Panasonic Cs Kexxnb4x Cz 18bt1u Service Manual
Here you can view all the pages of manual Panasonic Cs Kexxnb4x Cz 18bt1u Service Manual. The Panasonic manuals for Air Conditioner are available online for free. You can easily download all the documents as PDF.
Page 21
Compressor Accumulator Wide tube service valve Wide tube Narrow tube service valve Narrow tube Heat exchanger Heat exchanger Muffler Capillary tube for split flow Cooling cycle (Defrosting cycle) Heating cycle Indoor unit Outdoor unit Electric expansion valve Strainer Strainer M Muffler O.D. 3/8" (9.52 mm) O.D. 1/4" (6.35 mm)4-way valveHigh pressure switch H.P. 4. REFRIGERANT FLOW DIAGRAM 4-1. Refrigerant Flow Diagram Indoor Unit CS-KE12NB41 & CZ-18BT1UOutdoor Unit CU-KE12NK1 21
Page 22
Compressor 4-way valveAccumulator High pressure switch Wide tube service valve Wide tube Narrow tube service valve Narrow tube Heat exchanger Muffler Capillary tube for split flow Cooling cycle (Defrosting cycle) Heating cycle Indoor unit Outdoor unit Electric expansion valve Strainer M O.D. 1/2" (12.7mm) O.D. 1/4" (6.35 mm)H.P. Indoor Unit CS-KE18NB4UW & CZ-18BT1UOutdoor Unit CU-KE18NKU Heat exchanger Strainer 22
Page 23
Hi Fan Lo Fan Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 115V) (1) Low pressure performance chart (2) Operating current performance chart (3) Indoor discharge air performance chart Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. NOTE 5. PERFORMANCE DATA 5-1. Temperature Charts Indoor Unit CS-KE12NB41 & CZ-18BT1U Outdoor Unit CU-KE12NK1 Low pressure at wide tube service valve psig(MPaG) Operating...
Page 24
High pressure at wide tube service valve psig(MPaG) Operating current (A) 1314 16 17 12 1115 290 (2.0) 218 (1.5)363 (2.5)435 (3.0) 508 (3.5) 23 (-5)32 (0)41 (5)50 (10)59 (15)68 (20)77 (25) 23 ( -5)32 (0)41 (5)50 (10)59 (15)68 (20)77 (25) 131 (55) 122 (50) 113 (45) 104 (40) 95 (35) 86 (30) 77 (25) 68 (20) Outdoor inlet air DB temp. °F(°C) Outdoor inlet air DB temp. °F(°C) Indoor discharge air temperature °F(°C) 23 (-5)32 (0)41 (5)50 (10)59 (15)68 (20)77 (25)Outdoor inlet air DB temp. °F(°C) Indoor...
Page 25
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. NOTE Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 230V) (1) Low pressure performance chart (2) Operating current performance chart (3) Indoor discharge air performance chart Indoor Unit CS-KE18NB4UW & CZ-18BT1U Outdoor Unit CU-KE18NKU Hi Fan Lo Fan Low pressure at wide tube service valve psig(MPaG) Operating current (A)73 (0.5)102 (0.7)131 (0.9) Outdoor...
Page 26
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. • Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in heating mode. (Refer to "8-2. Protective Functions Overload prevention during heating.") NOTE Indoor Unit CS-KE18NB4UW & CZ-18BT1U Outdoor Unit CU-KE18NKU High pressure at wide tube service valve psig(MPaG) Operating current (A) 89 11 12 7 6 10...
Page 27
5-2. Cooling Capacity Indoor Unit : CS-KE12NB41 & CZ-18BT1U Outdoor Unit : CU-KE12NK1 Power Supply : 115V Single Phase 60Hz < Cooling Capacity > TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) 1. Rating conditions (#) : Indoor Unit Entering Air Temp. 80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB : Outdoor Ambient Temp. 95 °F (35 °C) DB 2. 3. Above data represents the value when the operation frequency of a compressor is fixed.Above data does not take Freeze Prevention...
Page 28
Indoor Unit : CS-KE18NB4UW & CZ-18BT1U Outdoor Unit : CU-KE18NKU Power Supply : 230V Single Phase 60Hz < Cooling Capacity > TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) 1. Rating conditions (#) : Indoor Unit Entering Air Temp. 80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB : Outdoor Ambient Temp. 95 °F (35 °C) DB 2. 3. Above data represents the value when the operation frequency of a compressor is fixed.Above data does not take Freeze Prevention Protection during cooling...
Page 29
5-3. Cooling Capacity (Low Ambient) Indoor Unit : CS-KE12NB41 & CZ-18BT1U Outdoor Unit : CU-KE12NK1 Power Supply : 115V Single Phase 60Hz < Cooling Capacity (Low Ambient) > TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) 1. 2. Above data represents the value when the operation frequency of a compressor is fixed.Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling...
Page 30
Indoor Unit : CS-KE18NB4UW & CZ-18BT1U Outdoor Unit : CU-KE18NKU Power Supply : 230V Single Phase 60Hz < Cooling Capacity (Low Ambient) > TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) 1. 2. Above data represents the value when the operation frequency of a compressor is fixed.Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics. NOTE RATING CAPACITY:...