Home > Lucent Technologies > Communications System > Lucent Technologies DEFINITY Enterprise Communications Server Release 6 Instructions Manual

Lucent Technologies DEFINITY Enterprise Communications Server Release 6 Instructions Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Lucent Technologies DEFINITY Enterprise Communications Server Release 6 Instructions Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 413 Lucent Technologies manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 2397
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Responding to Alarms and Errors 
    Page 5-11 Troubleshooting a Duplicated SPE 
    5
    Start by determining the time of the interchange. Then, examine the alarm and 
    error logs as described in the following section. If that does not identify the 
    problem, proceed to the next section, which describes a sequence of tests of the 
    standby SPE.
    Determining the Time of a Spontaneous 
    Interchange
    There are 2 ways to tell at what time a spontaneous interchange has taken place:
    nSTBY-SPE Error 103 
    This error is logged with a minor alarm whenever a spontaneous 
    interchange takes place. The time recorded for the 
    first occurrence of the 
    error is the approximate time of interchange. The error is logged against 
    the carrier of the SPE that was active before the interchange. This should 
    now be the standby SPE, assuming no further interchanges have taken 
    place.
    nDisplay initcauses
    The display initcauses command displays a record of all system resets. 
    In the following example, a spontaneous interchange 
    into the B carrier 
    SPE took place at 2:53 P.M. The standby SPE (B) transitioned into active 
    mode with a WARM restart, (reset level 1).
    Cause Action Escalated Carrier Time
    Interchange 1 no 1B 11/27 14:53 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Responding to Alarms and Errors 
    Page 5-12 Troubleshooting a Duplicated SPE 
    5
    Examining the Alarm and Error Logs
    The system may have had time to log alarms or errors against the fault the 
    caused the interchange. Proceed through the steps summarized in the following 
    flowchart. Examine only major alarms with a timestamp near the time of 
    interchange, and whose carrier designation is the current standby SPE (the SPE 
    interchanged out of). Include any resolved alarms meeting this description.
    Figure 5-2. Determining the Cause of an SPE Interchange
    Use the SYSTEM error table following this
    chart to determine which SPE component
    is implicated. This indicates a serious processor/memory
    bus problem. Busyout or, preferably, lock
    the standby SPE to prevent an
    interchange, and escalate the problem.
    Consult MO documentation for PKT-INT.
    Is there a Major alarm against
    the standby SW-CTL?
    no no no no no
    no
    no
    no
    Consult MO documentation for TAPE.Consult the MO documentation for the
    indicated component.
    yes
    yes
    yes
    yesReplace the standby
    MSSNET circuit pack.
    yes
    yes
    Consult CARR-POW in
    Chapter 9.
    yes
    yesIf handshake is down (checkstatus spe),
    replace the alarmed standby circuit pack
    If handshake is up, execute a
    test long clear of the alarmed
    component and consult documentation
    for that MO in Chapter 9.
    Proceed to the next ¯owchart, Testing
    the Standby SPE Is there a TAPE error 3585 with aux code 408?Is there a PKT-INT error 100? Is there an error 150 against any SPE component?Is there a SYSTEM error 6002, 6003,
    6102, or 6103? Enterdisplay errorsand look for unalarmed
    errors for SPE components, CARR-POW
    and SYSTEM. Is there a SYSTEM
    error 6001 or 6101. Enterdisplay alarmsfor categoriesSPE
    andenviron. Are there any major
    alarms against CARR-POW?
    Are there major alarms against other
    SPE components?
    All relevant alarms must be timestamped at or near the time of interchange. 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Responding to Alarms and Errors 
    Page 5-13 Troubleshooting a Duplicated SPE 
    5
    Auxiliary Data for SYSTEM Errors 6002, 6003,
    6102, and 6103
    The following table shows which components are indicted by the auxiliary error 
    codes found by using the preceding flowchart. Once you have identified the 
    faulted component, consult the section for that MO.
    AUX Data Implicated Maintenance Object
    16384 PROCR
    16385 MEM-BD
    4137 PKT-INT
    16391 SW-CTL
    16386 SYSAM
    16389 DUPINT
    16392 HOST-ADAPTER
    16397 TAPE
    16398 DISK 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Responding to Alarms and Errors 
    Page 5-14 Troubleshooting a Duplicated SPE 
    5
    Testing the Standby SPE
    The system may not have had time to log errors against the failed component 
    that caused the spontaneous interchange. If you have progressed through the 
    preceding flowchart without determining the cause of interchange, test the 
    standby for faults by proceeding through the following steps.
    Figure 5-3. Testing the Standby SPE
    Consult MO documentation for SW-CTL. Enter \f(HBtest spe-standby long\fH and wait
    for all tests to execute.
    Do all tests except for STBY-SPE test 855 pass?
    Busyout the standby SPE and enter \f(HBtest dup long\fH.
    Do all DUPINT and DUP-CHL tests pass?
    When call service needs allow for a
    possible disruption, release the standby
    SPE and wait for it to refresh (\f(HBstatus spe\fH).
    Enter \f(HBreset system interchange\fH. Did the
    planned interchange succeed?
    Busyout the standby SPE and enter \f(HBtest dupint long\fH.
    Do all tests pass?
    Do all tests pass?
    Do all tests pass? Run the long test sequence on the active SW-CTL.
    Enter \f(HBtest stored data long\fH.
    yes
    yes
    yes
    yes
    yes
    yes
    yes
    yes
    Have you completed the steps in the
    preceding ¯owchart?
    no
    no
    no
    no
    no
    no
    no
    Follow normal esclation procedures. Enter \f(HBstatus spe\fH. Is the standby SPE
    fully refreshed with handshake up?Troubleshoot using MO documentation
    for STBY-SPE.
    Consult MO documentation for the
    component whose test failed.
    Consult MO documentation for the
    component whose test failed. Consult MO documentation for
    DUPINT or DUP-CHL.
    Consult the following discussion of
    planned interchange failure.
    Consult MO documentation for DUPINT. 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Responding to Alarms and Errors 
    Page 5-15 Executing a Planned SPE Interchange 
    5
    Executing a Planned SPE Interchange
    Planned SPE interchanges are initiated on demand by the reset system 
    interchange command, or automatically by scheduled daily maintenance. The 
    latter is administered with the system-parameters maintenance screen. A 
    planned interchange normally has no perceivable effect on service. All active 
    calls, transient calls, system links and stimuli, and data transmission are 
    preserved. The SYSAM-RMT port (also called the Remote Access Port) is 
    dropped, necessitating a re-login. The duration of the interchange is 
    approximately one minute.
    !CAUTION:
    Switching the SPE-select switches to the standby carrier causes a 
    spontaneous interchange, not a planned one. This can disrupt service and 
    is not a recommended procedure.
    Prerequisites
    Several conditions must be met to guarantee a non-disruptive interchange. If 
    these are not met the system will not execute the interchange. All of these 
    conditions, listed below, are expected to be met during normal operation.
    nThe SPE must not be locked by the SPE-SELECT switches. 
    nThe standby SPE must be fully in service.
    That is, handshake is up, shadowing is on, memory is refreshed, and 
    standby SPE state-of-health is “functional”. ‘‘
    STBY-SPE (Standby SPE 
    Maintenance)’’ describes how to correct a failure of any of these.
    nThere can be no minor alarms against the standby’s PKT-INT or SYSAM 
    circuit packs.
    nThere can be no ongoing disk or tape operations on either active or 
    standby MSS components.
    Wait until all such operations, such as translation saves or backup 
    restores, are complete before requesting an interchange.
    SPE Interchange Failures
    If the above conditions are not met, or if any intermediate steps taken by the 
    system in executing the interchange fail, the interchange is prevented. Usually, 
    failure of a planned interchange has no effect on service.
    If the interchange fails after the packet interface links have migrated, the system 
    will require a reset level 1 (warm restart) to restore the links. In such a case, no 
    calls are dropped, and new call service resumes within 5 seconds. However, it is 
    probable that there is a severe system problem which predates the attempted 
    interchange. 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Responding to Alarms and Errors 
    Page 5-16 Executing a Planned SPE Interchange 
    5
    If the SPE is locked by means of the SPE-SELECT switches, error 607, auxiliary 
    data 1153, is logged against SYSTEM. If the switches are not locked and the 
    interchange fails, an unalarmed error 605 is logged against SYSTEM. The 
    auxiliary code associated with this error indicates which aspect of the 
    interchange failed. Table 5-1
     explains the meaning of the auxiliary codes and 
    what corrective action to take.
    Table 5-1. SYSTEM Error 605 Planned Interchange Failure 
    Aux 
    DataSee 
    Note Explanation
    13521
    Standby SOH “non-functional”
    13531
    Standby SOH not “functional”
    13551
    Handshake Communication with Standby SPE is down 
    13561
    Memory Shadowing not enabled 
    13571
    Standby memory not refreshed 
    13582
    Mass Storage System was in use 
    13593
    PKT-INT link migration failed 
    13601
    Interchange failed1 
    13614
    SW-CTL failure 
    13697
    Could not suspend G3-MT connectivity1
    13704Could not freeze active SW-CTL1
    1371 5 Internal Error associated with processor interrupts1
    13726Minor alarm on standby SYSAM or PKT-INT
    1395 SPE Duplication not administered
    13963
    PKT-INT Link Migration failure in Begin Step1
    13973PKT-INT Link Migration denied, (peer test in progress)
    13983
    PKT-INT Link Migration failure in Completion Step1
    13993PKT-INT Link Migration failure in Finish Step1
    14004Could Not Idle SW-CTL dual port RAM1
    14014Could Not Refresh SW-CTL dual port RAM1
    14025Internal Error (could not get duplication status)
    1403 5 Unable to inhibit Standby Maintenance Monitor
    14045
    Failure to determine Standby SPE alarm status
    Continued on next page 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Responding to Alarms and Errors 
    Page 5-17 Executing a Planned SPE Interchange 
    5
    Notes for SYSTEM Error 605 AUX Data:
    1. Follow repair instructions in ‘‘
    STBY-SPE (Standby SPE Maintenance)’’ for 
    the particular standby SPE problem. After fixing that problem, try the 
    interchange again. 
    2. Mass Storage System is in use. Check Disk and Tape LEDs for activity. 
    Wait until all MSS activity completes, then try the interchange again. If the 
    problem persists, check for alarms and errors against MSS components 
    and follow repair procedures in Chapter 9, ‘‘
    Maintenance Object Repair 
    Procedures’’.
    3. Test the PKT-INT on both carriers with the long test sequence. Follow 
    procedures for ‘‘
    PKT-INT (Packet Interface Circuit Pack)’’ in Chapter 9, 
    ‘‘Maintenance Object Repair Procedures’’. Once all tests of both PKT-INTs 
    pass, try the interchange again.
    4. Consult SW-CTL service documentation. Test SW-CTL on both carriers 
    with the long test sequence. Follow repair instructions for any failures. 
    Once 
    all tests of both SW-CTLs pass, try the interchange again.
    5. Make sure the standby SPE is refreshed Then try the interchange again.
    6. Examine alarm log to determine which of PKT-INT or SYSAM circuit packs 
    has a minor alarm against it. Consult service documentation of whichever 
    is alarm to clear
    7. Check for errors/alarms against active SPE’s SYSAM. If you find any, 
    consult SYSAM service documentation. If you find none, and if all tests of 
    the SYSAM long sequence pass, try the interchange again.
    8. Run test duplication-interface long and follow instructions for any test 
    that does not pass.
    1. A WARM restart is required.14063
    Active SPE’s PKT-INT in held-reset state
    14188
    Active Duplication Interface circuit pack is in a bad state 
    and needs to be reset.
    25005
    Internal Software failure1 (sometimes)
    Table 5-1. SYSTEM Error 605 Planned Interchange Failure  — Continued
    Aux 
    DataSee 
    Note Explanation
    Continued on next page 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Responding to Alarms and Errors 
    Page 5-18 Fiber Fault Isolation Procedure 
    5
    Fiber Fault Isolation Procedure
    Use the following procedure to isolate faults on a fiber-link. When troubleshooting 
    a system with duplicated Port Network Connectivity (PNC), first busyout 
    pnc-standby before busying out a standby Fiber-Link (FIBER-LK), Expansion 
    Interface (EXP-INTF), Switch Node Interface (SNI) or DS1 Converter (DS1C). At 
    the end of this section is a description of the loopback tests run and a pinout of 
    the cable used to connect the DS1 C to DS1 facilities.
    nA busyout of any of these components on a simplex PNC is destructive.
    nBe sure to release all busied out components after completing the tests.
    Steps:
    1. Enter display alarms with category pnc.
    Are there any on-board alarms? If so, replace the circuit pack(s).
