Home > Panasonic > Air Conditioner > Panasonic Cs Kexxnb4x Cz 18bt1u Service Manual

Panasonic Cs Kexxnb4x Cz 18bt1u Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Cs Kexxnb4x Cz 18bt1u Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Fuse
    PCB Ass'y
    Fig. 5
    Fig. 6
    Fuse
    10-2.  Checking Continuity of Fuse 
    on PCB Ass'y
    Remove the PCB Ass'y from the electrical 
    component box. Then pull out the fuse from the PCB 
    Ass'y. (Fig. 5)
    Check for continuity using a multimeter as shown in 
    Fig. 6.
    61 
    						
    							11.  REFRIGERANT R410A: 
    SPECIAL PRECAUTIONS WHEN SERVICING UNIT
    11-1.  Characteristics of New Refrigerant R410A
    11-1-1.  What is New Refrigerant R410A?
    R410A is a new refrigerant that contains two types of pseudo-non-azeotropic refrigerant mixture. Its 
    refrigeration capacity and energy efficiency are about the same level as the conventional refrigerant, R22.
    11-1-2.  Components (mixing proportions)
    HFC32 (50%) / HFC125 (50%)
    11-1-3.  Characteristics
    Less toxic, more chemically stable refrigerant
    The composition of refrigerant R410A changes whether it is in a gaseous phase or liquid phase. Thus, when 
    there is a refrigerant leak the basic performance of the air conditioner may be degraded because of a change in 
    composition of the remaining refrigerant. Therefore, do not add new refrigerant. Instead, recover the remaining 
    refrigerant with the refrigerant recovery unit. Then, after evacuation, totally recharge the specified amount of 
    refrigerant with the new refrigerant at its normal mixed composition state (in liquid phase).
    When refrigerant R410A is used, the composition will differ depending on whether it is in gaseous or liquid 
    phase, and the basic performance of the air conditioner will be degraded if it is charged while the refrigerant is in 
    gaseous state. Thus, always charge the refrigerant while it is in liquid phase. 
    Ether-type oil is used for compressor oil for R410A-type units, which is different 
    from the mineral oil used for R22. Thus more attention to moisture prevention and 
    faster replacement work compared with conventional models are required. 
    CAUTION
    62 
    						
    							Tubing precautions
    Refrigerant R410A is more easily affected by dust or moisture compared with R22, thus be sure to temporarily 
    cover the ends of the tubing with caps or tape prior to installation.
    Never use 0.0276" (0.7 mm)-thick copper tubing or tubing which is less than 0.0315" (0.8 mm) in thickness, since 
    air conditioners with R410A are subject to higher pressure than those using R22 and R407C.
    No addition of compressor oil for R410A
    No additional charge of compressor oil is permitted.
    No use of refrigerant other than R410A
    Never use a refrigerant other than R410A.
    If refrigerant R410A is exposed to fire
    Through welding, etc., toxic gas may be released when R410A refrigerant is exposed to fire. Therefore, be sure 
    to provide ample ventilation during installation work.
    Caution in case of R410A leak
    Check for possible leak points with the special leak detector for R410A. If a leak occurs inside the room, 
    immediately provide thorough ventilation.
    A D
    Flare tool for R410AA D
    Conventional flare tool (R22)
    Spacer
    11-2.  Checklist before Servicing
    Use a clutch-type flare tool for R410A or the conventional flare tool. Note that sizes of the resultant flares differ 
    between these two tools. Where a conventional flare tool is used, make sure to observe A Specification (amount of 
    extrusion) by using the flare spacer.
    Size of flare
    Specification A
    Diameter of tube D
    Dia.1/4" (6.35 mm)
    Dia.3/8" (9.52 mm)
    Dia.1/2" (12.7 mm)
    Dia.5/8" (15.88 mm)Flare tool for R410A Conventional flare tool (for R22)
    0 to 0.0196"
    (0 to 0.5 mm)0.0472"
    (1.2 mm)
    63 
    						
    							11-3.  Tools Specifically for R410A 
    For servicing, use the following tools for R410A
    Gauge manifold
    Charging hose
    Gas leak detector
    Refrigerant cylinder
    Charging cylinder
    Refrigerant recovery unit
    Vacuum pump with anti-reverse flow (*1)
    (Solenoid valve-installed type, which prevents oil from flowing back into the 
    unit when the power is off, is recommended.)
    Vacuum pump (*2)...can be used if the following adapter is attached.
    Vacuum pump adapter (reverse-flow prevention adapter) (*3).
    (Solenoid valve-installed adapter attached to a conventional vacuum pump.)
    Electronic scale for charging refrigerant
    Flare tool
    Bender
    Torque wrench 
    Cutter, reamer
    Welding tool, nitrogen gas cylinder
    Tools specifically for R410ATool Distinction Tool Name
    Tools which can be com-
    monly used for R22,
    R407C, and R410A
    CAUTIONThe above tools specifically for R410A must not be used for R22 and R407C. 
    Doing so will cause malfunction of the unit.
    For the above vacuum pump (*1, *2) and vacuum pump adapter (*3), those for 
    R22-type units can be used for R410A-type. However, they must be used 
    exclusively for R410A and never alternately with R22 and R407C.
    For details on tubing installation procedures, refer to the installation manuals attached to the indoor 
    unit and outdoor unit. To prevent other refrigerants (R22, R407C) from being mistakenly charged to this unit, shape and external 
    diameter of the service port screw has been altered.
         R410A : 5/16"
         R22, R407C : 1/4"
    11-4.  Tubing Installation Procedures
    When the tubes are connected, always apply HAB oil on the flare portions to improve the sealing of tubing.
    The following is the HAB oil generally used:
    Esso:  ZERICE S32
    NOTE
    64 
    						
    							11-5.  In Case of Compressor Malfunction 
    CAUTIONShould the compressor malfunction, be sure to make the switch to a replacement 
    compressor as quickly as possible.
    Use only the tools indicated exclusively for R410A.     See "11-3. Tools Specifically 
    for R410A."
    11-5-1.  Procedure for Replacing Compressor
    (1) Recovering refrigerant
    Any remaining refrigerant inside the unit should not be 
    released to the atmosphere, but recovered using the 
    refrigerant recovery unit for R410A. 
    Do not reuse the recovered refrigerant, since it will contain 
    impurities. 
    (2) Replacing Compressor
    Soon after removing seals of both discharge and suction 
    tubes of the new compressor, replace it quickly.
    (3) Checking for sealing
    Use nitrogen gas for the pressurized gas, and never use a 
    refrigerant other than R410A. Also do not use oxygen or 
    any flammable gas.
    (4) Evacuation
    Use a solenoid valve-installed vacuum pump so that 
    even if power is cut off in the middle of evacuation of air 
    due to a power interruption, the valve will prevent the 
    pump oil from flowing back.
    The equipment may be damaged if moisture remains in 
    the tubing, thus carry out the evacuation thoroughly.
    When using a vacuum pump with exhaust air volume more 
    than 0.883 cu.ft./min. and ultimate vacuum pressure rate 
    of 50 micron Hg.
    Standard time for evacuation
    (1) Recover refrigerant
    OK
    (2) Replace compressor
    OK
    (3) Check for sealing
    OK
    (4) Evacuation
    OK
    (5) Recharge
    Length of tubing
    Evacuation timeLess than 33 ft. (10 m)
    More than 10 minutesMore than 33 ft. (10 m)
    More than 15 minutes
    65 
    						
    							Valve
    Single valve
    Charge liquid refrigerant with 
    cylinder in up-side-down position.
    Single valve (with siphon tube)
    Charge with cylinder in normal position.Liquid
    Valve
    Liquid
    Charging
    cylinder
    Open
    Refrigerant
    cylinder
    Liquid
    NO!
    CAUTIONNever charge a large amount 
    of liquid refrigerant at once to 
    the unit. This may cause 
    damage to the compressor.
    CAUTIONTo prevent the composition 
    of R410A from changing, 
    never bleed the refrigerant 
    gas into the atmosphere 
    while transferring the 
    refrigerant. (Fig. 3) (5) Recharging
    Be sure to charge the specified amount of 
    refrigerant in liquid state using the service port 
    of the wide tube service valve. The proper 
    amount is listed on the unit's nameplate. 
    When the entire amount cannot be charged all at 
    once, charge gradually while operating the unit in 
    Cooling Operation.
    When charging with a refrigerant cylinder, use an 
    electronic scale for charging refrigerant. In this 
    case, if the volume of refrigerant in the cylinder 
    becomes less than 20% of the fully-charged 
    amount, the composition of the refrigerant starts 
    to change. Thus, do not use the refrigerant if 
    the amount in the charging cylinder is less 
    than 20%.
    Also, charge the minimum necessary amount to 
    the charging cylinder before using it to charge 
    the air conditioning unit.
    Example:
    In case of charging refrigerant to a unit requiring 
    1.68 lb. (0.76 Kg) using a capacity of a 22 lb. (10 
    Kg) cylinder, the minimum necessary amount for 
    the cylinder is: 
    1.68 + 22    0.20 = 6.08 lb.
    (0.76 + 10    0.20 = 2.76 Kg)
    For the remaining refrigerant, refer to the 
    instructions of the refrigerant manufacturer.
    If using a charging cylinder, transfer the specified 
    amount of liquid refrigerant from the refrigerant 
    cylinder to the charging cylinder. 
    Prepare an evacuated charging cylinder 
    beforehand.
    Do not use the refrigerant if the amount in the 
    charging cylinder is less than 20%.
    Configuration and characteristics of cylinders
    Fig. 1
    Fig. 2
    Fig. 3
    66 
    						
    							Length of tubing
    Evacuation timeLess than 33 ft. (10 m)
    More than 10 minutesMore than  33 ft. (10 m)
    More than 15 minutes
    11-6.  In Case Refrigerant is Leaking
    CAUTIONNever attempt to charge additional refrigerant when refrigerant has been leaking 
    from the unit. Follow the procedure described below to locate points of leaks and 
    carry out repairs, then recharge the refrigerant.
    (1) Detecting Leaks
    Use the detector for R410A to locate refrigerant leak 
    points. 
    (2) Recovering refrigerant
    Never release the gas to the atmosphere; recover residual 
    refrigerant using the refrigerant recovery unit for R410A, 
    instead.
    Do not reuse the recovered refrigerant because its 
    composition will have been altered.
    (3) Welding leaking points
    Confirm again that no residual refrigerant exists in the unit 
    before starting welding.
    Weld securely using flux and wax for R410A.
    Prevent oxide film from forming inside the tubes utilizing 
    substitution with nitrogen (N2) in the refrigerant circuit of 
    the unit. Leave ends of tubes open during welding.
    (4) Checking for sealing
    Use nitrogen gas for the pressurized gas, and never use a 
    refrigerant other than R410A. Also do not use oxygen or 
    any flammable gas.
    (5) Evacuation
    Use a solenoid valve-installed vacuum pump so that 
    even if power is cut off in the middle of evacuation of air 
    due to a power interruption, the valve will prevent the 
    pump oil from flowing back.
    The equipment may be damaged if moisture remains in 
    the tubing, thus carry out the evacuation thoroughly.
    When using a vacuum pump with exhaust air volume 
    more than 0.883 cu.ft./min. and ultimate vacuum pressure 
    rate of 50 micron Hg.
    Standard time for evacuation
    (6) Recharging
    Recharge unit in the same manner explained on the 
    previous page "(5) Recharging."
    (2) Recover refrigerant
    OK
    (3) Weld leaking points
    OK
    (4) Check for sealing
    OK
    (5) Evacuation
    OK
    (6) Recharge
    (1) Detect leaks
    OK
    67 
    						
    							11-7.  Charging Additional Refrigerant
    11-7-1.  When Tubes are Extended
    Observe the proper amount of refrigerant as stated in this service manual or the installation manual that came 
    with the indoor unit. Charge additional refrigerant in liquid state only. 
    11-8.  Retro-Fitting Existing Systems
    11-8-1.  Use of Existing Units
    Never use new refrigerant R410A for existing units which use R22. This will cause the air conditioner to 
    operate improperly and may result in a hazardous condition.
    11-8-2.  Use of Existing Tubing
    If replacing an older unit that used refrigerant R22 with a R410A unit, do not use its existing tubing. Instead, 
    completely new tubing must be used.
    CAUTIONNever charge additional refrigerant if refrigerant is leaking from the unit. Follow 
    instructions given in "11-6. In Case Refrigerant is Leaking" and completely carry 
    out repairs. Only then should you recharge the refrigerant.
    68 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Cs Kexxnb4x Cz 18bt1u Service Manual