Lincoln Na5 Service Manual
Have a look at the manual Lincoln Na5 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1 Lincoln manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
![](/img/blank.gif)
MECHANICAL INSTALLATION ELECTRIC SHOCK can kill. • Turn off input power to the welding power source using the disconnect switch before working on this equipment. INTRODUCTION This section covers the basic requirements to install the control box and welding head shown in Figure A.1. This section will give you mounting hole alignments, component mounting clearances, and any special instructions or precautions that must be fol- lowed when installing the control box and mounting head. CONTROL BOX INSTALLATION The control box can be mounted either on the standard travel carriage or on a separate fixture. It is electrically grounded by a lead in the input cable assembly. To install the control box on the standard travel carriage, use mounting kit T14469 and perform the following steps. Also refer to Figure A.2. 1. Align the mounting holes in adapter plate M-13945 to the holes in the travel carriage. 2. Install four hex head screws through the adapter plate and into the travel carriage. 3. Secure the control box to the adapter plate with four lock washers and four bolts, two from the bottom and two from the back. Before mounting the control box onto a fixture, you must provide mounting holes in the fixture per the measurements provided in Figure A.3 or dimension print S16717. When placing the mounting holes, ensure the controls and meters are convenient to the operator. INSTALLATIONA-4A-4 NA-5 WARNING ADAPTER PLATE TRAVEL CARRIAGE CONTROL BOX FIGURE A.2 – CONTROL BOX CARRIAGE MOUNTING. Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC
![](/img/blank.gif)
To install the control box on a fixture, perform the following steps and refer to Figure A.3.1. Align the mounting holes on the back and/or bottom of the control box with the holes you put in the fixture according to the measurements provided in Figure A.3. 2. Secure the control box to the fixture using lock washers and hex head screws at each of the mounting holes. WELDING HEAD INSTALLATION The welding head can be mounted either with the standard head mounting hardware or with the horizontal head and/or vertical lift adjusters. Design the installation of your welding head so it meets the adjustability requirements of your welding application. Refer to Section C, Accessories, for more information regarding the adjustable mounting hardware. The welding head and electrode are electrically “hot” when welding. They must be insulated from ground. Standard head mounting hardware and insulation are shipped with the NA-5 welding head. If you are mounting the welding head on a separate fixture, provide the mounting holes for the standard head mount as specified in Figure A.4. For best arc striking, use a rigid mounting that prevents the head from moving when the electrode strikes the work. FRONT VIEW FROM BOTTOM 1/4-20 THREAD HOLES 3.50 (88.9) VIEW FROM BACK 1/4-20 THREAD HOLES 1.71 (43.43) 1.09 (27.68) 0.28 (7.11) SLOTS 4 PLACES 0.41 (10.41) 0.43 (10.92) 13.77 (349.76) 12.75 (323.85) 0.562 DIA (14.27) 2 HOLES 12.00 (304.8) 12.00 (304.8) NOTE: DIMENSIONS ARE IN INCHES WITH MILLIMETERS IN PARENTHESES. 1.34 (34.04) 1.71 (43.43) APPROXIMATE INSULATOR SIZE 2.62 (66.55) 2.88 (73.15) 4.265 (108.33) 0.531 DIA. (13.49) NOTE: DIMENSIONS ARE IN INCHES WITH MILLIMETERS IN PARENTHESES. 4.5 (114.30) FIGURE A.4 – WELDING HEAD MOUNTING HOLES. INSTALLATIONA-5A-5 FIGURE A.3 – CONTROL BOXFIXTURE MOUNTING. NA-5 Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC
![](/img/blank.gif)
INSTALLATIONA-6A-6 NA-5 When mounting the welding head to the standard travel carriage, (see 305-B sec. T2.2.4) mount it so only a minimum of overhang weight exists. Mount the head so it stays within the dimension shown in Figure A.5. ELECTRICAL INSTALLATION ELECTRIC SHOCK can kill.• Do not touch electrically live parts such as output terminals or internal wiring. This section provides information on proper wiring procedures for the NA-5 welding sys- tem. This section also provides basic con- nection diagrams for connecting automatic welding systems to various welding power sources. INPUT POWER REQUIREMENTS 350 volt-amperes of 115 VAC 50/60 Hz power is required for the wire feed motor and controls. Another 250 volt-amperes may be required depending on the travel circuit. CONTROL BOX TO WELDING HEAD CONNECTIONS All welding heads include a 4 ft (1.2 m) motor cable and motor tachometer cable. Insert the plugs on these cables into the matching receptacles on the side of the control box. If the 4 ft (1.2 m) cables are not sufficient, install a K335 or K338 control to head extension cable of the length ordered [up to 30 ft (9.1 m)]. The K335, for the NA-5S head, includes motor, tachometer and flux hopper lead extensions with polarized plugs on each end, and electrode cables. The K338 for the NA-5N, NF, and SF heads is the same as the K335 without the flux hopper lead extension. The NA-5N and NA-5S also include two 4 ft (1.2 m) lengths of electrode cable. Bolt the terminals at one end of the the cable pair to the wire contact assembly and the terminals at the other end to the electrode leads on the power source to control cable assembly. Properly insulate the bolted connection. When the K335 or K338 extension cables are used between the controls and heads, the 4 ft (1.2 m) lengths of electrode cable are not used. If currents or duty cycles higher than 1000 amps at 80% duty cycle will be used, add additional electrode cable per Table A.1. TABLE A.1 FIGURE A.5 – MOUNT TO CARRIAGEOVERHANG DIMENSION. 19 IN. (483 MM) WARNING 80% Duty Cycle Below 1000 amps Two 4/0 1000 to 1300 amps Three 4/0 1300 to 1500 amps Four 4/0 Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC
![](/img/blank.gif)
The “F” models do not include the 4 ft (1.2 m) lengths of electrode cable as standard. If you are not using a K335 or K338 exten- sion cable for the NA-5NF or NA-5SF, order an appropriate length of the needed elec- trode cable. Connect it between the wire contact assembly and the control cable assembly as described above. POWER SUPPLY TO CONTROL BOX CONNECTIONS At the NA-5 control box, in order to activate the NA-5 weld current sensing switch, the electrode cables of the control cable assembly must be placed under the clamp bar on the left-hand side of the control box, as shown in Figure A.6. This is required for proper operation of the reed switch. The nuts holding the clamp bar in place need only to be pulled up snug. Do not overtighten. If a carriage is used, the electrode cables should also be clamped to it with the cable clamp supplied on the carriage. Do not clamp the control cable under the travel carriage clamp but route it over its top.Insert the polarized connector of the K215 or K597* control cable into the matching receptacle on the side of the control box. With the power source off, connect the control cable assembly to the power source as follows: 1. If using the multi-process power source (SAM, SA-800, SAF-600, DC-400, DC-600, DC-1000, or DC- 1500 types), be sure it is properly set for the welding process being used per the connection diagram (Figures A.8 to A.14). 2. Connect the K215 control cable leads to the power source terminal strip exactly as specified on the connection diagram.* Include all jumpers on the terminal strips as shown on the diagram. Do not put on any other jumpers. If currents or duty cycles higher than 1000 amps at 80% duty cycle will be used, add additional electrode cables to the K215 assembly per Table A.1. 3 Depending on the power source and the process to be used, the jumpers on the NA-5 voltage board may have to be changed. As shipped, the NA-5 is connected for use with the DC-400, DC-600, DC-1000, and DC-1500 type power sources. For other power sources, refer to the appropriate connection diagram and to IM305 Sec. T3.6. 4. Connect work leads of sufficient size and length per Table A.1. between the “To Work” stud on the power source and the work. Be sure the connection to the work makes a tight and clean metal-to-metal contact. *The K597 cable assembly has a 14-pin MS-type connector for use with later model Lincoln CV powersources. INSTALLATIONA-7A-7 NA-5 FROM POWER SOURCE TO WELDING HEAD CLAMP BAR FIGURE A.6 – CONTROL BOXELECTRICAL CONNECTIONS. Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC
![](/img/blank.gif)
INSTALLATIONA-8A-8 NA-5 ELECTRODE POLARITY ELECTRIC SHOCK can kill.• Turn off input power to the welding power source using the disconnect switch before working on this equipment. Polarity is changed at the power source. The polarity of the NA-5 control circuit is shipped connected for electrode positive. If electrode negative is required, two leads inside the NA-5 control must be reversed. Proceed as follows: 1. Turn off the input power to the NA-5 control box by turning off the welding power source. 2. Open the control box door and locate the terminal strips on the back of the control box in the lower left-hand corner as shown in Figure A.7. 3. On the right end of the lower terminal strip, interchange the black and white leads going to the terminals marked (+) and (-). The black lead (#67) must be connected to the same polarity as the electrode welding lead; i.e. if the electrode is positive, connect the black lead to the (+) terminal on the terminal strip. The white lead (#21) is connected to the opposite polarity terminal. POWER SOURCE CONNECTION DIAGRAMS The following section contains the wiring diagrams necessary to connect the applicable power source to the control box. If there is no diagram, refer to power source manual. ELECTRIC SHOCK can kill.• Turn off input power to the welding power source using the disconnect switch before working on this equipment. WARNING TERMINAL STRIPS FIGURE A.7 – TERMINAL STRIP LOCATION. WARNING Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC
![](/img/blank.gif)
INSTALLATIONA-9A-9 NA-5 FIGURE A.8 – CONNECTION OF NA-5 (ALL) TO A DC-600. N.A. ON EARLIER DC-600S, #67 TERMINAL WAS ALSO ON THE TERMINAL STRIP. N.B. WELDING CABLES MUST BE OF PROPER CAPACITY FOR THE CURRENT AND DUTY CYCLE\ OF IMMEDIATE AND FUTURE APPLICATIONS. N.C. EXTEND LEAD #21 USING #14 OR LARGER INSULATED WIRE PHYSICALLY SUITABLE F\ OR THE INSTALLATION. AN S-16586 - [ ] REMOTE VOLTAGE SENSING WORK LEAD IS AVAILABLE FOR THIS PURPOSE. CONNECT IT DIRECTLY TO THE WORK PIE\ CE KEEPING IT SEPARATE FROM THE WELDING WORK CABLE CONNECTION TO THE WORK PIECE. FOR CONVENIENCE, THIS EXTENDED #21 LEAD SHOULD BE TAP\ ED ALONG THE WELDING WORK CABLE. N.D. TAPE UP BOLTED CONNECTION. N.E. CONNECT THE NA-5 CONTROL CABLE GROUNDING LEAD TO THE FRAME TERMINAL MARK\ ED NEAR THE POWER SOURCE TERMINAL STRIP. THE POWER SOURCE MUST BE PROPERLY GROUNDED. N.F. IF USING AN OLDER K-215 CONTROL CABLE: CONNECT LEAD #75 TO #75 ON TERMIN\ AL STRIP, CONNECT LEAD #76 TO #76 ON TERMINAL STRIP, CONNECT LEAD #77 TO #77 ON TERMINAL STRIP. N.G. THE JUMPERS ON THE NA-5 VOLTAGE BOARD MUST BE CONNECTED AS FOLLOWS: CONN\ ECT RED JUMPER TO PIN S. CONNECT WHITE JUMPER TO PIN B. N.H. CONNECT A JUMPER FROM N TO P. THERE IS NO NPS TERMINAL STRIP ON DC-6\ 00 CODES ABOVE 8200. N.J. FOR PROPER NA-5 OPERATION, THE ELECTRODE CABLES MUST BE SNUGGED UNDER TH\ E CLAMP BAR ON THE LEFT SIDE OF THE NA-5 CONTROL BOX. NOTE: DIAGRAM SHOWS ELECTRODE CONNECTED POSITIVE. TO CHANGE POLARITY, TURN POWER OFF, REVERSE THE ELECTRODE AND WORK CABLES AT THE POWER SOURCE AND POSITON THE SWITCH ON POWER SOURCE TO PROPER POLARITY. REFER TO NA-5 OPERATING MANUAL FOR REQUIRED NA-5 CONTROL BOX POLARITY CONNECTIONS. ALL CODES: TURN OFF INPUT POWER ADJUST THE POWER SOURCE: DC-600: 1. CONNECT ELECTRODE CABLES TO TERMINAL OF DESIRED POLARITY. 2. SET TOGGLE SWITCH TO SAME POLARITY AS THE ELECTRODE CABLE CONNECTION. 3. SET TOGGLE SWITCH TO REMOTE. 4. SET MODE SWITCH TO THE DESIRED POSITION FOR THE PROCESS TO BE USED. DC-600 CODES 8000-8045: FOR SUB ARC: 1. SET MODE SWITCH TO CV SUB ARC. 2. WHITE LEAD ON CONTROL PC BOARD IS CONNECTED TO PIN M AND BLUE LEAD IS CONNECTED TO W. FOR ALL OPEN ARC PROCESSES EXCEPT NR-302 AND NR-203 ELECTRODES: 1. SET MODE SWITCH TO CV INNERSHIELD. 2. WHITE LEAD ON CONTROL PC BOARD IS CONNECTED TO PIN M AND BLUE LEAD IS CONNECTED TO W. FOR NR-203 AND NR-302 ELECTRODES: 1. SET MODE SWITCH TO CV INNERSHIELD. 2. WHITE LEAD ON CONTROL PC BOARD IS CONNECTED TO PIN I AND BLUE LEAD IS CONNECTED TO S.DC-600 CODES 8046-8200: FOR SUB ARC: 1. SET MODE SWITCH TO CV SUB ARC. 2. WHITE LEAD ON CONTROL PC BOARD IS CONNECTED TO PIN M. FOR ALL OPEN ARC PROCESSES EXCEPT MR-203 ELECTRODES: 1. SET MODE SWITCH TO CV INNERSHIELD. 2. WHITE LEAD ON CONTROL PC BOARD IS CONNECTED TO PIN M. FOR NR-203 ELECTRODES: 1. SET MODE SWITCH TO CV INNERSHIELD. 2. WHITE LEAD ON CONTROL PC BOARD IS CONNECTED TO PIN I. DC-600 CODES ABOVE 8200: FOR SUB ARC: 1. SET MODE SWITCH TO CV SUB ARC. FOR ALL OPEN ARC PROCESSES: 2. SET MODE SWITCH TO CV INNERSHIELD. FOR OPTIMUM PERFORMANCE WITH NA-5, DC-600S WITH CODES 8288 AND ABOVE ARE PREFERRED. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, SEE NA-5 OPERATING MANUAL. P A B P B . A. TO NA-5 INPUT CABLE PLUG CONNECT TO CABLES FROM NA-5 WIRE CONTACT ASSEMBLY CONNECT TO WORK CLEVELAND, OHIO U.S.A. Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC
![](/img/blank.gif)
INSTALLATIONA-10A-10 NA-5 FIGURE A.9 – CONNECTION OF NA-5 (ALL) TO A DC-650 PRO NOTE: ABOVE DIAGRAMS SHOW ELECTRODE CONNECTED POSITIVE. TO CHANGE POLA\ RITY, TURN POWER OFF, REVERSE THE ELECTRODE AND WORK CABLES AT THE POWER SOURCE AND POSITION THE SWITCH ON THE POWER\ SOURCE TO PROPER POLARITY. REFER TO NA-5 OPERATING MANUAL FOR REQUIRED NA-5 CONTROL BOX POLARITY CONNECTIONS\ . DC650 PRO POWER SOURCE SETTINGS 1. TURN OFF INPUT POWER. 2. CONNECT ELECTRODE CABLES TO TERMINALS OF DESIRED POLARITY. 3. SET TOGGLE SWITCH TO SAME POLARITY AS ELECTRODE CABLE CONNECTION. 4. SET TOGGLE SWITCH TO REMOTE. 5. SET MODE SWITCH TO DESIRED POSITION FOR THE PROCESS TO BE USED. 6. CONNECT NEGATIVE OUTPUT CABLES TO MATCH MODE SWITCH SETTING. P AR P A N.A. WELDING CABLES MUST BE SIZED FOR CURRENT AND DUTY CYCLE OF APPLICATION. \ N.B. EXTEND LEAD #21A BY REMOVING LEAD #21A FROM THE TERMINAL STRIP AND CONNE\ CTING IT TO A #14 OR LARGER INSULATED WIRE PHYSICALLY SUITABLE FOR THE INSTALLATION. N.C. EXTEND LEAD #21 USING A #14 OR LARGER INSULATED WIRE PHYSICALLY SUITABLE\ FOR INSTALLATION. N.D. CONNECT EXTENDED LEAD DIRECTLY TO THE WORK PIECE KEEPING IT SEPARATE FRO\ M THE WELDING WORK CABLE CONNECTION TO THE WORK PIECE. FOR CONVENIENCE, THIS EXTENDED LEAD SHOULD BE TAPED ALONG THE WELDING WORK C\ ABLE. N.E. TAPE UP CONNECTION. N.F. FOR PROPER NA-5 OPERATION, THE ELECTRODE CABLES MUST BE SNUGGED UNDER T\ HE CLAMP BAR ON THE LEFT SIDE OF THE NA-5 CONTROL BOX. N.G. CONNECT NEGATIVE OUTPUT CABLES TO STUDS TO MATCH DC650 PRO MODE SWITCH S\ ETTING. N.H. THE JUMPERS ON THE NA-5 VOLTAGE BOARD MUST BE CONNECTED AS FOLLOWS: CONN\ ECT RED JUMPER TO PIN S, CONNECT WHITE JUMPER TO PIN B. N.J. IF USING AN OLDER K-215 CONTROL CABLE, CONNECT LEAD #75 TO #75 ON TERMIN\ AL STRIP, CONNECT LEAD #76 TO #76 ON THE TERMINAL STRIP, CONNECT LEAD #77 TO #77 ON THE TERMINAL STRIP. N.K. CONNECT THE NA-5 CONTROL CABLE GROUNDING LEAD TO THE FRAME TERMINAL MARK\ ED NEAR THE POWER SOURCE TERMINAL STRIP. P6 CONTROLCABLE TO NA-5 INPUT CABLE PLUG CONNECT TO CABLES FROM NA-5 WIRE CONTACT ASSEMBLY TO NA-5 INPUT CABLE PLUG CONNECT TO CABLES FROM NA-5 WIRE CONTACT ASSEMBLY CONNECTTO WORK CLEVELAND, OHIO U.S.A. Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC
![](/img/blank.gif)
INSTALLATIONA-11A-11 NA-5 FIGURE A.10 – CONNECTION OF NA-5 (ALL) TO A R3S-400, -600, OR -800WITH NO LINE VOLTAGE COMPENSATOR (OBSOLETE). R3S POWER SOURCE SETTINGS TURN POWER SOURCE OFF. FOR ALL PROCESSES: 1. CONNECT ELECTRODE CABLE TO TERMINAL OF DESIRED POLARITY. 2. SET THE POLARITY SWITCH TO THE SAME POLARITY AS THE ELECTRODE CABLE CONNECTION. 3. SET TOGGLE SWITCH TO REMOTE. 4. INSTALL VOLTAGE TRIANGLE IN A POSITION AS CLOSE AS POSSIBLE TO THE DESIRED ARC VOLTAGE. NA-5 SETTINGS FOR SUB ARC: 1. RED LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN S. 2. WHITE LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN A. FOR ALL OPEN ARC PROCESSES: 1. RED LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN F. 2. WHITE LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN A. NOTE: ABOVE DIAGRAM SHOWS ELECTRODE CONNECTED POSITIVE. TO CHANGE POLARITY, T\ URN POWER OFF, REVERSE THE ELECTRODE AND WORK CABLES AT THE POWER SOURCE AND POSITION THE SWITCH ON POWER SOURCE TO PROPER POLARITY.\ REFER TO NA-5 OPERATING MANUAL FOR REQUIRED NA-5 CONTROL BOX POLARITY CONNECTIONS. N.A. ADD JUMPER FROM #75 TO #76, USING INSULATED COPPER WIRE. N.B. WELDING CABLES MUST BE OF PROPER CAPACITY FOR THE CURRENT AND DUTY CYCLE\ OF IMMEDIATE AND FUTURE APPLICATIONS. N.C. EXTEND LEAD #21 USING #14 OR LARGER INSULATED WIRE PHYSICALLY SUITABLE F\ OR THE INSTALLATION. AN S -16586 [ ] REMOTE VOLTAGE-SENSING WORK LEAD\ IS AVAILABLE FOR THIS PURPOSE. CONNECT IT DIRECTLY TO THE WORK PIECE, K\ EEPING IT SEPARATE FROM THE WELDING WORK CABLE CONNECTION TO THE WORK PIECE. FOR CONVENIENCE, THIS EXTENDED #21 LEAD SHOULD BE TAPED ALO\ NG THE WELDING WORK CABLE. N.D. TAPE UP BOLTED CONNECTION. N.E. CONNECT THE NA-5 CONTROL CABLE GROUNDING LEAD TO THE FRAME TERMINAL MARK\ ED , NEAR THE POWER SOURCE TERMINAL STRIP. THE POWER SOURCE MUST BE PROPERLY GROUNDED. N.F. IF USING AN OLDER K-215 CONTROL CABLE: CONNECT LEAD #75 TO #75 ON TERMIN\ AL STRIP, CONNECT LEAD #76 TO #77 ON TERMINAL STRIP, CONNECT LEAD #77 TO #76 ON TERMINAL STRIP, AND ADD JUMPER PER N.A. N.G. ON EARLIER R3S MACHINES, #67 AND #1 TERMINALS WERE ALSO ON THE TERMINAL \ STRIP. N.H. THE UPPER TERMINAL STRIP (#75, #76, #77) WAS NOT PRESENT ON EARLY R3S \ MACHINES. THOSE MACHINES ARE NOT COMPATIBLE WITH THE NA-5 SINCE THERE \ CAN BE NO ADJUSTMENT OF VOLTAGE BY THE NA-5. N.J. FOR PROPER NA-5 OPERATION, THE ELECTRODE CABLES MUST BE SNUGGED UNDER T\ HE CLAMP BAR ON THE LEFT SIDE OF THE NA-5 CONTROL BOX. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, SEE NA-5 OPERATING MANUAL. B B B POSITIVE CLEVELAND, OHIO U.S.A. Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC
![](/img/blank.gif)
INSTALLATIONA-12A-12 NA-5 FIGURE A.11 – CONNECTION OF NA-5 (ALL) TO A SAM-400 MOTORGENERATOR OR ENGINE WELDER. NOTE: TO CHANGE POLARITY, TURN POWER OFF, AND POSITION THE SWITCH ON POWER SOU\ RCE TO PROPER POLARITY. REFER TO NA-5 OPERATING MANUAL FOR REQUIRED NA-5 CONTROL BOX POLARITY CONNECTIONS. N.A. REMOVE SAM PORTABLE FIELD CONTROL AND CONNECT NA-5 CONTROL CABLE. N.B. WELDING CABLES MUST BE OF PROPER CAPACITY FOR THE CURRENT AND DUTY CYCLE\ OF IMMEDIATE AND FUTURE APPLICATIONS. N.C. EXTEND LEAD #21 USING #14 OR LARGER INSULATED WIRE PHYSICALLY SUITABLE F\ OR THE INSTALLATION. AN S-16586-[ ] REMOTE VOLTAGE-SENSING WORK LEAD IS AVAILABLE FOR THIS PURPOSE. CONNECT IT DIRECTLY TO THE WORK PIECE, K\ EEPING IT SEPARATE FROM THE WELDING WORK CABLE CONNECTION TO WORK PIECE. FOR CONVENIENCE, THIS EXTENDED #21 LEAD SHOULD BE TAPED ALO\ NG THE WELDING WORK CABLE. N.D. TAPE UP BOLTED CONNECTION. N.E. CONNECT THE NA-5 CONTROL CABLE GROUNDING LEAD TO THE FRAME TERMINAL MARK\ ED , NEAR THE POWER SOURCE TERMINAL STRIP. THE POWER SOURCE MUST BE PROPERLY GROUNDED. N.F. IF USING AN OLDER K-215 CONTROL CABLE: CONNECT LEAD #76 TO #75 ON TERMIN\ AL STRIP, CONNECT LEADS #75 AND #77 TO #76 ON TERMINAL STRIP. N.G. ON EARLIER SAM MACHINES, #1 TERMINAL WAS ALSO ON THE TERMINAL STRIP. N.H. FOR PROPER NA-5 OPERATION, THE ELECTRODE CABLES MUST BE SNUGGED UNDER TH\ E CLAMP BAR ON THE LEFT SIDE OF THE NA-5 CONTROL BOX. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, SEE NA-5 OPERATING MANUAL. NA-5 SETTINGS FOR SUB ARC: 1. RED LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN S. 2. WHITE LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN A. FOR ALL OPEN ARC PROCESSES: 1. RED LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN F. 2. WHITE LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN A. SAM POWER SOURCE SETTINGS FOR SUB ARC: 1. SET THE ELECTRODE POLARITY SWITCH TO THE VARIABLE VOLTAGE POSITION OF THE POLARITY DESIRED FOR THE PROCESS BEING USED. 2. SET THE TOGGLE SWITCH TO CONSTANT VOLTAGE. 3. SET THE CONSTANT VOLTAGE CONTROL TO NUMBER 7 AND THE CURRENT CONTROL TO 500. FOR ALL OPEN ARC PROCESSES: 1. SET THE ELECTRODE POLARITY SWITCH TO THE CONSTANT VOLTAGE POSITION OF THE POLARITY DESIRED FOR THE PROCESS BEING USED. 2. SET THE TOGGLE SWITCH TO CONSTANT VOLTAGE. 3. SET THE CONSTANT VOLTAGE CONTROL TO NUMBER 5. TURN POWER SOURCE OFF. P BOLT TO CABLES FROM NA-5 WIRE CONTACTASSEMBLY N.B. N.B. CLEVELAND, OHIO U.S.A. Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC
![](/img/blank.gif)
INSTALLATIONA-13A-13 NA-5 FIGURE A.12 – CONNECTION OF NA-5 (ALL) TO A SAM-650 ENGINE WELDER. NOTE: TO CHANGE POLARITY, TURN POWER OFF, AND POSITION THE SWITCH ON POWER SOURCE TO PROPER POLARITY. REFER TO NA-5 OPERATING MANUAL FOR REQUIRED NA-5 CONTROL BOX POLARITY CONNECTIONS. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, SEE NA-5 OPERATING MANUAL. SAM POWER SOURCE SETTINGS FOR SUB ARC: 1. SET THE ELECTRODE POLARITY SWITCH TO THE POLARITY DESIRED FOR THE PROCESS BEING USED. 2. SET THE TOGGLE SWITCH TO CONSTANT VOLTAGE. 3. SET THE CONSTANT VOLTAGE CONTROL TO NUMBER 7. 4. CONNECT THE TAP CABLE TO THE 300-575, MAX, SLOPE STUD. FOR ALL OPEN ARC PROCESSES: 1. SET THE ELECTRODE POLARITY SWITCH TO THE POLARITY DESIRED FOR THE PROCESS BEING USED. 2. SET THE TOGGLE SWITCH TO CONSTANT VOLTAGE. 3. SET THE CONSTANT VOLTAGE CONTROL TO NUMBER 5. 4. CONNECT THE TAP CABLE TO THE 450-MAX, MED SLOPE STUD. NA-5 SETTINGS FOR SUB ARC: 1. RED LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN S. 2. WHITE LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN A. FOR ALL OPEN ARC PROCESSES: 1. RED LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN F. 2. WHITE LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN A. TURN POWER SOURCE OFF. N.A. REMOVE SAM PORTABLE FIELD CONTROL AND CONNECT NA-5 CONTROL CABLE. N.B. WELDING CABLES MUST BE OF PROPER CAPACITY FOR THE CURRENT AND DUTY CYCLE\ OF IMMEDIATE AND FUTURE APPLICATIONS. N.C. EXTEND LEAD #21 USING #14 OR LARGER INSULATED WIRE PHYSICALLY SUITABLE F\ OR THE INSTALLATION. AN S-16586- [ ] REMOTE VOLTAGE-SENSING WORK LEAD IS AVAILABLE FOR THIS PURPOSE. CONNECT IT DIRECTLY TO THE WORK PIE\ CE, KEEPING IT SEPARATE FROM THE WELDING WORK CABLE CONNECTION TO THE WORK PIECE. FOR CONVENIENCE, THIS EXTENDED #21 LEAD SHOULD BE TA\ PED ALONG THE WELDING WORK CABLE. N.D. TAPE UP BOLTED CONNECTION. N.E. CONNECT THE NA-5 CONTROL CABLE GROUNDING LEAD TO THE FRAME TERMINAL MARK\ ED NEAR THE POWER SOURCE TERMINAL STRIP. THE POWER SOURCE MUST BE PROPERLY GROUNDED. N.F. IF USING AN OLDER K-215 CONTROL CABLE: CONNECT LEAD #76 TO #75 ON TERMIN\ AL STRIP, CONNECT LEADS #75 AND #77 TO #76 ON TERMINAL STRIP. N.G. ON EARLIER SAM MACHINES, #1 TERMINAL WAS ALSO ON THE TERMINAL STRIP. N.H. FOR PROPER NA-5 OPERATION, THE ELECTRODE CABLES MUST BE SNUGGED UNDER TH\ E CLAMP BAR ON THE LEFT SIDE OF THE NA-5 CONTROL BOX. PP P . . TAP POWER SOURCE TO NA-5 INPUTCABLE PLUG BOLT TO CABLES FROM NA-5 WIRE CONTACT ASSEMBLY CLEVELAND, OHIO U.S.A. Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC