Galaxy 2 Series Installation Manual
Zones
The Galaxy 2–20 has 12 on-board zones expandable to 20 (RS485 bus).
The Galaxy 2–44+ has 12 on-board zones expandable to 44 (RS485 bus) or 36 (ECP bus).
The zones on the Galaxy 2 Series can function in one of three modes; Normal Closed, Double Balanced and
U.S. End of line. Zone wiring for the three modes are illustrated in the following three Figures:
    
 
 
 
 
 
 
1K1K
Figure 6. Zone wiring for Normal Closed Zones
Figure 7. Zone wiring for Double Balanced...

Page 22

14
Galaxy 2 Series Installation Manual
Figure 9. Keyswitch/Push-Set Zone wiring
Wiring Zones
Keyswitch
zone
Push-set
zone
1k to unset, 2k to set
(only for a * keyswitch zone)
1k 
1%
Open - Closed
1k 
1k 
1k 
1k 
100mOR
Closed - Open
1%1%
1% 1%
Wiring Zones
The zones on Galaxy 2 Series panels are defaulted as double balanced.  Each zone is 1 kΩ closed and 2 kΩ
open. The transition from 1 to 2 kΩ generates an alarm condition.  Refer to Table 2 for details of the zone
resistance and resulting conditions....

Page 23

15
Galaxy 2 Series Installation Manual
Zone Addresses
Each zone on the Galaxy 2 Series has a 4-digit address. For example: 1004, 1058. The address is made up of
three reference numbers as shown in the following figure:
Figure 10. Zone Addresses
The example above, 1004,  is the detector connected to line 1, RIO 00, zone 4.
Zone Numbering System
The numbering system is as follows:
1. The first number is the Galaxy 2 Series Panel line that the RIO/Expander is connected to. This will
always be 1.
2. The next...

Page 24

16
Galaxy 2 Series Installation Manual
Outputs
The Galaxy 2 Series has four on-board outputs;  Bells, Strobe, Speaker and Set. The format of the address-
ing of the outputs is similar to zones. The addresses of these outputs are as follows:
Table 3. Output Addresses
Output Addresses
Table 4. Trigger Output Addresses *NOTE:Output 1002 - This output is configured as a 16 Ohm speaker driver (AC signal). The speaker
should be connected between this output and +12V. The speaker Entry/Exit volume is...

Page 25

17
Galaxy 2 Series Installation Manual
Figure 12. Daisy-chain Configuration
Data Buses
Two separate data buses are available to connect the Galaxy 2–44+ panel to its peripherals.
Communication between the Galaxy 2–44+ control panel and the peripherals attached to it (see Figure 1),
takes place on the data bus. The control panel constantly monitors the peripherals attached to it. A break in
the communication from any of the peripherals generates a tamper alarm.
RS485 Wiring Configurations
The system must...

Page 26

18
Galaxy 2 Series Installation Manual
RS485 Wiring Recommendations
1. The system must be wired in a daisy-chain configuration. Spur and star configurations must not be used.
2. The recommended cable used to connect the RS485 (AB) line is twisted pair screened cable (Belden
8723 equivalent). However, for cable runs of less than 100m in normal environments, standard 4-core
cable can normally be used.
3. There must only be a single AB pair of wires in each of the cables.
4. The power supply in the Galaxy 2...

Page 27

19
Galaxy 2 Series Installation Manual
Figure 15. GSM Module fitted to underside of Galaxy 2-44 PCB
Built-in Dialler/Modem
The built-in dialler allows signalling to an Alarm Receiving Centre (ARC), SMS signalling and remote servicing
from a PC.
LED’S
There are two LED’s on the Galaxy 2–44+  PCB. Pulsing of the red LED1 indicates an active telecommuni-
cations. Illumination of the green LED2 indicates the presence of AC mains supply.
There is one LED on the Galaxy 2–20 PCB. Pulsing of this LED indicates...

Page 28

20
Galaxy 2 Series Installation Manual
Panel Mounting (Plastic Box)
Installation Kit
The Galaxy 2 Series plastic box comes with an installation kit. It contains 13 zone links, a cable clamp with
two self tapping screws, two M4 x 20mm lid screws, a tamper spring, battery connector leads and 24,  1K
resistors.
WARNING:The lid of the plastic box must not be removed before isolating the mains supply.
Illumination of the keypad power LED indicates the presence of a.c. mains supply.
Removing the Enclosure Lid...

Page 29

21
Galaxy 2 Series Installation Manual
Remove the PCB
1. Gently pull back the PCB mounting clips to free the PCB.
2. Lift the PCB free of the PCB mounting pillars.
Replace the PCB
1. Insert the PCB into the PCB mounting slots.
2. Ensure that any cabling is clear of the PCB support pillars.
3. Gently pull back the PCB mounting clips and place the PCB on top of the PCB support pillars.
4. Release the PCB mouting clips ensuring that they spring back into place and that the PCB is held firmly in
place....

Page 30

22
Galaxy 2 Series Installation Manual
Panel Mounting (Metal Box)
Installation Kit
The Galaxy 2 Series metal box comes with an installation kit. It contains two No.8 x 12 mm self-tapping lid
screws, 6160 Text Programming Overlay, two battery leads (one red and one black), 10 mm cable staple and
24,  1K resistors.
WARNING:The lid of the metal box must not be removed before isolating the mains supply.
Illumination of the keypad power LED indicated the presence of a.c. mains supply.
Removing and Installing...