Page 61
Fuse PCB Ass'y Fig. 5 Fig. 6 Fuse 10-2. Checking Continuity of Fuse on PCB Ass'y Remove the PCB Ass'y from the electrical component box. Then pull out the fuse from the PCB Ass'y. (Fig. 5) Check for continuity using a multimeter as shown in Fig. 6. 61
Page 62
11. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT 11-1. Characteristics of New Refrigerant R410A 11-1-1. What is New Refrigerant R410A? R410A is a new refrigerant that contains two types of pseudo-non-azeotropic refrigerant mixture. Its refrigeration capacity and energy efficiency are about the same level as the conventional refrigerant, R22. 11-1-2. Components (mixing proportions) HFC32 (50%) / HFC125 (50%) 11-1-3. Characteristics Less toxic, more chemically stable refrigerant The...
Page 63
Tubing precautions Refrigerant R410A is more easily affected by dust or moisture compared with R22, thus be sure to temporarily cover the ends of the tubing with caps or tape prior to installation. Never use 0.0276" (0.7 mm)-thick copper tubing or tubing which is less than 0.0315" (0.8 mm) in thickness, since air conditioners with R410A are subject to higher pressure than those using R22 and R407C. No addition of compressor oil for R410A No additional charge of compressor oil is permitted. No...
Page 64
11-3. Tools Specifically for R410A For servicing, use the following tools for R410A Gauge manifold Charging hose Gas leak detector Refrigerant cylinder Charging cylinder Refrigerant recovery unit Vacuum pump with anti-reverse flow (*1) (Solenoid valve-installed type, which prevents oil from flowing back into the unit when the power is off, is recommended.) Vacuum pump (*2)...can be used if the following adapter is attached. Vacuum pump adapter (reverse-flow prevention adapter) (*3). (Solenoid...
Page 65
11-5. In Case of Compressor Malfunction CAUTIONShould the compressor malfunction, be sure to make the switch to a replacement compressor as quickly as possible. Use only the tools indicated exclusively for R410A. See "11-3. Tools Specifically for R410A." 11-5-1. Procedure for Replacing Compressor (1) Recovering refrigerant Any remaining refrigerant inside the unit should not be released to the atmosphere, but recovered using the refrigerant recovery unit for R410A. Do not reuse the...
Page 66
Valve Single valve Charge liquid refrigerant with cylinder in up-side-down position. Single valve (with siphon tube) Charge with cylinder in normal position.Liquid Valve Liquid Charging cylinder Open Refrigerant cylinder Liquid NO! CAUTIONNever charge a large amount of liquid refrigerant at once to the unit. This may cause damage to the compressor. CAUTIONTo prevent the composition of R410A from changing, never bleed the refrigerant gas into the atmosphere while transferring the refrigerant....
Page 67
Length of tubing Evacuation timeLess than 33 ft. (10 m) More than 10 minutesMore than 33 ft. (10 m) More than 15 minutes 11-6. In Case Refrigerant is Leaking CAUTIONNever attempt to charge additional refrigerant when refrigerant has been leaking from the unit. Follow the procedure described below to locate points of leaks and carry out repairs, then recharge the refrigerant. (1) Detecting Leaks Use the detector for R410A to locate refrigerant leak points. (2) Recovering refrigerant Never release...
Page 68
11-7. Charging Additional Refrigerant 11-7-1. When Tubes are Extended Observe the proper amount of refrigerant as stated in this service manual or the installation manual that came with the indoor unit. Charge additional refrigerant in liquid state only. 11-8. Retro-Fitting Existing Systems 11-8-1. Use of Existing Units Never use new refrigerant R410A for existing units which use R22. This will cause the air conditioner to operate improperly and may result in a hazardous condition. 11-8-2. Use of...