Home > Lincoln > Welding System > Lincoln Na5 Service Manual

Lincoln Na5 Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Lincoln Na5 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1 Lincoln manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							F-18TROUBLESHOOTING & REPAIRF-18
    NA-5
    Observe all Safety Guidelines detailed throughout this manual
    If for any reason you do not understand the test procedures or are unabl\
    e to perform the tests/repairs safely, contact the Lincoln Electric
    Service Department for technical troubleshooting assistance before you p\
    roceed. Call 216-383-2531 or 1-800-833-9353.
    CAUTION
    MODE FUNCTION PROBLEMS
    PROBLEMS
    (SYMPTOMS)POSSIBLE AREAS OF
    MISADJUSTMENTS(S)RECOMMENDED
    COURSE OF ACTION
    The burnback timer does not time
    out properly.
    The weld light does not light.  The
    weld controls (voltage and wire feed
    speed) may or may not function.
    The NA-5 is at idle with the selector
    switch in the “Weld” position.
    The weld light is ON but the weld
    controls (voltage and wire feed
    speed) do not function.  The NA-5 is
    at idle with the selector switch in the
    “Weld” postion.1.  Test if the other timers (start, weld, crater) function properly.  If
    they time out correctly the burn-
    back  module may be faulty.
    Replace.
    2.  If the other timers (start, weld, crater) do NOT function correctly
    the procedure board may be
    faulty.
    1.  The procedure board may be faulty.  Replace.
    1.  If the option boards (start and crater) are not installed make
    sure the jumper plugs are
    installed in the procedure board.
    2.  If the strike light is also lit (along with the weld light) the logic
    board may be faulty.
    3.  The procedure board may be faulty.  Replace.1.  Check the lead harness betweenthe burnback module and the pro-
    cedure board for loose or faulty
    connections.
    Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC 
    						
    							F-19TROUBLESHOOTING & REPAIRF-19
    NA-5
    Observe all Safety Guidelines detailed throughout this manual
    If for any reason you do not understand the test procedures or are unabl\
    e to perform the tests/repairs safely, contact the Lincoln Electric
    Service Department for technical troubleshooting assistance before you p\
    roceed. Call 216-383-2531 or 1-800-833-9353.
    CAUTION
    MODE FUNCTION PROBLEMS
    PROBLEMS
    (SYMPTOMS)POSSIBLE AREAS OF
    MISADJUSTMENTS(S)RECOMMENDED
    COURSE OF ACTION
    During the welding sequence the
    weld light does not go ON.
    While welding the  weld mode is
    omitted in the welding sequence.
    The weld timer is set for a longer
    time than zero seconds.
    The weld timer does not time out.
    the unit stays in the weld mode. 1.  If the optional start timer is installed determine if the start
    mode is timing out.  If the
    sequence stays in the “start”
    mode the start timer may be
    faulty.  
    2.  If the start module is OK and the weld light does not go ON the
    logic board may be faulty.
    Replace.
    3.  If a start module is NOT used make sure the jumper plug is
    installled in the procedure board
    receptacle.
    1.  The weld timer module may be faulty.  Replace.
    1.  Set the burnback timer for a value greater than zero seconds.  Start
    the weld sequence and then stop
    it with the stop button.  Check to
    see if the unit returns to the nor-
    mal idle state.(Strike light ON and
    “Hot Electrode” light OFF). • If the weld mode ends andthe unit returns to the nor-
    mal idle state, the weld
    timer module may be
    faulty.
    • If the unit does NOT return to the normal idle state the
    procedure board may be
    faulty.
    1.  Check the lead harness between the weld timer and the procedure
    board for loose or faulty connec-
    tions.
    1.  Check the lead harness between the weld timer and the procedure
    board for loose or faulty connec-
    tions.
    Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC 
    						
    							F-20TROUBLESHOOTING & REPAIRF-20
    NA-5
    Observe all Safety Guidelines detailed throughout this manual
    If for any reason you do not understand the test procedures or are unabl\
    e to perform the tests/repairs safely, contact the Lincoln Electric
    Service Department for technical troubleshooting assistance before you p\
    roceed. Call 216-383-2531 or 1-800-833-9353.
    CAUTION
    FUNCTION  PROBLEMS
    PROBLEMS
    (SYMPTOMS)POSSIBLE AREAS OF
    MISADJUSTMENTS(S)RECOMMENDED
    COURSE OF ACTION
    The start button does not initiate the
    power source output or the wire
    feed.  The mode selector switch is in
    the strike position and the mode
    strike light is lit.
    The start button initiates the power
    source output, but the wire does not
    feed.1.  If the crater and or start option boards are NOT used the jumper
    plugs must be installed in the pro-
    cedure board receptacles.
    2. With the unit at idle check light 7C on the logic board.  It should be
    OFF.   Also check light 7B on the
    logic board.  With the start button
    pressed light 7B should go ON.  If
    lights 7C and 7B are functioning
    normally the logic board may be
    faulty. 
    1.  If the wire inches up properly, but does not feed when the start but-
    ton is pressed,  the logic board
    may be faulty.
    2.  If the wire does NOT feed, when the inch up button is pressed,
    check light 1E on the power
    board.  It should go ON when the
    inch up button is pressed.  If light
    1E does not go on when the inch
    up button is pressed  the control
    board may be faulty.
    3.  The power board may be faulty.1.  If light 7C is ON check the stop button and associated leads for
    “shorts” or “grounds”.  Light 7C
    should be on ONLY when the
    stop button is pressed.
    2. If light 7B does NOT go on, when the start button is pressed, check
    the start switch (button) and asso-
    ciated leads for loose or faulty
    connections.  See wiring diagram.
    3.  Check the lead harness between the logic board and the procedure
    board for loose or faulty connec-
    tions.  See wiring diagram.
    1.  If the wire does not feed when the inch up button is pressed perform
    the 
    Wire Drive Motor Test.
    Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC 
    						
    							F-21TROUBLESHOOTING & REPAIRF-21
    NA-5
    Observe all Safety Guidelines detailed throughout this manual
    If for any reason you do not understand the test procedures or are unabl\
    e to perform the tests/repairs safely, contact the Lincoln Electric
    Service Department for technical troubleshooting assistance before you p\
    roceed. Call 216-383-2531 or 1-800-833-9353.
    CAUTION
    FUNCTION  PROBLEMS
    PROBLEMS
    (SYMPTOMS)POSSIBLE AREAS OF
    MISADJUSTMENTS(S)RECOMMENDED
    COURSE OF ACTION
    The start button initiates the wire
    feed, but does not activiate the
    power source output.1.  Make sure that lead #690 is con- nected to the proper pin on the
    logic board.  On newer logic
    boards the dip switches must be
    in the proper position.  See wiring
    diagram.
    2.  Make sure the power source is capable of producing  welding
    output voltage.  Jumper #2 and
    #4 at the power source’s terminal
    strip.  This should produce open
    circuit voltage at the output termi-
    nals.  If open circuit voltage is not
    present the power source may be
    faulty.
    3.  Check or replace the control cable between the NA-5 and the
    power source.
    4.  With the start button pressed check light 7K on the logic board
    and the “Electrode Hot” light.
    Both lights should be on.  If the
    lights are OFF unplug the burn-
    back timer.  If the problem is
    resolved the burnback timer may
    be faulty.  Replace.
    5.  The logic board may be faulty.1.  The CR3 relay may be faulty. Check or replace.
    2.  Check the #2 and #4 leads between the CR3 relay and the
    control cable receptacle.  See
    wiring diagram.
    Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC 
    						
    							F-22TROUBLESHOOTING & REPAIRF-22
    NA-5
    Observe all Safety Guidelines detailed throughout this manual
    If for any reason you do not understand the test procedures or are unabl\
    e to perform the tests/repairs safely, contact the Lincoln Electric
    Service Department for technical troubleshooting assistance before you p\
    roceed. Call 216-383-2531 or 1-800-833-9353.
    CAUTION
    TRAVEL FUNCTION PROBLEMS
    PROBLEMS
    (SYMPTOMS)POSSIBLE AREAS OF
    MISADJUSTMENTS(S)RECOMMENDED
    COURSE OF ACTION
    The travel function will not operate
    regardless of the travel switch posi-
    tion.
    The travel will not function with the
    travel switch in the “Hand” travel
    position.   The unit operates properly
    with the travel switch in the “Auto”
    position.1.  Check the travel switch for proper operation.   Also check associat-
    ed leads for loose or faulty con-
    nections.  
    2.  Check the travel receptacle and associated leads for loose or
    faulty connections.
    3.  Make sure the travel unit is oper- ational.
    1.  Check the travel switch and asso- ciated leads for loose or faulty
    connectioins.1.  With the travel switch (S2) in the hand travel position, and the
    115VAC input power applied to
    the NA-5 unit,  check for 115VAC
    at the travel receptacle.  115VAC
    should be present at leads #531
    to #532.  115VAC should also be
    present at leads #25 to #531.  If
    either of these two voltages are
    missing or not correct check the
    lead harness, switch (S2) and
    travel receptacle for loose or
    faulty connections.  See wiring
    diagram.
    2.  If the above voltages are correct the problem is in the travel unit or
    connecting cable.
    1.  The travel switch may be faulty. Check or replace.  
    Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC 
    						
    							F-23TROUBLESHOOTING & REPAIRF-23
    NA-5
    Observe all Safety Guidelines detailed throughout this manual
    If for any reason you do not understand the test procedures or are unabl\
    e to perform the tests/repairs safely, contact the Lincoln Electric
    Service Department for technical troubleshooting assistance before you p\
    roceed. Call 216-383-2531 or 1-800-833-9353.
    CAUTION
    TRAVEL FUNCTION PROBLEMS
    PROBLEMS
    (SYMPTOMS)POSSIBLE AREAS OF
    MISADJUSTMENTS(S)RECOMMENDED
    COURSE OF ACTION
    The travel will not function with the
    travel switch in the “Auto” postion.
    The travel operates correctly with the
    travel switch in the “Hand” position.
    The travel runs continuously when
    the travel switch is in the “Auto” posi-
    tion.1.  Make sure the jumper leads #691 and #692 are connected properly
    to the correct pins on the logic
    board.  See wiring diagram.
    2.  Check the travel switch (S2) and associated leads for loose or
    faulty connections.  See wiring
    diagram.
    3.  Check light 7H located on the logic board.  This light should be
    ON when the “Auto” travel is
    active.  If light 7H does not light
    the logic board may be faulty.
    1.  Make sure the jumper leads #691 and #692 are connected properly
    to the correct pins on the logic
    board.  See wiring diagram.
    2.  Check light 7H on the logic board. If light 7H is always ON the logic
    board may be faulty.1.  If light 7H, located on the logic board, does light when the auto-
    matic travel is active check the
    CR2 relay.  Normal coil resis-
    tance is 10,000 ohms.  The con-
    tacts (terminals 2 and 4) should
    “close” when 110VDC is applied
    to the relay coil (terminals 1 +
    and 3 -). 
    1.  The 2CR relay may be faulty. The contacts (terminals 2 and 4)
    may be stuck closed.
    2.  Check the associated leads for misconnections.  See wiring dia-
    gram.
    Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC 
    						
    							F-24TROUBLESHOOTING & REPAIRF-24
    NA-5
    Observe all Safety Guidelines detailed throughout this manual
    If for any reason you do not understand the test procedures or are unabl\
    e to perform the tests/repairs safely, contact the Lincoln Electric
    Service Department for technical troubleshooting assistance before you p\
    roceed. Call 216-383-2531 or 1-800-833-9353.
    CAUTION
    FUNCTION PROBLEMS
    PROBLEMS
    (SYMPTOMS)POSSIBLE AREAS OF
    MISADJUSTMENTS(S)RECOMMENDED
    COURSE OF ACTION
    After pressing the stop button, the
    electrode “Hot” light goes OFF, but
    the electrode wire remains electrical-
    ly hot.  (The welding voltage is
    always present).  The wire stops
    feeding.
    After pressing the stop button, the
    weld light remains on and the wire
    continues to feed.
    The set and actual speed meter
    readings match within a few IPM, but
    both are in error.1.  Carefully disconnect the #2 lead from the power source terminal
    strip.  The welding voltage should
    be disabled.  If the welding volt-
    age is still present the power
    source is faulty.
    2.  Check or replace the control cable between the power source
    and the NA-5 unit.
    1.  If a crater option module is used, check to make sure the logic
    board jumper (#694) is on pin
    P10.
    2.  While pressing the stop button observe light 7C located on the
    logic board.  It should be lit.  If
    light 7C is ON and the wire feed-
    ing and welding does not stop,
    the logic board may be faulty.
    1.  Made sure the calibration jumper on the speedmeter board is con-
    nected properly.  See 
    Operation
    Section. 
    1.  The 3CR relay may be faulty. The contacts (terminals 2 and 4)
    may be stuck closed.
    2.  Check the associated leads for misconnections.  See wiring dia-
    gram.
    1.  If, while pressing the stop button, light 7C does NOT go on,  check
    the stop button and associated
    leads.
    1.  Remove the drive motor end cap and the tach cover plate from the
    end of the wire drive motor.
    Check to make sure the slotted
    disc is secure and aligned and
    rotates freely through the center
    of the module pick-up.
    2.  Perform the 
    Wire Speed
    Accuracy Test
    3.  Perform the Meter Circuit
    Accuracy Test.
    4.  The control board may be faulty. Replace.
    Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC 
    						
    							F-25TROUBLESHOOTING & REPAIRF-25
    NA-5
    Observe all Safety Guidelines detailed throughout this manual
    If for any reason you do not understand the test procedures or are unabl\
    e to perform the tests/repairs safely, contact the Lincoln Electric
    Service Department for technical troubleshooting assistance before you p\
    roceed. Call 216-383-2531 or 1-800-833-9353.
    CAUTION
    FUNCTION PROBLEMS
    PROBLEMS
    (SYMPTOMS)POSSIBLE AREAS OF
    MISADJUSTMENTS(S)RECOMMENDED
    COURSE OF ACTION
    The set speed and actual speed
    meter readings do not match within a
    few IPM.  One or both readings may
    be erratic.
    The set speed is adjustable and
    steady.  The actual speed is uncon-
    trollable.  The meter displays the
    actual speed correctly. 1.  Contact your local Lincoln Authorized Field Service Facility.
    1.  Contact your local Lincoln Authorized Field Service Facility.1.  Check the lead and switch conti-nuity of the SET speedmeter cir-
    cuit.  See wiring diagram.
    2.  Check the lead and switch conti- nuity of the ACTUAL speedmeter
    circuit.  See wiring diagram.
    3. Perform the 
    Wire Speed
    Accuracy Test
    4.  Perform the Meter Circuit
    Accuracy Test.
    5.  The control board may be fault
    1.  While the motor is running care- fully unplug the 15 pin molex from
    the control board. A.  If the motor continues torun the power board may
    be faulty.  Replace.
    B.  If the motor stops the control board may be
    faulty.  Replace.
    2.  Perform the 
    Wire Drive Motor
    Test.
    Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC 
    						
    							F-26TROUBLESHOOTING & REPAIRF-26
    NA-5
    Observe all Safety Guidelines detailed throughout this manual
    If for any reason you do not understand the test procedures or are unabl\
    e to perform the tests/repairs safely, contact the Lincoln Electric
    Service Department for technical troubleshooting assistance before you p\
    roceed. Call 216-383-2531 or 1-800-833-9353.
    CAUTION
    FUNCTION  PROBLEMS
    PROBLEMS
    (SYMPTOMS)POSSIBLE AREAS OF
    MISADJUSTMENTS(S)RECOMMENDED
    COURSE OF ACTION
    The set speed is adjustable and
    steady.  The actual speed reading is
    incorrect and or erratic.
    The set volts and actual volts read-
    ings match within a few tenths of a
    volt while welding.  However both
    readings are inaccurate.1.  Check that the jumper plug is installed securely in the harness
    receptacle near the voltage
    board.  Codes below 8300 only.
    2.  Check for loose or faulty connec- tions on leads #510A, #525A  and
    #555 between the tach receptacle
    and the control board.
    3.  Check the tach cable from the tach board to the tach receptacle.
    The shield in the cable should
    NOT be grounded to the case.
    1.  Put the Lincoln power source in the machine control mode.
    Check to see if the power supply
    can be set for the arc voltage
    required for the process.  If not,
    the power source may be faulty.
    2.  The control cable may be faulty. Check or replace.1.  Remove the drive motor end cap and the tach cover plate from the
    end of the wire drive motor.
    Check to make sure the slotted
    disc is secure and aligned and
    rotates freely through the center
    of the module pick-up.
    2.  Perform the 
    Tach Board
    Feedback Test.
    3.  If the Tach Board Feedback
    Test 
    is OK the control board may
    be faulty.  Replace. 
    1.  Check the voltage sensing leads for continuity.  (zero ohms).  #21
    should have continuity to the
    work piece and #67 should have
    continuity to the wire feed head
    assembly.  See wiring diagram.
    2.  Perform the 
    Voltmeter Accuracy
    Test.
    3. Perform the Meter Circuit
    Accuracy Test.
    4.  The voltage board may be faulty.
    Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC 
    						
    							F-27TROUBLESHOOTING & REPAIRF-27
    NA-5
    Observe all Safety Guidelines detailed throughout this manual
    If for any reason you do not understand the test procedures or are unabl\
    e to perform the tests/repairs safely, contact the Lincoln Electric
    Service Department for technical troubleshooting assistance before you p\
    roceed. Call 216-383-2531 or 1-800-833-9353.
    CAUTION
    FUNCTION  PROBLEMS
    PROBLEMS
    (SYMPTOMS)POSSIBLE AREAS OF
    MISADJUSTMENTS(S)RECOMMENDED
    COURSE OF ACTION
    The actual volts reading does NOT
    match the set volts reading within a
    few tenths of a volt.  One reading
    may be erratic.  The NA-5 does not
    shut off. 1.  NA-5 units with a G1556-2 (or higher) voltage board do not con-
    trol the actual strike voltage to
    match the set strike voltage.  The
    actual strike voltage is a function
    of the set strike voltage and the
    OCV contrtol characteristics of
    the welding power source.
    NA-5 controls with a G1556-3 (or
    higher) voltage board must have
    the jumper plug connected to the
    4-cavity receptacle on the board,
    unless the pulsed power filter
    board option is connected.
    2.  Make sure the shutdown “BYPASS” pins are not jumpered
    together on the NA-5 voltage
    board.
    3.  Check the voltage sensing leads for continuity. (zero ohms).   #21
    lead should have continuity to the
    work piece and #67 lead should
    have continuity to the wire feed
    head assembly.  See wiring dia-
    gram.
    4.  Put the Lincoln welding power source in the machine control
    mode.  Check to see if the power
    supply can be set for the arc volt-
    age required for the process.  If
    not, the power supply may be
    faulty.1.  If the actual reading is the prob- lem check the actual volts switch
    and associated leads.  See wiring
    diagram.
    2.  If the set reading is the problem check the set volts switch and the
    asociated leads.  See wiring dia-
    gram.
    3.  Perform the 
    Voltmeter Accuracy
    Test
    4.  Perform the Meter Circuit
    Accuraty Test.
    5. The voltage board may be faulty.
    Return to Section TOC Return to Section TOC Return to Section TOCReturn to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOCReturn to Master TOC 
    						
    All Lincoln manuals Comments (0)