Lincoln Na5 Service Manual
Have a look at the manual Lincoln Na5 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1 Lincoln manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
F-18TROUBLESHOOTING & REPAIRF-18 NA-5 Observe all Safety Guidelines detailed throughout this manual If for any reason you do not understand the test procedures or are unabl\ e to perform the tests/repairs safely, contact the Lincoln Electric Service Department for technical troubleshooting assistance before you p\ roceed. Call 216-383-2531 or 1-800-833-9353. CAUTION MODE FUNCTION PROBLEMS PROBLEMS (SYMPTOMS)POSSIBLE AREAS OF MISADJUSTMENTS(S)RECOMMENDED COURSE OF ACTION The burnback timer does not time out properly. The weld light does not light. The weld controls (voltage and wire feed speed) may or may not function. The NA-5 is at idle with the selector switch in the “Weld” position. The weld light is ON but the weld controls (voltage and wire feed speed) do not function. The NA-5 is at idle with the selector switch in the “Weld” postion.1. Test if the other timers (start, weld, crater) function properly. If they time out correctly the burn- back module may be faulty. Replace. 2. If the other timers (start, weld, crater) do NOT function correctly the procedure board may be faulty. 1. The procedure board may be faulty. Replace. 1. If the option boards (start and crater) are not installed make sure the jumper plugs are installed in the procedure board. 2. If the strike light is also lit (along with the weld light) the logic board may be faulty. 3. The procedure board may be faulty. Replace.1. Check the lead harness betweenthe burnback module and the pro- cedure board for loose or faulty connections. Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC
F-19TROUBLESHOOTING & REPAIRF-19 NA-5 Observe all Safety Guidelines detailed throughout this manual If for any reason you do not understand the test procedures or are unabl\ e to perform the tests/repairs safely, contact the Lincoln Electric Service Department for technical troubleshooting assistance before you p\ roceed. Call 216-383-2531 or 1-800-833-9353. CAUTION MODE FUNCTION PROBLEMS PROBLEMS (SYMPTOMS)POSSIBLE AREAS OF MISADJUSTMENTS(S)RECOMMENDED COURSE OF ACTION During the welding sequence the weld light does not go ON. While welding the weld mode is omitted in the welding sequence. The weld timer is set for a longer time than zero seconds. The weld timer does not time out. the unit stays in the weld mode. 1. If the optional start timer is installed determine if the start mode is timing out. If the sequence stays in the “start” mode the start timer may be faulty. 2. If the start module is OK and the weld light does not go ON the logic board may be faulty. Replace. 3. If a start module is NOT used make sure the jumper plug is installled in the procedure board receptacle. 1. The weld timer module may be faulty. Replace. 1. Set the burnback timer for a value greater than zero seconds. Start the weld sequence and then stop it with the stop button. Check to see if the unit returns to the nor- mal idle state.(Strike light ON and “Hot Electrode” light OFF). • If the weld mode ends andthe unit returns to the nor- mal idle state, the weld timer module may be faulty. • If the unit does NOT return to the normal idle state the procedure board may be faulty. 1. Check the lead harness between the weld timer and the procedure board for loose or faulty connec- tions. 1. Check the lead harness between the weld timer and the procedure board for loose or faulty connec- tions. Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC
F-20TROUBLESHOOTING & REPAIRF-20 NA-5 Observe all Safety Guidelines detailed throughout this manual If for any reason you do not understand the test procedures or are unabl\ e to perform the tests/repairs safely, contact the Lincoln Electric Service Department for technical troubleshooting assistance before you p\ roceed. Call 216-383-2531 or 1-800-833-9353. CAUTION FUNCTION PROBLEMS PROBLEMS (SYMPTOMS)POSSIBLE AREAS OF MISADJUSTMENTS(S)RECOMMENDED COURSE OF ACTION The start button does not initiate the power source output or the wire feed. The mode selector switch is in the strike position and the mode strike light is lit. The start button initiates the power source output, but the wire does not feed.1. If the crater and or start option boards are NOT used the jumper plugs must be installed in the pro- cedure board receptacles. 2. With the unit at idle check light 7C on the logic board. It should be OFF. Also check light 7B on the logic board. With the start button pressed light 7B should go ON. If lights 7C and 7B are functioning normally the logic board may be faulty. 1. If the wire inches up properly, but does not feed when the start but- ton is pressed, the logic board may be faulty. 2. If the wire does NOT feed, when the inch up button is pressed, check light 1E on the power board. It should go ON when the inch up button is pressed. If light 1E does not go on when the inch up button is pressed the control board may be faulty. 3. The power board may be faulty.1. If light 7C is ON check the stop button and associated leads for “shorts” or “grounds”. Light 7C should be on ONLY when the stop button is pressed. 2. If light 7B does NOT go on, when the start button is pressed, check the start switch (button) and asso- ciated leads for loose or faulty connections. See wiring diagram. 3. Check the lead harness between the logic board and the procedure board for loose or faulty connec- tions. See wiring diagram. 1. If the wire does not feed when the inch up button is pressed perform the Wire Drive Motor Test. Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC
F-21TROUBLESHOOTING & REPAIRF-21 NA-5 Observe all Safety Guidelines detailed throughout this manual If for any reason you do not understand the test procedures or are unabl\ e to perform the tests/repairs safely, contact the Lincoln Electric Service Department for technical troubleshooting assistance before you p\ roceed. Call 216-383-2531 or 1-800-833-9353. CAUTION FUNCTION PROBLEMS PROBLEMS (SYMPTOMS)POSSIBLE AREAS OF MISADJUSTMENTS(S)RECOMMENDED COURSE OF ACTION The start button initiates the wire feed, but does not activiate the power source output.1. Make sure that lead #690 is con- nected to the proper pin on the logic board. On newer logic boards the dip switches must be in the proper position. See wiring diagram. 2. Make sure the power source is capable of producing welding output voltage. Jumper #2 and #4 at the power source’s terminal strip. This should produce open circuit voltage at the output termi- nals. If open circuit voltage is not present the power source may be faulty. 3. Check or replace the control cable between the NA-5 and the power source. 4. With the start button pressed check light 7K on the logic board and the “Electrode Hot” light. Both lights should be on. If the lights are OFF unplug the burn- back timer. If the problem is resolved the burnback timer may be faulty. Replace. 5. The logic board may be faulty.1. The CR3 relay may be faulty. Check or replace. 2. Check the #2 and #4 leads between the CR3 relay and the control cable receptacle. See wiring diagram. Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC
F-22TROUBLESHOOTING & REPAIRF-22 NA-5 Observe all Safety Guidelines detailed throughout this manual If for any reason you do not understand the test procedures or are unabl\ e to perform the tests/repairs safely, contact the Lincoln Electric Service Department for technical troubleshooting assistance before you p\ roceed. Call 216-383-2531 or 1-800-833-9353. CAUTION TRAVEL FUNCTION PROBLEMS PROBLEMS (SYMPTOMS)POSSIBLE AREAS OF MISADJUSTMENTS(S)RECOMMENDED COURSE OF ACTION The travel function will not operate regardless of the travel switch posi- tion. The travel will not function with the travel switch in the “Hand” travel position. The unit operates properly with the travel switch in the “Auto” position.1. Check the travel switch for proper operation. Also check associat- ed leads for loose or faulty con- nections. 2. Check the travel receptacle and associated leads for loose or faulty connections. 3. Make sure the travel unit is oper- ational. 1. Check the travel switch and asso- ciated leads for loose or faulty connectioins.1. With the travel switch (S2) in the hand travel position, and the 115VAC input power applied to the NA-5 unit, check for 115VAC at the travel receptacle. 115VAC should be present at leads #531 to #532. 115VAC should also be present at leads #25 to #531. If either of these two voltages are missing or not correct check the lead harness, switch (S2) and travel receptacle for loose or faulty connections. See wiring diagram. 2. If the above voltages are correct the problem is in the travel unit or connecting cable. 1. The travel switch may be faulty. Check or replace. Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC
F-23TROUBLESHOOTING & REPAIRF-23 NA-5 Observe all Safety Guidelines detailed throughout this manual If for any reason you do not understand the test procedures or are unabl\ e to perform the tests/repairs safely, contact the Lincoln Electric Service Department for technical troubleshooting assistance before you p\ roceed. Call 216-383-2531 or 1-800-833-9353. CAUTION TRAVEL FUNCTION PROBLEMS PROBLEMS (SYMPTOMS)POSSIBLE AREAS OF MISADJUSTMENTS(S)RECOMMENDED COURSE OF ACTION The travel will not function with the travel switch in the “Auto” postion. The travel operates correctly with the travel switch in the “Hand” position. The travel runs continuously when the travel switch is in the “Auto” posi- tion.1. Make sure the jumper leads #691 and #692 are connected properly to the correct pins on the logic board. See wiring diagram. 2. Check the travel switch (S2) and associated leads for loose or faulty connections. See wiring diagram. 3. Check light 7H located on the logic board. This light should be ON when the “Auto” travel is active. If light 7H does not light the logic board may be faulty. 1. Make sure the jumper leads #691 and #692 are connected properly to the correct pins on the logic board. See wiring diagram. 2. Check light 7H on the logic board. If light 7H is always ON the logic board may be faulty.1. If light 7H, located on the logic board, does light when the auto- matic travel is active check the CR2 relay. Normal coil resis- tance is 10,000 ohms. The con- tacts (terminals 2 and 4) should “close” when 110VDC is applied to the relay coil (terminals 1 + and 3 -). 1. The 2CR relay may be faulty. The contacts (terminals 2 and 4) may be stuck closed. 2. Check the associated leads for misconnections. See wiring dia- gram. Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC
F-24TROUBLESHOOTING & REPAIRF-24 NA-5 Observe all Safety Guidelines detailed throughout this manual If for any reason you do not understand the test procedures or are unabl\ e to perform the tests/repairs safely, contact the Lincoln Electric Service Department for technical troubleshooting assistance before you p\ roceed. Call 216-383-2531 or 1-800-833-9353. CAUTION FUNCTION PROBLEMS PROBLEMS (SYMPTOMS)POSSIBLE AREAS OF MISADJUSTMENTS(S)RECOMMENDED COURSE OF ACTION After pressing the stop button, the electrode “Hot” light goes OFF, but the electrode wire remains electrical- ly hot. (The welding voltage is always present). The wire stops feeding. After pressing the stop button, the weld light remains on and the wire continues to feed. The set and actual speed meter readings match within a few IPM, but both are in error.1. Carefully disconnect the #2 lead from the power source terminal strip. The welding voltage should be disabled. If the welding volt- age is still present the power source is faulty. 2. Check or replace the control cable between the power source and the NA-5 unit. 1. If a crater option module is used, check to make sure the logic board jumper (#694) is on pin P10. 2. While pressing the stop button observe light 7C located on the logic board. It should be lit. If light 7C is ON and the wire feed- ing and welding does not stop, the logic board may be faulty. 1. Made sure the calibration jumper on the speedmeter board is con- nected properly. See Operation Section. 1. The 3CR relay may be faulty. The contacts (terminals 2 and 4) may be stuck closed. 2. Check the associated leads for misconnections. See wiring dia- gram. 1. If, while pressing the stop button, light 7C does NOT go on, check the stop button and associated leads. 1. Remove the drive motor end cap and the tach cover plate from the end of the wire drive motor. Check to make sure the slotted disc is secure and aligned and rotates freely through the center of the module pick-up. 2. Perform the Wire Speed Accuracy Test 3. Perform the Meter Circuit Accuracy Test. 4. The control board may be faulty. Replace. Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC
F-25TROUBLESHOOTING & REPAIRF-25 NA-5 Observe all Safety Guidelines detailed throughout this manual If for any reason you do not understand the test procedures or are unabl\ e to perform the tests/repairs safely, contact the Lincoln Electric Service Department for technical troubleshooting assistance before you p\ roceed. Call 216-383-2531 or 1-800-833-9353. CAUTION FUNCTION PROBLEMS PROBLEMS (SYMPTOMS)POSSIBLE AREAS OF MISADJUSTMENTS(S)RECOMMENDED COURSE OF ACTION The set speed and actual speed meter readings do not match within a few IPM. One or both readings may be erratic. The set speed is adjustable and steady. The actual speed is uncon- trollable. The meter displays the actual speed correctly. 1. Contact your local Lincoln Authorized Field Service Facility. 1. Contact your local Lincoln Authorized Field Service Facility.1. Check the lead and switch conti-nuity of the SET speedmeter cir- cuit. See wiring diagram. 2. Check the lead and switch conti- nuity of the ACTUAL speedmeter circuit. See wiring diagram. 3. Perform the Wire Speed Accuracy Test 4. Perform the Meter Circuit Accuracy Test. 5. The control board may be fault 1. While the motor is running care- fully unplug the 15 pin molex from the control board. A. If the motor continues torun the power board may be faulty. Replace. B. If the motor stops the control board may be faulty. Replace. 2. Perform the Wire Drive Motor Test. Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC
F-26TROUBLESHOOTING & REPAIRF-26 NA-5 Observe all Safety Guidelines detailed throughout this manual If for any reason you do not understand the test procedures or are unabl\ e to perform the tests/repairs safely, contact the Lincoln Electric Service Department for technical troubleshooting assistance before you p\ roceed. Call 216-383-2531 or 1-800-833-9353. CAUTION FUNCTION PROBLEMS PROBLEMS (SYMPTOMS)POSSIBLE AREAS OF MISADJUSTMENTS(S)RECOMMENDED COURSE OF ACTION The set speed is adjustable and steady. The actual speed reading is incorrect and or erratic. The set volts and actual volts read- ings match within a few tenths of a volt while welding. However both readings are inaccurate.1. Check that the jumper plug is installed securely in the harness receptacle near the voltage board. Codes below 8300 only. 2. Check for loose or faulty connec- tions on leads #510A, #525A and #555 between the tach receptacle and the control board. 3. Check the tach cable from the tach board to the tach receptacle. The shield in the cable should NOT be grounded to the case. 1. Put the Lincoln power source in the machine control mode. Check to see if the power supply can be set for the arc voltage required for the process. If not, the power source may be faulty. 2. The control cable may be faulty. Check or replace.1. Remove the drive motor end cap and the tach cover plate from the end of the wire drive motor. Check to make sure the slotted disc is secure and aligned and rotates freely through the center of the module pick-up. 2. Perform the Tach Board Feedback Test. 3. If the Tach Board Feedback Test is OK the control board may be faulty. Replace. 1. Check the voltage sensing leads for continuity. (zero ohms). #21 should have continuity to the work piece and #67 should have continuity to the wire feed head assembly. See wiring diagram. 2. Perform the Voltmeter Accuracy Test. 3. Perform the Meter Circuit Accuracy Test. 4. The voltage board may be faulty. Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC
F-27TROUBLESHOOTING & REPAIRF-27 NA-5 Observe all Safety Guidelines detailed throughout this manual If for any reason you do not understand the test procedures or are unabl\ e to perform the tests/repairs safely, contact the Lincoln Electric Service Department for technical troubleshooting assistance before you p\ roceed. Call 216-383-2531 or 1-800-833-9353. CAUTION FUNCTION PROBLEMS PROBLEMS (SYMPTOMS)POSSIBLE AREAS OF MISADJUSTMENTS(S)RECOMMENDED COURSE OF ACTION The actual volts reading does NOT match the set volts reading within a few tenths of a volt. One reading may be erratic. The NA-5 does not shut off. 1. NA-5 units with a G1556-2 (or higher) voltage board do not con- trol the actual strike voltage to match the set strike voltage. The actual strike voltage is a function of the set strike voltage and the OCV contrtol characteristics of the welding power source. NA-5 controls with a G1556-3 (or higher) voltage board must have the jumper plug connected to the 4-cavity receptacle on the board, unless the pulsed power filter board option is connected. 2. Make sure the shutdown “BYPASS” pins are not jumpered together on the NA-5 voltage board. 3. Check the voltage sensing leads for continuity. (zero ohms). #21 lead should have continuity to the work piece and #67 lead should have continuity to the wire feed head assembly. See wiring dia- gram. 4. Put the Lincoln welding power source in the machine control mode. Check to see if the power supply can be set for the arc volt- age required for the process. If not, the power supply may be faulty.1. If the actual reading is the prob- lem check the actual volts switch and associated leads. See wiring diagram. 2. If the set reading is the problem check the set volts switch and the asociated leads. See wiring dia- gram. 3. Perform the Voltmeter Accuracy Test 4. Perform the Meter Circuit Accuraty Test. 5. The voltage board may be faulty. Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC