Panasonic Cs Kexxnb4x Cz 18bt1u Service Manual
Here you can view all the pages of manual Panasonic Cs Kexxnb4x Cz 18bt1u Service Manual. The Panasonic manuals for Air Conditioner are available online for free. You can easily download all the documents as PDF.
Page 1
TECHNICAL & SERVICE MANUAL CS-KE12NB41 & CZ-18BT1U + CU-KE12NK1 CS-KE18NB4UW & CZ-18BT1U + CU-KE18NKU DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Unit Outdoor Model No. Product Code No. 1 852 361 17 1 852 361 20 Outdoor Unit CS-KE12NB41 (Body) & CZ-18BT1U (Panel) CS-KE18NB4UW (Body) & CZ-18BT1U (Panel) Remote Controller Wired Remote Controller (Option) CU-KE12NK1 CU-KE18NKU REFERENCE NO. SM700880 Indoor Model No. Body (Panel)Product Code No. Body (Panel) 1 852 361 05 (1 852 361 15) 1 852 361 07 (1...
Page 2
• Before doing repair work, please read the " SAFETY PRECAUTIONS" carefully and fully understand them. • The precautionary items here are divided into " Warning" and " Caution" items. Items in particular which may cause death or serious injury to the service personnel if the work is not performed correctly, are included in the " Warning" table. However, even precautionary items identified as " Caution" also have the potential for serious...
Page 3
Warning If refrigerant gas blows off during the work, do not touch the refrigerant gas as it may cause frostbite. If refrigerant gas leaks during the work, ventilate the room. If refrigerant gas catches fire, harmful gas may be generated. Do not mix any gas other than the specified refrigerant gas in the refrigerating cycle. If air or other contaminants mix with the gas, pressure will become extremely high in the refrigerating cycle, which may cause a unit breakdown." When the welded section of the...
Page 4
Table of Contents SAFETY PRECAUTIONS TABLE OF CONTENTS 1. OPERATING RANGE 2. SPECIFICATIONS 2-1. Unit Specifications 2-2. Major Component Specifications 2-3. Other Component Specifications 3. DIMENSIONAL DATA 4. REFRIGERANT FLOW DIAGRAM 4-1. Refrigerant Flow Diagram 5. PERFORMANCE DATA 5-1. Temperature Charts 5-2. Cooling Capacity 5-3. Cooling Capacity (Low Ambient) 5-4. Heating Capacity 6. ELECTRICAL DATA 6-1. Electrical Characteristics 6-2. Electric Wiring Diagrams 7....
Page 5
10. CHECKING ELECTRICAL COMPONENTS 10-1. Measurement of Insulation Resistance 10-2. Checking Continuity of Fuse on PCB Ass'y 11. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT 11-1. Characteristics of New Refrigerant R410A 11-2. Checklist before Servicing 11-3. Tools Specifically for R410A 11-4. Tubing Installation Procedures 11-5. In Case of Compressor Malfunction 11-6. In Case Refrigerant is Leaking 11-7. Charging Additional Refrigerant 11-8. Retro-Fitting Existing Systems...
Page 6
95 °F DB / 71 °F WB 67 °F DB / 57 °F WB 80 °F DB / 67 °F WB – DB / – WB 1. OPERATING RANGE Maximum Minimum Maximum Minimum115 °F DB 0 °F DB 75 °F DB / 65 °F WB – DB / 0 °F WB Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Cooling Heating 6
Page 7
2. SPECIFICATIONS 2-1. Unit Specifications Indoor UnitCS-KE12NB41 & CZ-18BT1U Outdoor UnitCU-KE12NK12-1-1. Vertical dB-A dB-A Indoor : Hi/Me/Lo Outdoor : Hi Air Filter Compressor Refrigerant / Amount charged at shipment Ibs (g) Refrigerant Control12.6 1,260( 2.5 to 12.6 ) ( 250 to 1,260 ) 11,900 3.5( 3,000 to 11,900 ) ( 0.9 to 3.5 )Cooling 7,200 4,700 115V Single-Phase 60Hz 104 to 126 Refrigerant Tubing Connections Operation Sound Electrical Rating Sensible Capacity Latent Capacity W Power InputV A...
Page 8
Indoor UnitCS-KE12NB41 & CZ-18BT1U Outdoor UnitCU-KE12NK1 DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks:Rating conditions are: Cooling: Indoor air temperature 80 °F DB / 67 °F WB Outdoor air temperature 95 °F DB / 75 °F WBHeating: Indoor air temperature 70 °F DB Outdoor air temperature 47 °F DB / 43 °F WB Shipping VolumeNet Shipping Weight Ib. (kg) Ib. (kg) cu.ft (m3) inch (mm) Dimensions & Weight (Indoor Unit) Unit Dimensions Height Width Depth - -22-5/8 (575) 35.3 (16)Individual Unit Body...
Page 9
< 230V > Indoor UnitCS-KE18NB4UW & CZ-18BT1U Outdoor UnitCU-KE18NKU 2-1-2. Vertical dB-A dB-A Indoor : Hi/Me/Lo Outdoor : Hi Air Filter Compressor Refrigerant / Amount charged at shipment Ibs (g) Refrigerant Control8.3 1,860( 1.2 to 8.3 ) ( 250 to 1,860 ) 17,500 5.15( 4,000 to 17,500 ) ( 1.2 to 5.15 )Cooling 10,600 6,900230V Single-Phase 60Hz 187 to 253 Refrigerant Tubing Connections Operation Sound Electrical Rating Sensible Capacity Latent Capacity W Power InputV A Available Voltage Range Running...
Page 10
Indoor UnitCS-KE18NB4UW & CZ-18BT1U Outdoor UnitCU-KE18NKU DATA SUBJECT TO CHANGE WITHOUT NOTICE. Shipping VolumeNet Shipping Weight Ib. (kg) Ib. (kg) cu.ft (m3) inch (mm) Dimensions & Weight (Indoor Unit) Unit Dimensions Height Width DepthIndividual Unit Body (CS-KE18NB4UW) Panel (CZ-18BT1U) Indoor Unit(CS-KE18NB4UW & CZ-18BT1U) inch (mm) inch (mm) inch (mm) Package Dimensions Height Width Depthinch (mm) inch (mm) Shipping VolumeNet Shipping Weight Ib. (kg) Ib. (kg) cu.ft (m3) inch (mm) Dimensions &...