    							UnitCS-W12CKPCU-W12CKP5
    Net Weightlb (kg)20 (9.0)77 (35)
    CompressorType—Rotary (1 cylinder)
    rolling pistontype
    MotorType—Induction (2-poles)
    RatedOutputW—830
    Air CirculationTypeCross-flow FanPropeller Fan
    MaterialAS + Glass Fiber 20%PP Resin
    MotorTypeInduction (4-poles)Induction (6-poles)
    InputW49.267.4
    RatedOutputW1533
    Fan SpeedLowrpmCooling; 900—
    Heating; 960
    MediumrpmCooling; 1,120—
    Heating; 1,120
    HighrpmCooling; 1,260845
    Heating; 1,300
    SuperHighrpmCooling; 1,300—
    Heating; 1,300
    Heat ExchangerDescriptionEvaporatorCondenser
    Tube materialCopperCopper
    Fin materialAluminium (Pre Coat)Aluminium (Blue Coat)
    Fin TypeSlit FinCorrugate Fin
    Row / Stage(Plate fin configuration, forced draft)
    2×152×24
    FPI2117
    Size (W×H×L)mm610×315×25.4705.8
    735.1×504×18.9
    Refrigerant Control Device—Capillary Tube
    Refrigeration Oil(cm3)—FVC68D (330)
    Refrigerant (R-410A)g (oz)—1,060 (37.4)
    ThermostatElectronic Control—
    Protection Device—Overload Protector
    Capillary TubeLengthmm—Cooling; 970, Heating; 590
    Flow Ratel/min—Cooling; 5.0, Heating; 8.2
    Inner Diametermm—Cooling; 1.2, Heating; 1.3
    Air FilterMaterial
    StyleP.P.
    Honeycomb—
    Capacity ControlCapillary Tube
    Compressor CapacitorµF, VAC—35 µF, 370VAC
    Fan Motor CapacitorµF, VAC1.5 µF, 400VAC2.0 µF, 450VAC
     • 
    Specifica tions are subject to change without notice for further improvement.
    11
    CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5 
    						
    							4 Dimensions
    12
    CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5 
    						
    							13
    CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5 
    						
    							5 Refrigeration Cycle Diagram
    14
    CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5 
    						
    							6 Block Diagram
    15
    CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5 
    						
    							7 Wiring Diagram
    16
    CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5 
    						
    							Cooling in operation according to Remote Control setting.
    Time DelaySafety Control (3 minutes)
    7 minutes TimeSave Control
    Starting Current Control
    Anti-Freezing Control
     • If the temperature of the indoor heat exchan ger falls
    continuously below 2°C for 4 minutes or more, the
    compressor turns off to protect the indoor heat exchanger
    from freezing. The fan speed setting remains the same.
     • Compressor will restart again when the indoor heat
    exchanger temperature rises to 10°C (Recovery).
    3 minutes waiting of Time Delay Safety Control is valid for
    Cooling Operation.
    Compressor Reverse Rotation Protection Control
    8 Operation Details
    8.1. Cooling Mode Operation
     • W hen the compressor is stopped by Remote Control, it restarts after 3 minutes when it is turned ON by Remote Control.
     • W hen the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
     • The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
    ON temperature and OFF temperature.
     • W hen the compressor outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will operate 1.6
    second later.
     • If the compressor is operating continuously for 5 minutes or longer and thetemperature differen ce between intake air and
    indoor heat exchan ger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically.
    (Time Delay Safety Control is valid)
    
    T = Intake air temperature - Indoor heat exchanger temperature
    This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
    17
    CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5 
    						
    							Compressor Protection Control
    Automatic Fan Speed Mode
     • After the compressor starts for 50 seconds but the outdoor fan motor is still OFF, the compressor will stop and restart
    automatically. (Time Delay Safety Control is valid).
     • If the above phenomenon is repeated for 3 times, the compressor will stop totally.
     • The above phenomenon is reset when there is a change to heating mode or stopped by Remote Control Switch.
    WhenAutomatic Fan Speed is selected at Remote Control during cooling operation.
     • Fan speed rotates in the range of Hi to Me.
     • Deodorizing Control.
    18
    CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5 
    						
    							Cooling Operation Time Diagram
    19
    CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5 
    						
    							Quiet Operation Control
    (For Cooling Mode or cooling region of Soft Dry Mode)
     • Purpose of this operation is to provide quite cooling operation compare to normal operation.
     • W hen the Quiet Mode is set at the remote control, Quiet Mode LED illuminates, the sound level will be automatically decreased
    2 dB (Lo), decreased 3 dB (Hi, Me), against the present sound level operation.
     • Quiet setting of fan speed rpm refer to Indoor Fan Speed Control.
     • Dew formation become severe at Quiet Lo cool, therefore Quiet Lo cool is operated only 1h 30 min (1h QLo, 30 min QLo + 50).
    After that, it goes back to Lo cool (However Quiet LED remains on).
     • Manual Airflow Direction:-
     − RPM control during Lo cool
     − RPM control during Hi & Me cool
     • Auto Airflow Direction:-
     • Quiet Mode Operation will stop if:-
     − Quiet mode button is pressed again.
     − Stopped by ON/OFF switch.
     − Timer OFF activates.
     − Powerful mode button is pressed.
     − W hen change mode to Air Circulation mode.
    20
    CS-W7CKP CU-W7CKP 5 / CS-W9CKP CU-W9CKP 5 / CS-W12CKP CU-W12CKP5 
    						