Lincoln Na5 Service Manual
Have a look at the manual Lincoln Na5 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1 Lincoln manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
OPERATING INSTRUCTIONSB-8B-8 Wire Feed Motor AccelerationELECTRIC SHOCKcan kill. • Turn off input power to the welding power source using the disconnect switch before working on this equipment. The NA-5 has two different speeds of controlled wire feed motor acceleration. As shipped, the unit is connected for fast acceleration which is best for most applications. To change to the slower acceleration, turn off all input power to the NA-5 control box. Open the control box. Locate the Control PC Board mounted on the back of the box in the lower right hand corner. Change the jumper plug from the “F” pin to the “S” pin as shown in Figure B.2. Burnback and Electrode Backup The primary consideration in setting the arc stopping sequence is to prevent the electrode from sticking in the puddle. This is easily done with the machine as shipped. The standard stopping sequence when the optional “Crater Controls” are not used is as follows: 1. Press the “Stop” button. 2. The wire feed motor stops and the “Burnback Time Delay” starts. 3. The arc continues to burn the electrode back from the puddle until the arc goes out or the time set on the thumbwheel switch elapses. This control should be set for just enough burnback time to prevent crater sticking. There are two other ways this circuit can be connected. One will cause the wire to retract* with a contactor drop out delay at the end of the weld. The second will cause the wire to retract* during burnback time, and there will be no contactor drop out delay at the end of the weld. If either one of these alternate methods of stopping the weld is desired, the connections on the logic board can be easily changed. To change the stopping sequence, turn the input AC power off at the power source, remove the screw holding the inner panel, and swing the panel open. Change the connections (older models) or switch positions (newer models) on the logic board as shown in Table B.2. Optional “Crater Controls” This option is recommended for applications where the ending bead size must be controlled, applications when the crater must be filled, roundabouts, and any other welds where the end overlaps the start. When the “Stop” button is pressed, the machine welds at the wire speed and voltage set by the “Crater Controls” until the time set on the thumbwheel switch elapses. The circuit then automatically switches to the arc stopping sequence described above. NOTE : Setting crater time to 0.00 seconds will give zero crater time; however, the crater settings will be active during burnback time until the arc goes out. *Wire will retract at weld mode speed (or crater mode speed, if installed) until the arc goes out and then retract at strike mode speed for the remainder of burnbacktime. NA-5 JUMPER PLUG FIGURE B.2 – ACCELERATION JUMPER PLUGS. WARNING Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOC Return to Master TOC
TABLE B.2 – STOPPING SEQUENCE SETTINGS. When “Stop” Button is Pressed Older Models Newer Models* Feed motor stops and Lead #693 to Pin 3 electrode burns back with Lead #690 to Pin 4 contactor delay (standard) Feed motor inches up and Lead #693 to Pin 1 electrode burns back with Lead #690 to Pin 4 contactor delay Feed motor inches up and Lead #693 to Pin 1 contactor opens Lead #690 to Pin 2 (no burnback) *NOTE: VOLTAGE CONTROL RESPONSE The NA-5 is provided with selectable voltage control response. Proper setting depends on the power source and process being used. Refer to the appropriate power source connection diagram for the proper connection of the jumpers located on the NA-5 Voltage P.C. Board, shown in Figure B.3. To change the voltage control response: 1. Turn off all input power to the NA-5 control. 2. Open the control box. 3. Locate the Voltage P.C. Board mounted on the right side of the box. Position the jumper plugs on the Voltage P.C. Board per the appropriate power source connection diagram. 1234 Switch #2 1234Switch #2 1234Switch #2 OPERATING INSTRUCTIONSB-9B-9 NA-5 Indicates switch in up position Indicates switch in down position Indicates switch position does not matter NA-5 VOLTAGE A D B RED JUMPER PLUG WHITE JUMPER PLUG FIGURE B.3 – VOLTAGE CONTROL RESPONSE JUMPER PLUG LOCATIONS. Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOC Return to Master TOC
