Home > Honeywell > Control panel > Honeywell Galaxy 2 User Manual

Honeywell Galaxy 2 User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell Galaxy 2 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							13
    Galaxy 2 Series Installation Manual
    Zones
    The Galaxy 2–20 has 12 on-board zones expandable to 20 (RS485 bus).
    The Galaxy 2–44+ has 12 on-board zones expandable to 44 (RS485 bus) or 36 (ECP bus).
    The zones on the Galaxy 2 Series can function in one of three modes; Normal Closed, Double Balanced and
    U.S. End of line. Zone wiring for the three modes are illustrated in the following three Figures:
        
     
     
     
     
     
     
    1K1K
    Figure 6. Zone wiring for Normal Closed Zones
    Figure 7. Zone wiring for Double Balanced Zones
    Figure 8. Zone wiring for US EOL Zones
    The mode of operation for the zones is programmed from menu option 51.46 = Parameters. Zone Resist-
    ance. The default zone resistors are 1k ohm. However this can be changed in option 51.46. It is strongly
    recommended that the maximum cable run on each zone is 100 m.
    Zone Links
    The bell tamper circuit can be shorted using the Links provided in the installation kit.  If the zones are pro-
    grammed as Double Balanced or U.S. End of Line, fit a 1k resistor across the zone and not the zone link. It is
    strongly recommended that this be done if any of the circuits are not to be used.
    Zones
    1K
    1K
    ALARM       TAMP 
    						
    							14
    Galaxy 2 Series Installation Manual
    Figure 9. Keyswitch/Push-Set Zone wiring
    Wiring Zones
    Keyswitch
    zone
    Push-set
    zone
    1k to unset, 2k to set
    (only for a * keyswitch zone)
    1k 
    1%
    Open - Closed
    1k 
    1k 
    1k 
    1k 
    100mOR
    Closed - Open
    1%1%
    1% 1%
    Wiring Zones
    The zones on Galaxy 2 Series panels are defaulted as double balanced.  Each zone is 1 kΩ closed and 2 kΩ
    open. The transition from 1 to 2 kΩ generates an alarm condition.  Refer to Table 2 for details of the zone
    resistance and resulting conditions.
    NOTE:The circuit debounce time (the period the zone must remain open to register a change in condition) is
    300 milliseconds by default.
    Table 2. Zone Resistance
    Multiple detectors can be wired into a single zone. The maximum number of detectors that can be connected
    to a single zone is 10.
    Wiring Keyswitches
    The transition from 1 kΩ to 2 kΩ initiates the setting procedure of an unset system, the transition from 2 kΩ to
    1 kΩ instantly unsets a set system.  If the system is already set, then the transition from 1 kΩ to 2 kΩ has no
    effect.  If the system is unset, the transition from 2 kΩ to 1 kΩ has no effect.
    The wiring of the keyswitch is shown in  Figure 9.
    Wiring Push-Set Buttons
    Zones programmed as Push-Set (terminator) buttons can be open going closed (2 kΩ to 1 kΩ) or closed
    going open (1 kΩ to 2 kΩ). The first activation of the terminator button initialises its status to the system.
    NOTE:For push-set zones to operate, parameter 51.08, Exit Terminate, must be set up.
    The wiring of the terminator is shown in the following Figure .
    Zone Resistance (ohms) Condition
    0-700 Tamper Short Circuit (TAMP S/C)
    700-1500 Normal (CLOSED)
    1500-11000 Alarm (Open) (OPEN)
    11000-infinity Tamper Open Circuit (TAMP O/C) 
    						
    							15
    Galaxy 2 Series Installation Manual
    Zone Addresses
    Each zone on the Galaxy 2 Series has a 4-digit address. For example: 1004, 1058. The address is made up of
    three reference numbers as shown in the following figure:
    Figure 10. Zone Addresses
    The example above, 1004,  is the detector connected to line 1, RIO 00, zone 4.
    Zone Numbering System
    The numbering system is as follows:
    1. The first number is the Galaxy 2 Series Panel line that the RIO/Expander is connected to. This will
    always be 1.
    2. The next two numbers refer to the address of the RIO/Expander that the zone is on.
    00 = On board RIO
    01 = On board RIO
    02 = RIO/Expander 1
    03 = RIO/Expander 2
    04 = RIO/Expander 3
    05 = RIO 4
    3. The last number is the actual zone on the RIO/Expander 1-8. Therefore the valid zone numbers are:
    1001 - 1004
    1011 - 1018
    1021 - 1028
    1031 - 1038
    1041 - 1048
    1051 - 1058
    This gives a total of 44 zones.
    Zone Addresses
    Example: 1004
    Represents Panel
    Line No.Represents
    RIO AddressRepresents
    Zone No. 1-8 on 
    RIO/Expander
    GALAXY
     2 Series
    PANEL
    1 
    RIO 
    ADDRESS 00ZONE 4
    1004 
    						
    							16
    Galaxy 2 Series Installation Manual
    Outputs
    The Galaxy 2 Series has four on-board outputs;  Bells, Strobe, Speaker and Set. The format of the address-
    ing of the outputs is similar to zones. The addresses of these outputs are as follows:
    Table 3. Output Addresses
    Output Addresses
    Table 4. Trigger Output Addresses *NOTE:Output 1002 - This output is configured as a 16 Ohm speaker driver (AC signal). The speaker
    should be connected between this output and +12V. The speaker Entry/Exit volume is controlled
    by parameter 51.10. It is possible to reprogram the output to operate as a normal switched
    negative output by programming parameter 51.15 to 0=Switch DC. However, when it is
    reprogrammed to operate as Switch DC, a loudspeaker should never be connected directly to
    this terminal otherwise damage may result. Always ensure that this parameter is set to 1=SPK
    Driver, before connecting a loudspeaker.
    Trigger Header
    The Trigger Header on the Galaxy 2 Series is a set of pins, which consists of programmable outputs for an
    external communication module. The connection is via an optional ribbon cable (Part No. A229).
    Trig 1-8
    There are eight trigger outputs, which are intended as communication triggers, but can be used for any pur-
    pose. By default these outputs are programmed as positive. They are designed to sink current (to 0V) not
    source current (from 12V). The addresses of these outputs are as follows:
    Output
    AddressDefault
    functionCurrent (mA)
    0001 Fire 100
    0002 Panic 100
    0003 Intruder 100
    0004 Set 100
    0005 Omit 100
    0006 Not Used 100
    0007 Confirm 100
    0008 Not Used 100
    The function of the trigger outputs can be programmed in menu 53=Outputs.
    Output
    AddressDefault
    functionCurrent (mA) Normal State Active State
    1001 Set 100 Off 0V
    1002
    *SPK Driver - - -
    1003 Bell 100 Off 0V
    1004 Strobe 100 Off 0V 
    						
    							17
    Galaxy 2 Series Installation Manual
    Figure 12. Daisy-chain Configuration
    Data Buses
    Two separate data buses are available to connect the Galaxy 2–44+ panel to its peripherals.
    Communication between the Galaxy 2–44+ control panel and the peripherals attached to it (see Figure 1),
    takes place on the data bus. The control panel constantly monitors the peripherals attached to it. A break in
    the communication from any of the peripherals generates a tamper alarm.
    RS485 Wiring Configurations
    The system must be wired in a daisy-chain configuration.  That is the A line from the previous peripheral is
    connected to the A terminal of the current peripheral and then on to the A line of the next peripheral.
    The RS485 (AB) line must have a 680 Ω resistor fitted across the A and B terminals of the last peripheral on
    the line.Figure 11. Trigger Header
    Inputs
    Line Fault: This input tells the panel that the communicator has a telephone line fault (active low).
    Reset:This input from the communicator resets the panel on a low to high signal (negative removed).
    Supply
    A 100 mA, 12V output is also provided. The output is fused by the on-board AUX FUSE (F2).
    Trigger Header
    ResetLine Fault
    GND
    +12V
    Trig 1 Trig 2Trig 3 Trig 4Trig 5 Trig 6Trig 7 Trig 8
    Galaxy 2-44
    Control Panel
    680 Ω 
    Factory fitted on PCB
    ABA
    B
    680 Ω EOL
    A
    B
    Keypad
    OR
    Peripheral
    GALAXY 44  V1.0
    09:51       01/08/04
    1
    2
    3A4
    5
    6B789ent
    *0#esc
    GALAXY 44  V1.0
    09:51       01/08/04
    1
    2
    3A4
    5
    6B789ent
    *0#esc 
    						
    							18
    Galaxy 2 Series Installation Manual
    RS485 Wiring Recommendations
    1. The system must be wired in a daisy-chain configuration. Spur and star configurations must not be used.
    2. The recommended cable used to connect the RS485 (AB) line is twisted pair screened cable (Belden
    8723 equivalent). However, for cable runs of less than 100m in normal environments, standard 4-core
    cable can normally be used.
    3. There must only be a single AB pair of wires in each of the cables.
    4. The power supply in the Galaxy 2 Series control panel and remote power supplies must not be connected
    in parallel.
    5. The 0V of all remote power supplies must be connected in common to the 0V of the Galaxy 2 Series
    control panel.
    6. Ensure that any extension loudspeakers are not wired in the same cable as an AB pair of wires.
    7. Where possible, ensure that the AB cable is at least 30 centimetres away from any other cables.
    8. Where possible, ensure that the AB  cable does not run parallel to other cables for extended
    distances (maximum five metres).
    9. The maximum length of cable run is one kilometre. If  two lines are connected, both ends must be terminated with 680 Ω resistors and the appropriate End OF
    Line (EOL)  resistor on the control panel PCB must be disconnected by removal of  link LK1.
    Figure 13. Twin AB Line Daisy-Chain Configuration
    RS485 Wiring
    Galaxy 2-44
    Control Panel
    A
    B
    680 Ω EOL
    A
    B
    GALAXY 2-44  V1.0
    09:51       01/08/04
    1
    2
    3A4
    5
    6B789ent
    *0#esc
    GALAXY 2-44  V1.0
    09:51       01/08/04
    1
    2
    3A4
    5
    6B789ent
    *0#esc
    Keypad
    OR
    Peripheral
    AB
    680 Ω EOL
    Keypad
    OR
    Peripheral
    Remove link LK1 
    						
    							19
    Galaxy 2 Series Installation Manual
    Figure 15. GSM Module fitted to underside of Galaxy 2-44 PCB
    Built-in Dialler/Modem
    The built-in dialler allows signalling to an Alarm Receiving Centre (ARC), SMS signalling and remote servicing
    from a PC.
    LED’S
    There are two LED’s on the Galaxy 2–44+  PCB. Pulsing of the red LED1 indicates an active telecommuni-
    cations. Illumination of the green LED2 indicates the presence of AC mains supply.
    There is one LED on the Galaxy 2–20 PCB. Pulsing of this LED indicates an active telecommunications.
    Audio Header (2–44+ Only)
    This is a 14-way shrouded header for audio connection. When an alarm is received at the ARC, the ARC can
    communicate through a loudspeaker at the premises, and ask for a password before authenticating the alarm.
    GSM Interface (2–44+ Only)
    This module provides a mobile telecommunications interface to provide an alternative to the land line. The
    GSM interface provides the same functionality as the built-in dialler/modem. The module  attaches to the
    underside of the PCB and also connects to the antenna on the edge of the enclosure box.
    ECP Bus (2–44+ Only)
    The ECP bus can operate at the same time as the RS485 bus. The cable can be standard 4-core and can be
    spurred or T wired.
    The maximum length of cable run is 100 metres.
    Figure 14. ECP Line - T Wire Configuration
    ECP Bus
    GSM
    Module
    Heatsink
    to antenna on
    enclosure box
    Galaxy 
    2-44 PCB
    (underside)
    Galaxy 2-44
    Control PanelKeypad
       OR
    PeripheralECP Bus 
    						
    							20
    Galaxy 2 Series Installation Manual
    Panel Mounting (Plastic Box)
    Installation Kit
    The Galaxy 2 Series plastic box comes with an installation kit. It contains 13 zone links, a cable clamp with
    two self tapping screws, two M4 x 20mm lid screws, a tamper spring, battery connector leads and 24,  1K
    resistors.
    WARNING:The lid of the plastic box must not be removed before isolating the mains supply.
    Illumination of the keypad power LED indicates the presence of a.c. mains supply.
    Removing the Enclosure Lid
    1. Remove the two M4 x 20 mm pan head screws  from the bottom corner of the lid.
    2. Pull the lid away from the lid hinge recesses (two menus of four) on the top of the enclosure base .
    3. Remove the lid.
    Installing the Enclosure Lid
    1. Hold the lid at an angle of 90 deg. to the enclosure base.
    2. Place the eight (two menus of four) lid hinges into the recesses on the top of the enclosure base.
    3. Swing the lid down making sure that the hinges fit into the holes in the top of the enclosure rim.
    4. Attach the lid in place with the two M4 x 20 mm pan head screws provided.
    Removing and Replacing the Galaxy 2 Series PCB
    NOTE:The plastic box comes with the PCB installed. The PCB must be removed to enable access to the
    keyhole mounting slot (see Figure 16).
    Figure 16. Galaxy 2 Series Plastic Box Layout
    Keyhole 
    Mounting 
    Slot
    PCB ClipPCB ClipPCB
    Lid Hinge 
    Recess
    Cable Entry
    PointsMains Terminal Block 
    with 200mA fuse 
    Secure Mains 
    Cable After Feeding  
    Through Entry Point
    User Instruction
    retaining Clip Lid Screw
    Lid Screw Mounting
    HoleMounting
    Hole Lid Hinge 
    Recess
    Transformer Output 
    Lead to PCB 
    Terminal Marked 
    Keyhole
    Mounting
    Slot
    Panel Mounting 
    						
    							21
    Galaxy 2 Series Installation Manual
    Remove the PCB
    1. Gently pull back the PCB mounting clips to free the PCB.
    2. Lift the PCB free of the PCB mounting pillars.
    Replace the PCB
    1. Insert the PCB into the PCB mounting slots.
    2. Ensure that any cabling is clear of the PCB support pillars.
    3. Gently pull back the PCB mounting clips and place the PCB on top of the PCB support pillars.
    4. Release the PCB mouting clips ensuring that they spring back into place and that the PCB is held firmly in
    place.
    Mounting the Plastic Enclosure Base
    Use the keyhole slot in the plastic box base to position the base. Three mounting screws (not provided) are
    required to mount the plastic box. Fix one of the screws into the mounting surface, this will be used for the
    top, keyhole mounting hole. Hang the enclosure base onto the mounting screw ensuring that the screw sits in
    the narrow portion of the keyhole.
    All cables must be brought into the enclosure base via the cable entry points shown in Figure 16. There are six
    cable entry holes for the entry of alarm cables. There is one a.c. mains cable entry point located below the
    mains terminal block.
    Fitting the Tamper Spring
    The Galaxy 2 Series plastic box enclosure is supplied without the tamper spring in place. The panel will not
    function without a Tamper. It is therefore the engineer’s responsibility to correctly attach the tamper spring.
    The spring  is supplied in the Installation Kit. The engineer must ensure the spring is securely attached to the
    Tamper Post (SW1). Refer to Figure 4.
    Panel Mounting (cont’d) 
    						
    							22
    Galaxy 2 Series Installation Manual
    Panel Mounting (Metal Box)
    Installation Kit
    The Galaxy 2 Series metal box comes with an installation kit. It contains two No.8 x 12 mm self-tapping lid
    screws, 6160 Text Programming Overlay, two battery leads (one red and one black), 10 mm cable staple and
    24,  1K resistors.
    WARNING:The lid of the metal box must not be removed before isolating the mains supply.
    Illumination of the keypad power LED indicated the presence of a.c. mains supply.
    Removing and Installing the Enclosure Lid
    1. Remove the two self-tapping screws that secures the lid to the enclosure base.
    2. Slide the lid forward on the locating slots then lift clear.
    3. To install the lid, simply reverse the process.
    NOTE:The top self-tapping screw activates the Lid Tamper Microswitch.
    Figure 17. Galaxy 2-20 Series Metal Box Layout
    Panel Mounting (cont’d)
    Enclosure
    Earth
    Connection
    Transformer
     
    
    
      
     
    Lid Tamper
    Microswitch
    Mains
    Terminal block
    with 200mA Fuse
    Mains Cable
    Entry Hole
    
    
    
    
    
    
    
    
    
    
    NOTE:Figure 17 shows the Galaxy 2-20 in the metal box. The procedure to remove and install the Galaxy
    2-44+ is identical to the 2-20. 
    						
    All Honeywell manuals Comments (0)

    Related Manuals for Honeywell Galaxy 2 User Manual