Page 41
Accenta/Optima Engineer’s Manual 37 3 = Inhibit Zones This is a zone which, on setting the panel, allows access to the entry/exit zone. However, if the panel is set and a time inhibited zone is triggered before an entry/exit timed zone then an alarm will be generated immediately. LCD Keypad: NOTE:Pressing the number toggles the zone ON or OFF While in Engineer program mode, to set up zones as inhibit, • Press [PROG] to give a choice of programs or press [up arrow] until P>Set Up Programs is displayed...
Page 42
Accenta/Optima Engineer’s Manual 38 Programs (cont’d) Immediate (Intruder) Zone This is a zone which will, when enabled as used and then activated, go into alarm when the panel is set. To assign a zone as immediate, remove the timed or timed inhibit function and make sure that it is enabled in the Used Zones section. 4 = Entry Time This is the time allowed to enter the premises via the entry route and unset the system. The programmable range is 00-99 seconds. The actual time is multiplied by 10. 00 = 5...
Page 43
Accenta/Optima Engineer’s Manual 39 5 = Exit Time This is the time allowed to leave the premises via the exit route before the system sets. The programmable range is 00-99 seconds. The actual time is multiplied by 10. If the Exit Time is interrupted within the last 10 seconds, then the Exit Time will restart at 10 seconds after the interruption has cleared. 00 = 5 seconds 01 = 10 seconds 03 = 30 seconds 99 = 990 seconds (16.5 minutes) The default is 30 seconds.[PROG] [4] P>Program Edit P>Program...
Page 44
Accenta/Optima Engineer’s Manual 40 6 = Exit Mode This program determines the way the panel functions during the exit time. There are four settings: 0 = Disabled A disabled program is not available for use and cannot be selected at setting time. Program 1 cannot be disabled. 1 = Timed A timed program will become Set as the Exit timer expires. 2 = Final Door A final door program will be set five seconds after a timed zone is closed if the rest of the zones are clear to set. NOTE:Final door programs must...
Page 45
Accenta/Optima Engineer’s Manual 41 LED Keypad: While in Engineer program mode, to set the Exit Mode , • Press [PROG] to give a choice of programs.LED’s 1, 2 and 3 areflashing. • Select program 1, 2 or 3. If program 2 is selected, LED 2 is ON. • Press [6] to enter into Exit Mode edit. The Exit Mode can now be changed. • Enter [0, 1, 2 or 3] for required Exit Mode. Appropriate LED is ON for selected mode (1 = disabled, 2 = timed, 3 = final door, 4 = silent timed) NOTE: Program Mode DISABLED is not...
Page 46
Accenta/Optima Engineer’s Manual 42 Operating System Operating the System This section gives a brief description of how to set and unset the system as well as how to reset after an alarm. For further information please refer to the Gen 4 Series User Guide. Setting the System LCD Keypad: • The system shows the day mode display. The system is unset. The Power and Day LED’s are ON. • Enter your 4-digit code (0123 default) and check that the system is clear (no zone indicators on). • The exit tone begins to...
Page 47
Accenta/Optima Engineer’s Manual 43 LCD Keypad: • Enter the premises by the agreed entry route. Thesystem produces an entry tone. The Power LED is ON and the Day LED is OFF indicating that the system is set. • Enter your 4-digit code (0123 default). • The system unsets with a double beep. The Day LED comes ON indicating that the system is unset. • After 30 seconds the Day Mode display appears. Resetting After an Alarm, Tamper or PA The system may be programmed to be reset by the user or the installer....
Page 48
Accenta/Optima Engineer’s Manual 44 Engineer Reset - LCD Keypad: After a tamper an engineer reset is required if the Engineer Reset flag is enabled. • Enter your user code [0123] default.When System is in Tamper the appropriate LED will be flashing. NOTE: Only the first event will cause the LED to flash. Subsequent events will have a steady ON condition. • Enter your 4-digit engineer code (9999 default). The Tamper LED goes OFF and the system resets • The system is in day mode. The Day LED is on. TA...
Page 49
Accenta/Optima Engineer’s Manual 45 Faults Fault conditions are often the result of minor installation errors. Whenever working close to the mains supply or connector, you should exercise extreme caution. Always isolate the mains supply before removing the control panel covers. Codes As supplied the default user code is 0123 and the engineer code is 9999. Both codes can revert back to default settings. See Defaulting Panel to Factory Settings and Defaulting User Code 1 and Engineer Code. Engineer Mode...
Page 50
Accenta/Optima Engineer’s Manual 46 Specifications Table 3. Specifications Specs 8 zones +ve loop, programmable function in each program Tamper -ve loop, internal sounders in Day - Full alarm in Set PA +ve loop, always active Exte rna l sire n (Be ll Bo x) o utp ut 1 2 V, a d justa b le time r (1 - 9 9 mins) o r c o ntinuo us Strobe output 12V latching External speaker 16 ohm (2 maximum) 260mA each Exit /Entry Timers seconds Programmable (05 - 990 seconds) Set output 0V in Day (sinking 400mA) 12V...