AUTOMATIC SHUTDOWN If the NA-5 voltage control is unable to supply the “Set” value of the arc voltage while welding, the automatic shutdown circuit will activate. This protection circuit immediately returns the NA-5 control to idle state within a few seconds after the arc voltage discrepancy occurs. Typical causes that activate this protective shutdown circuit are as follows:1. “Set” value of arc voltage is outside the power source range. 2. Power source voltage control not set for “Remote”. 3. Misconnection of NA-5 control cable leads to the power source. 4. Incorrect weld polarity connections, or settings, at NA-5 or power source. 5. Lost connection of NA-5 voltage sensing leads (#67 and #21) between arc and voltage control or a blown 1/8 amp fuse on voltage PC boards built since 1983. With NA-5 units above Code 8300, the conditions of causes 4 and 5 above would result in the wrong wire feed direction when the weld is started. See the section on Cold Start Circuitry. In the case of full-range control power sources, such as the DC-600, this protective shutdown circuit could prevent welding under the conditions of causes 3, 4 and 5 above by holding the power output at minimum, possibly providing too low of a power source output to even establish an arc, or causing the field fuse to blow because of rapid field reversals with NA-5 controls above Code 8300. See the section on Cold Start Circuitry. Although out of range shutdown can occur with all power sources when working with very low or very high arc voltages, it is most likely to occur when using the R3S models with the somewhat limited voltage ranges of the various taps. For instance, if the R3S- 400 triangle tap setting is for 31 volts, the range of control from the remote circuit is approximately 7 volts, i.e. 27.5 to 34.5 volts at nominal input voltage. If the NA-5 controls are set for 29 volts, and the input voltage to the R3S goes up, it may not be possible for the NA-5 control circuit to hold the 29 volts, so the welding will shut down. By changing to the 27 volt triangle setting, the range will be approximately 23.5 to 30.5 volts, and at high input voltage, there will be sufficient control to hold the “Set” arc voltage. On these machines, if the NA-5 stops welding, follow this procedure: 1. Move the NA-5 voltage set point 2 volts lower than the desired procedure and make a test weld. a. If the NA-5 still shuts down, go to step 2 below. b. If the NA-5 keeps welding, change the R3S triangle setting to the next higher voltage and reset the NA-5 set point to the desired procedure. The R3S is now set properly unless there is a significant change in input voltage. Skip the following step. 2. Move the NA-5 voltage setting set point 2 volts higher than the desired procedure and make a test weld. a. If the NA-5 keeps welding, change the R3S triangle setting to the next lower voltage and reset the NA-5 set point to the desired procedure. The R3S is now set properly unless there is a significant change in input voltage. Skip the following step. b. If the NA-5 still shuts down, refer to the following paragraph and other causes previously listed. OPERATING INSTRUCTIONSB-10B-10 NA-5Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOC Return to Master TOC
OPERATING INSTRUCTIONSB-11B-11 NA-5 In some cases, it is also possible to hold the “Actual” button pressed while starting the arc. Before the NA-5 shuts down, the actual arc voltage can be read on the digital meter. Comparing this reading to the “Set” reading will tell what change in the range controls of the power source are required so it can supply the desired voltage. Should the meter read zero, check the NA-5 sensing leads (#21 and #67) connections. Should the meter read negative (-) voltage, the polarity connections or settings at the NA-5 or power source are wrong. This same general procedure can be used on the other power sources. For example, if the NA-5 keeps shutting down and the other possible causes have been checked, adjust the “Set” voltage higher and/or lower than the desired voltage. If the NA-5 continues to weld at one of these voltages, it can be determined what change in the range controls of the power source are required so it can supply the desired voltage. COLD START CIRCUITRY NA-5 controls above Code 8300 contain circuitry added to the voltage PC board to facilitate the “cold starting” features of these units.* This circuitry senses the voltage present between the electrode and work, via leads #67 and #21, and permits normal wire feed if this voltage exceeds approximately 6.5 VDC. However, if this voltage level is not exceeded, or drops below approximately 3.5 VDC, the “Auto Stop” activates while inching down or electrode backup occurs if the arc start circuit has been initiated. *Units below Code 8300 can be provided with the coldstart circuitry by replacing the old L-6257 voltage boardwith the new G-1556 voltage board. This new boardwill mount and connect in the same manner as the oldboard, except the third harness connector (previouslyconnected to a jumper plug) must be connected to thelower receptacle of the new voltage board. NOTE: HI-FREQ starting cannot be used with converted units below Code 8300. A. Auto Stop When the “Inch Down” button is pressed, a low-level DC voltage signal is applied between the electrode and work which permits the wire to inch down normally. When the electrode makes electrical contact with the work, it shorts out this signal causing the wire feed to automatically stop and the flux solenoid to activate until the “Inch Down” button is released. The “Inch Up” button is not affected by this circuit. B. Electrode Backup If while starting or welding the electrode stubs or shorts to work, the resulting loss of arc voltage will cause the electrode to momentarily back up until the arc voltage is re-established and then change back to the normal feed direction. NOTE : The “cold starting” circuitry will cause the NA-5 to feed in the wrong direction when the “Start” button is pressed if the “Actual” arc voltage, as read on the NA-5 voltmeter, does not exceed typically about 6.5 volts. Usual causes for the situation are: 1. No wire loaded through the NA-5 head and nozzle assembly (except when using the K148 Contact Nozzle). 2. No power source weld cable connection to the NA-5 head or work. 3. Incorrect electrode polarity connections at the NA-5 or power source. 4. Little or no output voltage from the power source. 5. An open voltage sensing lead #67 or #21 to the NA-5 control box or a blown 1/8 amp fuse on a voltage PC board built since 1983. Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOC Return to Master TOC
OPERATING INSTRUCTIONSB-12B-12 NA-5 SECURITY OF WELD PROCEDURE SETTINGS There are two means provided to prevent or limit unauthorized readjustment of the NA-5 voltage and wire feed speed controls once set to the desired procedure.1. The security panel of the NA-5 can be locked to prevent access to the control knobs. 2. The control range of the procedure control knobs can be limited to either about 3% or about 15% of the full range control by installing a knob rotation stop screw to any or all of the control knobs. This stop screw is installed in the following manner: a. Turn off the input power to the NA-5. b. Loosen each knob set screw and remove all knobs, including the rotary select switch knob. c. Remove the felt seal and square spacer tube mounted behind each control knob. d. Open the control box. Disconnect, then remove, the procedure control PC board assembly and its panel insulation. e. Install a 1/2 in. long, pan or round head, #4 sheet metal screw into the 0.10 in. diameter hole located beneath each square so the head is on the back side of the panel (inside the control box). f. Remount the PC board assembly and its panel insulation. Reconnect the PC board and close and secure the control box. g. Remount the rotary select switch knob and replace each square spacer tube and felt seal so the #4 screw protrudes between the tube and the felt seal. h. Turn on the NA-5 input power and set the desired procedure by rotating the shafts of the controls. i. Carefully replace each control knob so the #4 screw inserts into the center of the shorter length channel on the back of the knob for about 3% of the total range of control or into the center of the longer length channel for about 15% of the total range of control. j. With finger pressure on the knob against the felt seal, carefully retighten the set screw of each knob. NOTE : Steps h thru j will have to be repeated if it is desired to change the procedure settings to values outside the selected 3% or 15% control range limit. Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOC Return to Master TOC Return to Master TOC
TABLE OF CONTENTS - ACCESSORIES SECTION - NA-5 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .\ . . . . . . . . . . . Section C General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .\ . . . . . . . . . C-2 Listing of Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3 K29 Vertical Lift Adjuster . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3 K58 Magnetic Separator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3 K96 Horizontal Adjuster . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3 K129 Submerged Arc Small Wire Twinarc ® . . . . . . . . . . . . . . . . . C-3 K148 Contact Nozzle and K149 Linc-FillTM Long Stickout Extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3 K218 Horizontal Fillet/Lap Attachment . . . . . . . . . . . . . . . . . . . . C-3 K219 Flux Hopper Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3 K223 Solenoid Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3 K225 Submerged Arc Twinarc Kit . . . . . . . . . . . . . . . . . . . . . . . C-4 K238 High Frequency Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4 K239 Twinarc Kit for Innershield ®Electrodes . . . . . . . . . . . . . . . C-4 K278 SpreadarcTM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4 K281 Solid Wire Straightener for Tiny Twinarc . . . . . . . . . . . . . . C-4 K285 Concentric Flux Cone . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4 K310 Flux Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4 K325 TC-3 Travel Carriage . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4 K334 Start and Crater Controls . . . . . . . . . . . . . . . . . . . . . . . . . C-5 K336 Remote Interface Module . . . . . . . . . . . . . . . . . . . . . . . . . C-5 K337 Weld Timer Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-5 K349 Multi-Procedure Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-5 S-22022 or S-22182 Current Relay . . . . . . . . . . . . . . . . . . . . . . C-5 Speed-Feed Drum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-5 Speed-Feed Reel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-5 Section CSection C Return to Master TOC Return to Master TOCReturn to Master TOC Return to Master TOC
C-2ACCESSORIESC-2 NA-5 Product NumberProduct Name K29 VERTICAL LIFT ADJUSTER K58 MAGNETIC SEPARATOR K96 HORIZONTAL ADJUSTER K129 SUBMERGED ARC SMALL WIRE TWINARC K148 CONTACT NOZZLE K149 LINC-FILL LONG STICKOUT EXTENSION K218 HORIZONTAL FILLET/LAP ATTACHMENT K219 FLUX HOPPER KIT K223 SOLENOID KIT K225 SUBMERGED ARC TWINARC KIT K238 HIGH FREQUENCY UNIT K239 TWINARC KIT FOR INNERSHIELD ELECTRODES K278 SPREADARC K281 SOLID WIRE STRAIGHTENER FOR TINY TWINARC K285 CONCENTRIC FLUX CONE K310 FLUX SCREEN K325 TC-3 TRAVEL CARRIAGE K334 START AND CRATER CONTROLS K336 REMOTE INTERFACE MODULE K337 WELD TIMER MODULE K349 MULTI-PROCEDURE KIT S22022 or S22182 CURRENT RELAY SPEED-FEED DRUMS SPEED-FEED REELS GENERAL This section contains a listing and short description of the accessories that are available with the NA-5 automatic welding system. TABLE C.1 – NA-5 AUTOMATIC WELDING SYSTEM ACCESSORIES. Return to Section TOC Return to Section TOCReturn to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC
ACCESSORIESC-3C-3 NA-5 LISTING OF ACCESSORIES K29 VERTICAL LIFT ADJUSTER When mounted in the NA-5 head mounting system, the K29 Vertical Lift Adjuster provides quick hand crank adjustment of the vertical head position. It also has some horizontal adjustability as described in Sec. T3.2.3 of operator’s manual IM305. Installation instructions are shipped with each K29 Vertical Lift Adjuster kit, are contained in the IM305 manual, and can be ordered as Sec. T2.2.11. K58 MAGNETIC SEPARATOR Useful with any submerged arc equipment. The unit removes foreign magnetic particles from reused submerged arc welding flux. Operating instructions are included with the kit. K96 HORIZONTAL ADJUSTER When mounted in the NA-5 head mounting system, the K96 Horizontal Adjuster provides quick hand crank adjustment of the horizontal head position. Installation instructions are shipped with each K96 Horizontal Adjuster kit, are contained in the IM305 manual, and can be ordered as Sec. T2.2.12. K129 SUBMERGED ARC SMALL WIRE TWINARC ® The Twinarc system provides for the feeding of two small solid wires through a single wire feeder. The Twinarc assembly includes a wire reel, reel brake, shaft and mounting bracket, drive roll, idle roll assembly, dual wire guides, and nozzle and contact tip or contact tip holder. Instructions are shipped with each kit, are contained in the IM305 manual, and can be ordered as Sec. T2.5.3 K129. K148 CONTACT NOZZLE AND K149 LINC-FILL TMLONG STICKOUT EXTENSION This Innershield and submerged arc nozzle is designed for 0.062 through 3/16 in. (1.57 through 4.76 mm) wire at high currents. When long stickout [2 to 5 (50.80 to 127.00 mm)] is required, the K149 Linc-Fill Long Stickout Extension is recommended along with the K237 Linc-Fill Starting Relay. Instructions are contained in the IM305 manual and can also be ordered as Sec. T2.2.7. K218 HORIZONTAL FILLET/LAP ATTACHMENT This special contact assembly automatically guides the electrode when making submerged arc horizontal fillet and lap welds to ensure accurate bead placement without expensive fixtures and clamps. Installation, operating, and maintenance instructions are shipped with each kit, are contained in the IM305 manual, and can also be ordered as Sec. T2.5.4. K219 FLUX HOPPER KIT This flux hopper, which has an electric flux valve, can be mounted on NA-5N and NA-5NF heads for submerged arc welding. Installation instructions are included with each kit. The operator and maintenance instructions are contained in the IM305 manual and can also be ordered as Sec. T2.5.9. K223 SOLENOID KIT The solenoid kit includes a valve to control water flow when using the cooling attachment on the K148 or K239 contact nozzle assembly. It opens when the start button is pressed and can be wired to close either when the stop button is pressed or when the arc goes out. Installation instructions are shipped with each kit. Return to Section TOC Return to Section TOCReturn to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC
ACCESSORIESC-4C-4 K225 SUBMERGED ARC TWINARC KIT The Twinarc kit provides for the feeding of two 5/64, 3/32, or 1/8 in. (1.98, 2.38, or 3.18 mm) solid wires through a single wire feeder. The electrode wire must be the same size. The assembly includes a wire reel, insulated reel mounting bracket, wire straightener, dual wire guides, nozzle, and contact block. Installation, operating, and maintenance instructions are shipped with each kit, are contained in the IM305 manual, and can be ordered as Sec. T2.5.3 K225. K238 HIGH FREQUENCY UNIT This unit supplies high frequency to the welding leads for more positive starts, which may be required for certain difficult starting applications. Factory-installed insulation is required. Instructions are shipped with each unit. Installation instructions are contained in the IM305 manual and can be ordered as Sec. T2.5.8. K239 TWINARC KIT FOR INNERSHIELD ®ELECTRODES This kit provides for welding with two Innershield electrodes. Two 3/32 in. (2.38 mm) flux-cored electrodes are fed through a single wire feeder. Both wires must be the same size. The K239 kit includes the nozzle equipped for water cooling, drive rolls, drive roll locating collar, idle roll assembly, ingoing and outgoing guide tubes, wire straightener, wire reel, and wire reel mounting shaft and insulation. Instructions are included in the kit, are contained in the IM305 manual, and can also be ordered as Sec. T2.5.3 K239. K278 SPREADARCTM The primary application for this accessory is for hardfacing buildup using a Twinarc nozzle. The combination “Spreadarc- Twinarc” covers large areas quickly with smooth beads of minimum admixture with the base metal. Flux cored electrode, openarc, and submerged arc procedures can be used. Instructions are shipped with the kit, are contained in the IM305 manual, and can also be ordered as Sec. T2.5.6. K281 SOLID WIRE STRAIGHTENER FOR TINY TWINARC This wire straightener will straighten 0.045 through 3/32 in. (1.14 through 2.38 mm) wire diameters. It is recommended for welding procedures requiring long stickout and where wire position accuracy is essential. Instructions are shipped with the kit, are contained in the IM305 manual, and can be ordered as Sec. T2.5.5. K285 CONCENTRIC FLUX CONE The concentric flux cone was designed to fit on the K148 Contact Nozzle alone, the K148 Contact Nozzle with a K149 Linc-Fill Long Stickout Extension, the K129 Submerged Arc Small Wire Twinarc, and the K391 nozzles. (The maximum electrical stickout when using the K149 Linc-Fill Long Stickout Extension will be 4 in. [101.6 mm.]). Use of this attachment results in the flux being fed concentrically around the electrodes. Installation, operating, and maintenance instructions are shipped with each kit, are contained in the IM305 manual, and can be ordered as Sec. T2.2.8 K285. K310 FLUX SCREEN Useful for any submerged arc equipment. It removes foreign magnetic particles from reused submerged arc welding flux. Operating instructions are included in the kit. K325 TC-3 TRAVEL CARRIAGE The K325 Travel Carriage carries the control box and wire drive head, in either direction, on a beam of suitable length and mechanical specifications. Two models are available: Standard and High Capacity. NA-5 Return to Section TOC Return to Section TOCReturn to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC
ACCESSORIESC-5C-5 NA-5 K334 START AND CRATER CONTROLS Easily installed procedure and timer boards to permit adjustment of wire speed and voltage. Can be installed to function at either the start of the weld or at the end for crater filling. Installation, operating, and maintenance instructions are shipped with each kit and can be ordered as Sec. T2.5.13 K334. K336 REMOTE INTERFACE MODULE Permits connection of customer-furnished remote start-stop and inch momentary contact closure or momentary 24 volt signals. Also used when a single remote signal is desired to start or stop multiple heads. This module replaces the earlier K336 Remote Pushbutton Interface Module. Installation and application instructions are shipped with each kit and can be ordered as Sec. T2.5.11 K336. K337 WELD TIMER MODULE Permits setting of weld time for an adjustable period. Eliminates need to press the “Stop” button. Instructions are included in the kit. K349 MULTI-PROCEDURE KIT The K349 Multi-Procedure Kit provides three additional weld mode procedure settings of wire feed speed and voltage, allowing the choice of four NA-5 weld mode procedures. Installation, operating, and maintenance instructions are shipped with each kit, are contained in the IM305 manual, and can be ordered as Sec. T2.5.19 K349. S22022 OR S22182 CURRENT RELAY MODULES The current relay is useful to fixture builders and others who need a signal indicating that welding current is flowing. Installation, operating, and maintenance instructions are shipped with each kit. The S22022 relay module is suitable for dry circuit applications and it is rated at 2 Amps, 115 VAC or 28 VDC. This relay has both normally open and normally closed contacts. The S22182 relay module is suitable for applications requiring at least 10 mA current and it is rated at 3 Amps, 115 VAC or 28 VDC. This relay only has normally open contacts. SPEED-FEED DRUM These drums must be set on a turntable which permits them to freely turn in a clockwise direction. Installation, operating, and maintenance instructions are contained in the IM305 manual and can be ordered as Sec. T2.5.7-A. SPEED-FEED REEL These reels require dereeling equipment that permits the reel to rotate freely as the electrode is used. Installation, operating, and maintenance instructions are contained in the IM305 manual and can be ordered as Sec. T2.5.7-B. Return to Section TOCReturn to Section TOCReturn to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC