Home > Lincoln > Welding System > Lincoln Na5 Service Manual

Lincoln Na5 Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Lincoln Na5 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1 Lincoln manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							OPERATING INSTRUCTIONSB-8B-8
    Wire Feed Motor AccelerationELECTRIC SHOCKcan kill.
    • Turn off input power to the welding power source
    using the disconnect
    switch before working on
    this equipment.
    The NA-5 has two different speeds of
    controlled wire feed motor acceleration.  As
    shipped, the unit is connected for fast
    acceleration which is best for most
    applications.  To change to the slower
    acceleration, turn off all input power to the
    NA-5 control box.  Open the control box.
    Locate the Control PC Board mounted on
    the back of the box in the lower right hand
    corner.  Change the jumper plug from the “F”
    pin to the “S” pin as shown in Figure B.2. 
    Burnback and Electrode Backup
    The primary consideration in setting the arc
    stopping sequence is to prevent the
    electrode from sticking in the puddle.  This
    is easily done with the machine as shipped. The standard stopping sequence when the
    optional “Crater Controls” are not used is as
    follows:
    1. Press the “Stop” button.
    2. The wire feed motor stops and the “Burnback Time Delay” starts.
    3. The arc continues to burn the electrode back from the puddle until
    the arc goes out or the time set on the
    thumbwheel switch elapses.  This
    control should be set for just enough
    burnback time to prevent crater
    sticking.
    There are two other ways this circuit can be
    connected.  One will cause the wire to
    retract* with a contactor drop out delay at
    the end of the weld.  The second will cause
    the wire to retract* during burnback time,
    and there will be no contactor drop out delay
    at the end of the weld.  If either one of these
    alternate methods of stopping the weld is
    desired, the connections on the logic board
    can be easily changed.
    To change the stopping sequence, turn the
    input AC power off at the power source,
    remove the screw holding the inner panel,
    and swing the panel open.  Change the
    connections (older models) or switch
    positions (newer models) on the logic board
    as shown in Table B.2.
    Optional “Crater Controls”
    This option is recommended for applications
    where the ending bead size must be
    controlled, applications when the crater must
    be filled, roundabouts, and any other welds
    where the end overlaps the start.
    When the “Stop” button is pressed, the
    machine welds at the wire speed and
    voltage set by the “Crater Controls” until the
    time set on the thumbwheel switch elapses.
    The circuit then automatically switches to the
    arc stopping sequence described above.
    NOTE
    : Setting crater time to 0.00 seconds
    will give zero crater time; however, the
    crater settings will be active during
    burnback time until the arc goes out. 
    *Wire will retract at weld mode speed (or crater mode
    speed, if installed) until the arc goes out and then retract at strike mode speed for the remainder of burnbacktime.
    NA-5
    JUMPER 
     PLUG
    FIGURE B.2 – ACCELERATION JUMPER PLUGS. 
    WARNING
    Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOC Return to Master TOC 
    						
    							TABLE  B.2 – STOPPING SEQUENCE SETTINGS.
    When “Stop” Button is Pressed Older Models Newer Models*
    Feed motor stops and  Lead #693 to Pin 3
    electrode burns back with  Lead #690 to Pin 4
    contactor delay (standard)
    Feed motor inches up and  Lead #693 to Pin 1
    electrode burns back with Lead #690 to Pin 4
    contactor delay
    Feed motor inches up and  Lead #693 to Pin 1
    contactor opens Lead #690 to Pin 2
    (no burnback)
    *NOTE:
    VOLTAGE CONTROL
    RESPONSE
    The NA-5 is provided with selectable voltage
    control response. Proper setting depends on
    the power source and process being used.
    Refer to the appropriate power source
    connection diagram for the proper
    connection of the jumpers located on the
    NA-5 Voltage P.C. Board, shown in Figure
    B.3.
    To change the voltage control response:
    1. Turn off all input power to the NA-5 control.
    2. Open the control box.
    3. Locate the Voltage P.C. Board mounted on the right side of the box.
    Position the jumper plugs on the
    Voltage P.C. Board per the
    appropriate power source connection
    diagram.
    1234
    Switch #2
    1234Switch #2
    1234Switch #2
    OPERATING INSTRUCTIONSB-9B-9
    NA-5
    Indicates switch in up   position
    Indicates switch in down   position
    Indicates switch position does not matter
    NA-5
    VOLTAGE
    A D
    B
    RED
    JUMPER
     PLUG
    WHITE
    JUMPER
     PLUG
    FIGURE B.3 – VOLTAGE CONTROL RESPONSE JUMPER PLUG LOCATIONS. 
    Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOC Return to Master TOC 
    						
    							AUTOMATIC SHUTDOWN
    If the NA-5 voltage control is unable to
    supply the “Set” value of the arc voltage
    while welding, the automatic shutdown
    circuit will activate.  This protection circuit
    immediately returns the NA-5 control to idle
    state within a few seconds after the arc
    voltage discrepancy occurs.
    Typical causes that activate this protective
    shutdown circuit are as follows:1. “Set” value of arc voltage is outside the power source range.
    2. Power source voltage control not set for “Remote”.
    3. Misconnection of NA-5 control cable leads to the power source.
    4. Incorrect weld polarity connections, or settings, at NA-5 or power source.
    5. Lost connection of NA-5 voltage sensing leads (#67 and #21) between
    arc and voltage control or a blown 1/8
    amp fuse on voltage PC boards built
    since 1983.
    With NA-5 units above Code 8300, the
    conditions of causes 4 and 5 above would
    result in the wrong wire feed direction when
    the weld is started.  See the section on 
    Cold
    Start Circuitry.
    In the case of full-range control power
    sources, such as the DC-600, this protective
    shutdown circuit could prevent welding
    under the conditions of causes 3, 4 and 5
    above by holding the power output at
    minimum, possibly providing too low of a
    power source output to even establish an
    arc, or causing the field fuse to blow
    because of rapid field reversals with NA-5
    controls above Code 8300.  See the section
    on 
    Cold Start Circuitry.
    Although out of range shutdown can occur
    with all power sources when working with
    very low or very high arc voltages, it is most likely to occur when using the R3S models
    with the somewhat limited voltage ranges of
    the various taps.  For instance, if the R3S-
    400 triangle tap setting is for 31 volts, the
    range of control from the remote circuit is
    approximately 7 volts, i.e. 27.5 to 34.5 volts
    at nominal input voltage.  If the NA-5
    controls are set for 29 volts, and the input
    voltage to the R3S goes up, it may not be
    possible for the NA-5 control circuit to hold
    the 29 volts, so the welding will shut down.
    By changing to the 27 volt triangle setting,
    the range will be approximately 23.5 to 30.5
    volts, and at high input voltage, there will be
    sufficient control to hold the “Set” arc
    voltage.  On these machines, if the NA-5
    stops welding, follow this procedure:
    1. Move the NA-5 voltage set point 2 volts lower than the desired
    procedure and make a test weld.
    a. If the NA-5 still shuts down, go to step 2 below.
    b. If the NA-5 keeps welding, change the R3S triangle setting
    to the next  higher  voltage  and
    reset the NA-5 set point to the
    desired procedure.  The R3S is
    now set properly unless there is
    a significant change in input
    voltage.  Skip the following step.
    2. Move the NA-5 voltage setting set point 2 volts higher than the desired
    procedure and make a test weld.
    a. If the NA-5 keeps welding, change the R3S triangle setting
    to the next lower voltage and
    reset the NA-5 set point to the
    desired procedure. The R3S is
    now set properly unless there is
    a significant change in input
    voltage.  Skip the following step.
    b.  If the NA-5 still shuts down, refer to the following paragraph and
    other causes previously listed.
    OPERATING INSTRUCTIONSB-10B-10
    NA-5Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOC Return to Master TOC 
    						
    							OPERATING INSTRUCTIONSB-11B-11
    NA-5
    In some cases, it is also possible to hold the
    “Actual” button pressed while starting the
    arc.  Before the NA-5 shuts down, the actual
    arc voltage can be read on the digital meter.
    Comparing this reading to the “Set” reading
    will tell what change in the range controls of
    the power source are required so it can
    supply the desired voltage.  Should the
    meter read zero, check the NA-5 sensing
    leads (#21 and #67) connections.  Should
    the meter read negative (-) voltage, the
    polarity connections or settings at the NA-5
    or power source are wrong.  
    This same general procedure can be used
    on the other power sources.  For example,
    if the NA-5 keeps shutting down and the
    other possible causes have been checked,
    adjust the “Set” voltage higher and/or lower
    than the desired voltage.  If the NA-5
    continues to weld at one of these voltages,
    it can be determined what change in the
    range controls of the power source are
    required so it can supply the desired voltage.
    COLD START CIRCUITRY 
    NA-5 controls above Code 8300 contain
    circuitry added to the voltage PC board to
    facilitate the “cold starting” features of these
    units.* This circuitry senses the voltage
    present between the electrode and work, via
    leads #67 and #21, and permits normal wire
    feed if this voltage exceeds approximately
    6.5 VDC.  However, if this voltage level is
    not exceeded, or drops below approximately
    3.5 VDC, the “Auto Stop” activates while
    inching down or electrode backup occurs if
    the arc start circuit has been initiated. 
    *Units below Code 8300 can be provided with the coldstart circuitry by replacing the old L-6257 voltage boardwith the new G-1556 voltage board.  This new boardwill mount and connect in the same manner as the oldboard, except the third harness connector (previouslyconnected to a jumper plug) must be connected to thelower receptacle of the new voltage board.
    NOTE: HI-FREQ starting cannot be used
    with converted units below Code 8300. A. Auto Stop 
    When the “Inch Down” button is pressed, a
    low-level DC voltage signal is applied
    between the electrode and work which
    permits the wire to inch down normally.
    When the electrode makes electrical contact
    with the work, it shorts out this signal
    causing the wire feed to automatically stop
    and the flux solenoid to activate until the
    “Inch Down” button is released.  The “Inch
    Up” button is not affected by this circuit.
    B. Electrode Backup
    If while starting or welding the electrode
    stubs or shorts to work, the resulting loss of
    arc voltage will cause the electrode to
    momentarily back up until the arc voltage is
    re-established and then change back to the
    normal feed direction. 
    NOTE
    : The “cold starting” circuitry will
    cause the NA-5 to feed in the wrong
    direction when the “Start” button is pressed
    if the “Actual” arc voltage, as read on the
    NA-5 voltmeter, does not exceed typically
    about 6.5 volts.  Usual causes for the
    situation are:
    1. No wire loaded through the NA-5 head and nozzle assembly (except
    when using the K148 Contact
    Nozzle).
    2. No power source weld cable connection to the NA-5 head or work.
    3. Incorrect electrode polarity connections at the NA-5 or power
    source. 
    4. Little or no output voltage from the power source.
    5. An open voltage sensing lead #67 or #21 to the NA-5 control box or a
    blown 1/8 amp fuse on a voltage PC
    board built since 1983.
    Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOC Return to Master TOC 
    						
    							OPERATING INSTRUCTIONSB-12B-12
    NA-5
    SECURITY OF WELD
    PROCEDURE SETTINGS
    There are two means provided to prevent or
    limit unauthorized readjustment of the NA-5
    voltage and wire feed speed controls once
    set to the desired procedure.1. The security panel of the NA-5 can be locked to prevent access to the
    control knobs.
    2. The control range of the procedure control knobs can be limited to either
    about 3% or about 15% of the full
    range control by installing a knob
    rotation stop screw to any or all of the
    control knobs.  This stop screw  is
    installed in the following manner:
    a. Turn  off  the  input  power  to  the NA-5.
    b. Loosen each knob set screw and remove all knobs, including the
    rotary select switch knob.
    c. Remove the felt seal and square spacer tube mounted behind
    each control knob.
    d. Open the control box. Disconnect, then remove, the
    procedure control PC board
    assembly and its panel insulation. 
    e. Install a 1/2 in. long, pan or round head, #4 sheet metal screw into
    the 0.10 in. diameter hole located beneath each square so the head
    is on the back side of the panel
    (inside the control box).
    f. Remount the PC board assembly and its panel insulation.
    Reconnect the PC board and
    close and secure the control box. 
    g. Remount the rotary select switch knob and replace each square
    spacer tube and felt seal so the
    #4 screw protrudes between the
    tube and the felt seal.
    h. Turn on the NA-5 input power and set the desired procedure by
    rotating the shafts of the controls. 
    i. Carefully replace each control knob so the #4 screw inserts into
    the center of the shorter length
    channel on the back of the knob
    for about 3% of the total range of
    control or into the center of the
    longer length channel for about
    15% of the total range of control.
    j.  With finger pressure on the knob against the felt seal, carefully
    retighten the set screw of each
    knob. 
    NOTE
    : Steps h thru j will have to be
    repeated if it is desired to change the
    procedure settings to values outside the
    selected 3% or 15% control range limit.  
    Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOC Return to Master TOC 
    						
    							TABLE OF CONTENTS
    - ACCESSORIES SECTION - 
    NA-5
    Accessories  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .\
     . . . . . . . . . . . Section C
    General  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .\
     . . . . . . . . . C-2
    Listing of Accessories  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3 K29 Vertical Lift Adjuster  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3
    K58 Magnetic Separator  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3
    K96 Horizontal Adjuster . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3
    K129 Submerged Arc Small Wire Twinarc
    ® . . . . . . . . . . . . . . . . . C-3
    K148 Contact Nozzle and K149 Linc-FillTM
    Long Stickout Extension  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3
    K218 Horizontal Fillet/Lap Attachment  . . . . . . . . . . . . . . . . . . . . C-3
    K219 Flux Hopper Kit  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3
    K223 Solenoid Kit  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3
    K225 Submerged Arc Twinarc Kit  . . . . . . . . . . . . . . . . . . . . . . . C-4
    K238 High Frequency Unit  . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4
    K239 Twinarc Kit for Innershield
    ®Electrodes  . . . . . . . . . . . . . . . C-4
    K278 SpreadarcTM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4
    K281 Solid Wire Straightener for Tiny Twinarc  . . . . . . . . . . . . . . C-4
    K285 Concentric Flux Cone  . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4
    K310 Flux Screen  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4
    K325 TC-3 Travel Carriage  . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4
    K334 Start and Crater Controls  . . . . . . . . . . . . . . . . . . . . . . . . . C-5
    K336 Remote Interface Module  . . . . . . . . . . . . . . . . . . . . . . . . . C-5
    K337 Weld Timer Module  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-5
    K349 Multi-Procedure Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-5
    S-22022 or S-22182 Current Relay  . . . . . . . . . . . . . . . . . . . . . . C-5
    Speed-Feed Drum  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-5
    Speed-Feed Reel  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-5
    Section CSection C
    Return to Master TOC Return to Master TOCReturn to Master TOC Return to Master TOC 
    						
    							C-2ACCESSORIESC-2
    NA-5
    Product NumberProduct Name
    K29 VERTICAL LIFT ADJUSTER
    K58 MAGNETIC SEPARATOR
    K96 HORIZONTAL  ADJUSTER
    K129 SUBMERGED ARC SMALL WIRE TWINARC
    K148 CONTACT NOZZLE
    K149 LINC-FILL LONG STICKOUT EXTENSION
    K218 HORIZONTAL FILLET/LAP ATTACHMENT
    K219 FLUX HOPPER KIT
    K223 SOLENOID KIT
    K225 SUBMERGED ARC TWINARC KIT
    K238 HIGH FREQUENCY UNIT
    K239 TWINARC KIT FOR INNERSHIELD ELECTRODES
    K278 SPREADARC
    K281 SOLID WIRE STRAIGHTENER FOR TINY TWINARC
    K285 CONCENTRIC FLUX CONE
    K310 FLUX SCREEN
    K325 TC-3 TRAVEL CARRIAGE
    K334 START AND CRATER CONTROLS
    K336 REMOTE INTERFACE MODULE
    K337 WELD TIMER MODULE
    K349 MULTI-PROCEDURE KIT
    S22022 or S22182 CURRENT RELAY
    SPEED-FEED DRUMS
    SPEED-FEED REELS
    GENERAL
    This section contains a listing and short
    description of the accessories that are available with the NA-5 automatic welding
    system.
    TABLE  C.1  –  NA-5  AUTOMATIC  WELDING  SYSTEM  ACCESSORIES.
    Return to Section TOC Return to Section TOCReturn to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC 
    						
    							ACCESSORIESC-3C-3
    NA-5 
    LISTING OF ACCESSORIES
    K29 VERTICAL LIFT ADJUSTER
    When mounted in the NA-5 head mounting
    system, the K29 Vertical Lift Adjuster
    provides quick hand crank adjustment of the
    vertical head position. It also has some
    horizontal adjustability as described in Sec.
    T3.2.3 of operator’s manual IM305.
    Installation instructions are shipped with
    each K29 Vertical Lift Adjuster kit, are
    contained in the IM305 manual, and can be
    ordered as Sec. T2.2.11.
    K58 MAGNETIC SEPARATOR
    Useful with any submerged arc equipment.
    The unit removes foreign magnetic particles
    from reused submerged arc welding flux.
    Operating instructions are included with the
    kit.
    K96 HORIZONTAL ADJUSTER
    When mounted in the NA-5 head mounting
    system, the K96 Horizontal Adjuster
    provides quick hand crank adjustment of the
    horizontal head position. Installation
    instructions are shipped with each K96
    Horizontal Adjuster kit, are contained in the
    IM305 manual, and can be ordered as Sec.
    T2.2.12.
    K129 SUBMERGED ARC SMALL
    WIRE TWINARC
    ®
    The Twinarc system provides for the feeding
    of two small solid wires through a single wire
    feeder. The Twinarc assembly includes a
    wire reel, reel brake, shaft and mounting
    bracket, drive roll, idle roll assembly, dual
    wire guides, and nozzle and contact tip or
    contact tip holder. Instructions are shipped
    with each kit, are contained in the IM305
    manual, and can be ordered as Sec. T2.5.3
    K129.
    K148 CONTACT NOZZLE AND
    K149 LINC-FILL
    TMLONG
    STICKOUT EXTENSION
    This Innershield and submerged arc nozzle
    is designed for 0.062 through 3/16 in.
    (1.57 through 4.76 mm) wire at high
    currents. When long stickout [2 to 5 (50.80
    to 127.00 mm)] is required, the K149
    Linc-Fill Long Stickout Extension is
    recommended along with the K237 Linc-Fill
    Starting Relay. Instructions are contained in
    the IM305 manual and can also be ordered
    as Sec. T2.2.7.
    K218 HORIZONTAL
    FILLET/LAP ATTACHMENT
    This special contact assembly automatically
    guides the electrode when making
    submerged arc horizontal fillet and lap welds
    to ensure accurate bead placement without
    expensive fixtures and clamps. Installation,
    operating, and maintenance instructions are
    shipped with each kit, are contained in the
    IM305 manual, and can also be ordered as
    Sec. T2.5.4.
    K219 FLUX HOPPER KIT
    This flux hopper, which has an electric flux
    valve, can be mounted on NA-5N and
    NA-5NF heads for submerged arc welding.
    Installation instructions are included with
    each kit. The operator and maintenance
    instructions are contained in the IM305
    manual and can also be ordered as
    Sec. T2.5.9.
    K223 SOLENOID KIT
    The solenoid kit includes a valve to control
    water flow when using the cooling
    attachment on the K148 or K239 contact
    nozzle assembly. It opens when the start
    button is pressed and can be wired to close
    either when the stop button is pressed or
    when the arc goes out. Installation
    instructions are shipped with each kit.
    Return to Section TOC Return to Section TOCReturn to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC 
    						
    							ACCESSORIESC-4C-4
    K225 SUBMERGED
    ARC TWINARC KIT
    The Twinarc kit provides for the feeding of
    two 5/64, 3/32, or 1/8 in. (1.98, 2.38, or
    3.18 mm) solid wires through a single wire
    feeder. The electrode wire must be the
    same size. The assembly includes a wire
    reel, insulated reel mounting bracket, wire
    straightener, dual wire guides, nozzle, and
    contact block. Installation, operating, and
    maintenance instructions are shipped with
    each kit, are contained in the IM305 manual,
    and can be ordered as Sec. T2.5.3 K225.
    K238 HIGH FREQUENCY UNIT
    This unit supplies high frequency to the
    welding leads for more positive starts, which
    may be required for certain difficult starting
    applications. Factory-installed insulation is
    required. Instructions are shipped with each
    unit. Installation instructions are contained
    in the IM305 manual and can be ordered as
    Sec. T2.5.8.
    K239 TWINARC KIT FOR
    INNERSHIELD
    ®ELECTRODES
    This kit provides for welding with two
    Innershield electrodes. Two 3/32 in.
    (2.38 mm) flux-cored electrodes are fed
    through a single wire feeder. Both wires
    must be the same size. The K239 kit
    includes the nozzle equipped for water
    cooling, drive rolls, drive roll locating collar,
    idle roll assembly, ingoing and outgoing
    guide tubes, wire straightener, wire reel, and
    wire reel mounting shaft and insulation.
    Instructions are included in the kit, are
    contained in the IM305 manual, and can
    also be ordered as Sec. T2.5.3 K239.
    K278 SPREADARCTM
    The primary application for this accessory is
    for hardfacing buildup using a Twinarc
    nozzle. The combination “Spreadarc-
    Twinarc” covers large areas quickly with
    smooth beads of minimum admixture with
    the base metal. Flux cored electrode, openarc, and submerged arc procedures can be
    used. Instructions are shipped with the kit,
    are contained in the IM305 manual, and can
    also be ordered as Sec. T2.5.6.
    K281 SOLID WIRE
    STRAIGHTENER FOR
    TINY TWINARC
    This wire straightener will straighten 0.045
    through 3/32 in. (1.14 through 2.38 mm) wire
    diameters. It is recommended for welding
    procedures requiring long stickout and
    where wire position accuracy is essential.
    Instructions are shipped with the kit, are
    contained in the IM305 manual, and can be
    ordered as Sec. T2.5.5.
    K285 CONCENTRIC FLUX CONE 
    The concentric flux cone was designed to
    fit on the K148 Contact Nozzle alone, the
    K148 Contact Nozzle with a K149 Linc-Fill
    Long Stickout Extension, the K129
    Submerged Arc Small Wire Twinarc, and
    the K391 nozzles.  (The maximum electrical
    stickout when using the K149 Linc-Fill Long
    Stickout Extension will be 4 in. [101.6 mm.]).
    Use of this attachment results in the flux
    being fed concentrically around the
    electrodes.  Installation, operating, and
    maintenance instructions are shipped with
    each kit, are contained in the IM305 manual,
    and can be ordered as Sec. T2.2.8 K285.
    K310 FLUX SCREEN
    Useful for any submerged arc equipment. It
    removes foreign magnetic particles from
    reused submerged arc welding flux.
    Operating instructions are included in the kit.
    K325 TC-3 TRAVEL CARRIAGE
    The K325 Travel Carriage carries the control
    box and wire drive head, in either direction,
    on a beam of suitable length and
    mechanical specifications. Two models are
    available: Standard and High Capacity.
    NA-5
    Return to Section TOC Return to Section TOCReturn to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC 
    						
    							ACCESSORIESC-5C-5
    NA-5
    K334 START AND CRATER
    CONTROLS 
    Easily installed procedure and timer boards
    to permit adjustment of wire speed and
    voltage.  Can be installed to function at
    either the start of the weld or at the end for
    crater filling.  Installation, operating, and
    maintenance instructions are shipped with
    each kit and can be ordered as Sec. T2.5.13
    K334.
    K336 REMOTE INTERFACE
    MODULE 
    Permits connection of customer-furnished
    remote start-stop and inch momentary
    contact closure or momentary 24 volt
    signals.  Also used when a single remote
    signal is desired to start or stop multiple
    heads.  This module replaces the earlier
    K336 Remote Pushbutton Interface Module.
    Installation and application instructions are
    shipped with each kit and can be ordered as
    Sec. T2.5.11 K336.
    K337 WELD TIMER MODULE 
    Permits setting of weld time for an adjustable
    period.  Eliminates need to press the “Stop”
    button.  Instructions are included in the kit. 
    K349 MULTI-PROCEDURE KIT 
    The K349 Multi-Procedure Kit provides three
    additional weld mode procedure settings of
    wire feed speed and voltage, allowing the
    choice of four NA-5 weld mode procedures.
    Installation, operating, and maintenance
    instructions are shipped with each kit, are
    contained in the IM305 manual, and can be
    ordered as Sec. T2.5.19 K349.
    S22022 OR S22182 CURRENT
    RELAY MODULES
    The current relay is useful to fixture builders
    and others who need a signal indicating that
    welding current is flowing.  Installation,
    operating, and maintenance instructions are
    shipped with each kit. The S22022 relay
    module is suitable for dry circuit applications
    and it is rated at 2 Amps, 115 VAC or 28
    VDC. This relay has both normally open and
    normally closed contacts. The S22182 relay
    module is suitable for applications requiring
    at least 10 mA current and it is rated at 3
    Amps, 115 VAC or 28 VDC. This relay only
    has normally open contacts.  
    SPEED-FEED DRUM
    These drums must be set on a turntable
    which permits them to freely turn in a
    clockwise direction.  Installation, operating,
    and maintenance instructions are contained
    in the IM305 manual and can be ordered as
    Sec. T2.5.7-A.
    SPEED-FEED REEL
    These reels require dereeling equipment
    that permits the reel to rotate freely as the
    electrode is used.  Installation, operating,
    and maintenance instructions are contained
    in the IM305 manual and can be ordered as
    Sec. T2.5.7-B.
    Return to Section TOCReturn to Section TOCReturn to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC 
    						
    All Lincoln manuals Comments (0)