Accenta/Optima Engineer’s Manual
17
Entering/Exiting Engineer Program Mode
NOTE:The factory configured engineer’s access code is 9999. If however this code is changed then enter
the appropriate code.
Enter Your Code Enter Your CodeEnter Your Code Enter Your Code
Enter Your Code
0>Walk test 0>Walk test0>Walk test 0>Walk test
0>Walk testLCD Indications LED Indications
Press
To exit Engineer program mode press
Defaulting Panel to Factory Settings
CAUTION:All configurations of the panel are reset to factory...

Page 22

Accenta/Optima Engineer’s Manual
18
Menu Options
The full menu structure for the panel can only be accessed while in Engineer program mode. The structure is
shown in the following table:
Table 2.  Menu Options
Menu Options
MEN U  OPTION S
0 = Walk Test 7 = Timers
1 = Alarm Test 8 = Codes
2 = Test Outputs C = View Event Log
3 = System Flags O = Omit Allow & Double Knock
4 = Time and Date P = Set up Programs
6 = Zone Names
Enter Engineer program mode. Press [PROG] [9] [9] [9] [9].
0 = Walk Test
The walk...

Page 23

Accenta/Optima Engineer’s Manual
19
1 = Alarm Test
This function tests the alarm function of the Bell, Strobe or Sounder. Pressing the appropriate button
[1-3] toggles the function ON or OFF. Using the [up arrow] also selects the appropriate alarm function.
Pressing the [0] button turns all alarm outputs to OFF.
Pressing the [SET] button toggles the selected alarm output.
Pressing the [RESET] button turns off all outputs and leaves the function.
The outputs are:
1 = Bell, 2 = Strobe, 3 = Sounder
NOTE:To...

Page 24

Accenta/Optima Engineer’s Manual
20
2 = Test Outputs
NOTE:These tests are not applicable to Optima compact  panels.
This function tests all the outputs on the system.
The outputs are:1 = Fire, 2 = PA, 3 = Intruder, 4 = Set, 5 = Abort.
Pressing the [0] button turns all outputs to OFF.
Pressing the [SET] button toggles the selected alarm output.
Pressing the appropriate button [1-5] toggles the function ON or OFF.
Pressing the [RESET] button turns off all outputs and leaves the function.
LCD keypad:
•...

Page 25

Accenta/Optima Engineer’s Manual
21
Test Outputs
3 = Set Up System Flags
The System Flags are divided into Flags 1, 2 or 3.
LCD Keypad:
• Press [up arrow] to display menu Set Up System Flags.
• Press [3] or [SET] to display the next screen.
LED Keypad:
• Press [3].  LED’s 1, 2 and 3 are ON.
Flag 1
NOTE: Pressing the [9] button sets all flags ON. Pressing the
[0] button sets all flags OFF. Pressing the [RESET]
button leaves the function.
LCD Keypad:
• Press [1] to display first option of System Flag 1....

Page 26

Accenta/Optima Engineer’s Manual
22
System Flags
Flag 1 - Options
There are eight options under Flag1 which are described below:
1 = Silent PA
When this flag is set to ON, operating PA will cause a silent PA alarm. Pressing the [1] button toggles the flag
ON or OFF.
2 = RKP PA
When this flag is set to ON, the keypad PA buttons are enabled. Pressing the [2] button toggles the flag ON
or OFF.
3 = Engineer Reset
When this flag is set to ON, an engineer code must be entered to reset the system after Tamper,...

Page 27

Accenta/Optima Engineer’s Manual
23
Flag 2
NOTE:Pressing the [9] button sets all flags ON. Pressing the [0] button sets all flags OFF. Pressing the
[RESET] button leaves the function.
Accenta Optima Accenta OptimaAccenta Optima Accenta Optima
Accenta Optima
Version 1.00 Version 1.00Version 1.00 Version 1.00
Version 1.00F130-01-101 F130-01-101F130-01-101 F130-01-101
F130-01-101Build 101 (01)R Build 101 (01)RBuild 101 (01)R Build 101 (01)R
Build 101 (01)R
Date May 05 2006 Date May 05 2006Date May 05 2006...

Page 28

Accenta/Optima Engineer’s Manual
24
6 = Set Up Zone Names
This  option allows each of the eight zones to be given a name from the library (Appendix 2).
4 = Set Up Time and Date
LCD Keypad:
This option allows the Time or Date to be modified. Pushing button [4] selects the option and the first screen
appears as typically below:
Time and Date Time and DateTime and Date Time and Date
Time and Date
Time?  Time? Time?  Time? 
Time? 
1 11 1
1
3:46:17 3:46:173:46:17 3:46:17
3:46:17 The Time can be modified in...

Page 29

Accenta/Optima Engineer’s Manual
25
Timers
LCD keypad:
To change the Bell Time from 15 to 20 minutes:
•Press [up arrow] for menu Set Up Timers.
•Press [7] or [SET] for option 71 Set up Bell Time.
•Press [1] or [SET]. The Bell Time in minutes is displayed.
• The cursor is under the first digit. Select [2].
• The cursor moves to the second digit. Select [0].
• To accept the change press [SET] then [RESET]
OR to cancel the change press the [RESET] button twice.
7 = Set Up Timers
This option allows the Bell...

Page 30

Accenta/Optima Engineer’s Manual
26
Timers (cont’d)
LCD keypad:
 To change the Bell Delay time from 00 to 12 minutes:
•Press [up arrow] for menu Set Up Timers.
•Press [7]or [SET]. Option 1 Set up Bell Time appears.
•Press [2]. The Bell Delay time in minutes is displayed.
• The cursor is under the first digit. Select [1].
• The cursor moves to the second digit. Select [2].
• To accept the change press [SET] then [RESET]
OR to cancel the change press the [RESET] button twice.
72 = Set Up Bell Delay
This...