    2. Enter display errors for category pnc.
    Check for any of the following errors:
    If 
    one or more of the above errors are present go to step 3.
    If 
    none of the above errors are present, look for SNI-PEER errors.
    nIf there is one SNI circuit pack with many different SNI-PEER error 
    types, replace the indicated SNI circuit pack
    nIf there are many SNI-PEER errors of the same error type, replace 
    the indicted SNI circuit pack using the following table.  Maintenance 
    ObjectError 
    Type
    FIBER-LK Any
    SNI-BD 513
    EXP-INTF 257 
    769 
    770 
    1281 
    1537 
    3073 
    3074 
    3075 
    3076 
    3585 
    3841 
    3842 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Responding to Alarms and Errors 
    Page 5-19 Fiber Fault Isolation Procedure 
    5
    nAfter replacing an SNI circuit pack, clear alarms by executing test 
    board UUCSSlong clear for all alarmed EXP-INTF circuit packs. 
    Wait 5 minutes for any SNI-BD or SNI-PEER alarms to clear. (You 
    can speed this process with clear firmware counters [a-pnc | 
    b-pnc] for the PNC that was repaired).
    nExit this procedure.
    3. Enter list fiber-link to get the physical location of the fiber-link endpoints. 
    If a DS1 CONV is administered to the fiber-link (DS1 CONV is “y”), use the 
    display fiber-link command to get the physical location of the DS1 CONV 
    circuit packs on the fiber-link.
    4. Execute busyout fiber-link FP followed by test fiber-link FP long.
    If any tests in the sequence fail, proceed with step 5.
    If all of the tests pass, clear alarms by executing test board UUCSS long 
    clear for all alarmed EXP-INTF circuit packs. Wait 5 minutes for any 
    SNI-BD, SNI-PEER, FIBER-LK, or DS1C-BD alarms to clear. You can 
    speed this process with clear firmware counters [a-pnc | b-pnc] for the 
    PNC that was repaired. You are finished with this procedure.Error Type SNI slot
    12
    257 3
    513 4
    769 5
    1025 6
    1281 7
    1537 8
    1793 9
    2049 13
    2305 14
    2561 15
    2817 16
    3073 17
    3329 18
    3585 19
    3841 20 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Responding to Alarms and Errors 
    Page 5-20 Fiber Fault Isolation Procedure 
    5
    5. For each endpoint of the fiber-link, follow this flowchart:
    Busyout and test board UUCSS long and record all test failures. When 
    looking at test results, consult the explanations and illustrations of the 
    tests, which appear at the end of this procedure.
    Is Board Not Assigned displayed for an EXP-INTF in an EPN? If yes, 
    test maintenance 
    long to release an EXP-INTF that may be held reset by an EPN 
    Maintenance circuit pack.
    If No
    Ê
    Did EXP-INTF test 242 fail? If yes, replace the EXP-INTF circuit pack and 
    the lightwave transceiver (if present) and go back to step 4. (EXP-INTF 
    test 242 runs an on-board looparound if no lightwave transceiver is 
    connected to the EXP-INTF.)
    If No
    Ê
    Did SNI test 757 fail? If yes, replace the SNI circuit pack and go back to 
    step 4 of this procedure.
    If No
    Ê
    Did SNI test 756 fail? If yes, replace the SNI circuit pack and the lightwave 
    transceiver (if present) and go back to step 4.
    If No
    Ê
    Did EXP-INTF test 240 fail? If yes, replace the EXP-INTF circuit pack and 
    go back to step 4.
    If No
    Ê
    Did tests 238 (EXP-INTF) or 989 (SNI) fail? If yes, replace the lightwave 
    transceivers and fiber-optic cable, or metallic cable, and go back to step 
    4. The faulted component can be further isolated by using the Manual 
    Loopback Procedure described at the end of this procedure.
    NOTE:
    If a fiber out of frame condition exists and lightwave transceivers are 
    used, check that both lightwave transceivers are of the same type, 
    (9823a or 9823b). If they are not both the same, replace one of the 
    lightwave transceivers so that they match. (9823A is used for  
    						
    All Lucent Technologies manuals Comments (0)

    Related Manuals for Lucent Technologies DEFINITY Enterprise Communications Server Release 6 Instructions Manual