operation. 1. When air-conditioner unit is at“OFF”conditio n (standby) and ION operation button at remocon is pressed. Fan & ionizer on, ION LED illuminates, but power LED maintain off. (1 →2) However, fan speed can be adjusted later by customer during this operation. Air flow direction (Horizontal Vane) control: Follow vane direction control at cooling mode. Horizontal vane can be changed by customer during ion only operation. 2. Ion only operation can be off by pressed ION button again. (2 →1) 3. It can be changed to previous operated mode (Auto, Heat, Cool, Dry) + ion operation by OFF/ON switch. (2 →4) 4. During ion only operation, if power failure occur, after power resume, ionizer & air-conditioner resumes immediately. 5. After error = 24 times, (about 11h 30 min.), ion & fan off with Ion LED blinks continuously. (Detail refer to Ionizer Error detection control.) b. Operation Mode + Ionizer Operation. 1. Ionising Operation Start Condition When air-conditioner unit is in“ON”conditio n (Heat, Cool, Dry, Auto mode) and ION operation button at remote controller is pressed. Ionizer on & ION LED illuminates. (3 →4) Power LED also illuminates. 2. Ionising Operation Stop Condition When one of thefollowin g conditio n is satisfied, ION operation stops. a. Stoppe d by ON/OFF switch. b. Timer OFF activates. c. ION operation button is pressed again. d. ION feedba ck signal shows error. 34 CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5
Case 1a: Ionizer only operation (12h delaytimer ON) Case 2a: Ionizer only operation (24h real time timer ON) Case 1b: Ionizer only operation (12h delaytimer OFF) Case 2b: Ionizer only operation (24h real time timer OFF) 3. Ionizer operation status is not memorised after off. After OFF,when operation is“ON”again, air-conditio ner operates without ionizer operation. However, during Cool mode etc. + ionizer operation, if there is a power failure & then power resume, A/con shall on at that mode + ionizer operation. c. Timer during ionizer operation Refer to case study in next page for detail. 8.11.1. Ionizer Error Detection Control A. Purpose To inform user that error occurs at ionizer system so that repairing job can be carried out. B. Two type oferror detection control: (a) WhenIonizer is ON (example case: Ionizer shorted, ionizer over current protection) • During ionizer ON operation, when feed back voltage = Lo (micon input) is detected, Ion is OFF. If feedba ck = Lo for 11 hrs 30 min, ION LED blinks continuously. • To cancel ion LED blinking, press ion button at remocon (or forcible operation sw at a/con unit). If ion button is pressed again, ion LED blinks again. • The error can be reset by: i) Operation ON/OFF button press to operation OFF. ii) Forcible switch press to operation OFF. iii) Operation OFF due to Timer OFF reach. iv) Timer set ON & operation from ON to OFF (only applica ble to 12 hrs timer models). (b) WhenIonizer is OFF (example case: ionizer connecting wire loose) • During air conditio ner is at standby or ON operation and ionizer at OFF conditio n, if ionizer feed back voltage = Hi (micon input) is detected, Ionizer breakdown detection control is activated and ion LED immediately blinks. • To cancel Ion LED blinking, press ion button at remocon (or forcible operation sw at a/con unit). If ion button is pressed again, ion LED blinks again. • During ionizer at breakdown conditio n, if ionizer feedba ck voltage = Lo (become OK), ion LED will stop blinking. 8.11.2. Ionizer Operation case study 35 CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5
Case 3a: Operation Mode + Ionizer (12h delaytimer ON) Case 4a: Operation Mode + Ionizer (24h real time timer ON) Case 5a: Ionizer only operation (24h real time timer ON) Case 6a: Ionizer only operation (12 delaytimer ON) Case 7a: Operation Mode + Ionizer (12 delaytimer ON) Case 3b: Operation Mode + Ionizer (12h delaytimer OFF) Case 4b: Operation Mode + Ionizer (24h real time timer OFF) Case 5b: Ionizer only operation (24h real time timer OFF) Case 6b: Ionizer only operation (24h real time timer ON) Case 7b: Operation Mode + Ionizer (24h real time timer ON) Case 8: Ionizer only operation (Auto Fan) & shift to Cool Mode 36 CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5
Note: 1. 24 times checking: Actual Ion ON for 10s & OFF for 1s 30 min continuously for 24 times. 2. 24 times count will be cleared when followin g conditio ns happen . a) 24 times count over, b) Ionizer cancel if press Ion button or power reset, c) Ion f/b sgnl OK. 3. Error protection will be cleared when followin g conditio ns happen . a) Power reset, b) Remocon operation ON/OFF button press, c) Forcible operation press, d) Opt OFF due to Timer OFF 4. Ion auto restart: Ion will auto restart if Actual Ion was ON with no error protection control before power shutdown. Otherwise Ion will not auto restart. 5. Ion LED blinking can ON/OFF during error protection by followin g conditio ns: a) Press remocon ion button b) Press emergency opt SW to OFF blinking. 37 CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5
38 CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5
9 Operating Instructions SAFETY PRECAUTIONS Before operating, please read the following “Safety Precautions” carefully. To prevent personal injury, injury to others and property damage, the following instructions must be followed. Incorrect operation due to failure to follow instructions will cause harm or damage, the seriousness of which is classified as follow: ! WarningThis sign warns of death or serious injury. ! CautionThis sign warns of damage to property. The instructions to be followed are classified by the following symbols: This symbol (with a white background) denotes an action that is PROHIBITED. These symbols (with a black background) denote actions that are COMPULSORY. OFF Installation Precautions ! Warning This room air conditioner must be earthed. Improper grounding could cause electric shock. Ensure that the drainage piping is connected properly. Otherwise, water will leak out. Do not install the unit in a potentially explosive atmosphere. Gas leak near the unit could cause fire. Do not install, remove and reinstall the unit by yourself. Improper installation will cause leakage, electric shock or fire. Please engage an authorized dealer or specialist for the installation work. ! Caution Operation Precautions ! WarningThis sign warns of death or serious injury. Do not share outlet. Do not insert plug to operate the unit. Do not pull out plug to stop the unit. Do not operate with wet hands. Do not damage or modify the power cord. Do not insert finger or other objects into the indoor or outdoor units. Do not expose directly to cold air for a long period. Plug in properly. Use specified power cord. If abnormal condition (burnt smell, etc.) occurs, switch off and unplug the power supply. ! CautionThis sign warns of injury.Do not pull the cord to disconnect the plug. Do not wash the unit with water. Do not use for other purposes such as preservation. Do not use any combustible equipment at airflow direction. Do not sit or place anything on the outdoor unit. Switch off the power supply before cleaning. Ventilate the room regularly. Pay attention as to whether the installation rack is damaged after long period of usage. Switch off the power supply if the unit is not used for a long period. O F F OFF NAME OF EACH PART Indoor Unit 1Front Panel 2Air Intake Vent 3Power Supply Cord 4Air Outlet Vent 5Vertical Airflow Direction Louver 6Horizontal Airflow Direction Louver (manually adjusted) 7Indicator Panel 1Auto Operation Button (when the front panel is opened) 2Powerful Mode Indicator–ORANGE 3Ionizer Mode Indicator–GREEN 4Power Indicator–GREEN 5Quiet Mode Indicator–ORANGE 6Timer Mode Indicator–ORANGEIndoor Unit (when the front panel is opened) 1Front Panel 2Air Filters 3Air Purifying Filter Outdoor Unit 1Air Intake Vents 2Ground Terminal (Inside cover) 3Piping 4Connecting Cable 5Drain Hose 6Air Outlet Vents Accessories Remote Control Remote Control Indication Sticker Remote Control Holder Two RO3 (AAA) dry-cell batteries or equivalent Air Purifying Filter C H E C K TEMPAUTAUTOONO F FAU TAUTOD RDRYFA NANC OO LCOOLFANANAUTAUTO R E S E TB A T T E R Y C L O C K MODESLEEPECONOMYFA N S PE E DAIR SWINGOFFC A N C E LONSETS te p12 3T IM E R+ H E AHEAT O F F / O N 1 2 3 4 5 76 213 1 62 3 4 5 123 65 4 (Catechin Air Purifying Filter)(Triple Deodorizing Filter) 39 CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5
NAME OF EACH PART Remote Control Remote Control Signal. Make sure it is not obstructed. Maximum distance : 10 m. Signal received sound. One short beep or one long beep. Notes for Remote Control. Do not throw or drop. Do not get it wet. Certain type of fluorescent lamps may affect signal reception. Consult your dealer. CHECK TEMPAUTOONOFF AUT AUTODR DRYFAN ANCOOL COOL FAN AUTO RESETCLOCK MODEPOWERFULQUIET FAN SPEEDAIR SWING OFFCANCELONSET12 3 TIMER OFF/ON AUTOMANUAL # ! $ %^ $ * & 3 5 87 9 0 6 4 ( 2 1 HEAHEAT How to Insert the Batteries 1Slide down the remote control cover completely 2Insert the batteries –Be sure the direction is correct –12.00 at display - flashing Set the current time (CLOCK) immediately to prevent battery exhaustion. About the batteries Can be used for approximately one year. Observe the following when replacing the batteries Replace with new batteries of the same type. Do not use rechargeable batteries (Ni-Cd). Remove the batteries if the unit is not going to be used for a long period. 1Signal Transmitter 2Operation Display 3Ionizer Mode Operation Button 4Room Temperature Setting Button (illuminating button) 5Operation Mode Selection Button 6Quiet Mode Operation Button 7Auto Airflow Direction Button 8ON-Timer Button 9OFF-Timer Button 0Reset Point (Press with fine-tipped object to clear the memory) !OFF/ON Button (illuminating button) @Powerful Mode Operation Button #Fan Speed Selection Button $Manual Airflow Direction Selection Button %Timer Set Button ^Timer Cancellation Button &Time-Setting Button *Clock Button (Remote Control Cover CHECK AUTOOFAUTO HEATDRY FA N COOL FA NAUTO AUTO RESETCLOCK AIR SWI NGOFF CANCEL 12 3 TIMER POWERFUL AUTO MANUALECONO MYSLEO N SETFAN SPEED MODE 2 1 1.5V1.5V PREPARATION BEFORE OPERATION Indoor Unit 1Connect the power supply cord to an independent power supply 2Open the front panel 3Remove the air filters 4Fit the air purifying filters in place 5Insert the air filters 6Close the front panel Remote Control–To set the current time 1Press 1.2Then press 2 to increase or decrease the time.3Press 1 again. Set time at display will light up. CHECK AUTO AUTO HEAT DRY FANCOOL FA NAUTO RESETCLOCK FAN SPEEDAIR SWING OFFCANCELONSET12 3 TIMER AUTOMANUAL 1 2 621 4 5 3 Setting TemperaturePress 3 to increase or decrease the temperature. The temperature can be set between 16°C ~ 30°C. Recommended temperature: During AUTO Operation, press 3 to select:- Operation with 2°C higher than the standard temperature. Operation with the standard temperature. Operation with 2°C lower than the standard temperature. Standard Temperature Cooling Model Once the Automatic Operation is selected, the indoor temperature sensor operates automatically to select the desired operation mode with Cooling or Soft Dry. After the operation mode has been selected, the mode does not change. Heat Pump Model At the beginning of the automatic operation, Heating, Cooling or Soft Dry is automatically selected according to the indoor temperature. The operation mode changes every hour, when necessary. Operation Cooling Soft DryStandard temperature 25°C 22°C Indoor temperature 23°C HOW TO OPERATE To start the operation Press 1. POWER indicator (green) on the indoor unit will light up. To stop, press once more. Setting Mode Press 2 to select:- Cooling Model AUTO–Automatic Operation COOL–Cooling Operation DRY–Soft Dry Operation FAN–Air Circulation Operation Heat Pump Model AUTO–Automatic Operation HEAT–Heating Operation COOL–Cooling Operation DRY–Soft Dry Operation Operation Cooling Soft Dry HeatingStandard temperature 25°C 22°C 21°C Indoor temperature 23°C 20°C Heat Pump Model COOL–> 26°C ~ 28°C DRY–> 1°C ~ 2°C lower than the room temperature HEAT–> 20°C ~ 24°C Cooling Model COOL–> 26°C ~ 28°C DRY–> 1°C ~ 2°C lower than the room temperatureO F FONHEA HEATDR DRY FAN AN COOL COOL CHECK T E MP AUT AUTO A UT AUTO FA N AN A U T AUTO RESETCLOCK A IR S W IN GOFF C A NC E L 12 3 TIM ER OFF/ONAUTO MANUALQU IETPOWERFULON S E TFAN SPEED MODE 2 3 5 1 6 4 40 CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5