Page 71
CHAPTER 4: SOFTWARE PQMII POWER QUALITY METER – INSTRUCTION MANUAL4–11 4.4 Using the EnerVista PQMII Setup Software 4.4.1 Entering Setpoints The System Setup page will be used as an example to illustrate the entering of setpoints. Select the Setpoint > System Setup menu item. The following window will appear: When a non-numeric setpoint such as CT WIRING is selected, EnerVista PQMII Setup Software displays a drop-down menu: When a numeric setpoint such as PHASE CT PRIMARY is selected, EnerVista...
Page 72
4–12PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 4: SOFTWARE 4.4.2 Viewing Actual Values If a PQMII is connected to a computer via the serial port , any measured value, status and alarm information can be displayed. Use the Actual pull-down menu to select various measured value screens. Monitored values will be displayed and continuously updated. 4.4.3 Setpoint Files To print and save all the setpoints to a f ile follow the steps outlined in 4.3.2: Saving Setpoints to a File. To load an...
Page 73
CHAPTER 4: SOFTWARE PQMII POWER QUALITY METER – INSTRUCTION MANUAL4–13 4.5 Power Analysis 4.5.1 Waveform Capture Two cycles (64 samples/cycle) of voltage and current waveforms can be captured and displayed on a PC using the EnerVista PQMII Setup Software or third party software. Distorted peaks or notches from SCR switching provides clues for taking corrective action. Waveform capture is also a useful tool when investigating possible wiring problems due to its ability to display the phase...
Page 74
4–14PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 4: SOFTWARE parameter. EnerVista PQMII Setup Software then takes this data and performs a FFT (Fast Fourier Transform) to extract the harmonic information. The harmonic analysis feature is implemented into EnerVista PQMII Setup Software as shown below. Select the Actual > Power Analysis > Harmonic Analysis > Harmonic Spectrum menu item. The EnerVista PQMII Setup Software can display the Harmonic Analysis Spectrum window including the...
Page 75
CHAPTER 4: SOFTWARE PQMII POWER QUALITY METER – INSTRUCTION MANUAL4–15 running total of all valid Trace Memory Triggers from the last time power was applied to the PQMII. The Total Trace Triggers counter will rollover to 0 at 65536. The trace memory feature is implemented into the EnerVista PQMII Setup Software as shown below. Select the Setpoint > PQMII Setup > Trace Memory Setup menu item to setup the trace memory feature. The Trace Memory Usage parameter is set as follows: • 1 x 36 cycles: upon...
Page 76
4–16PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 4: SOFTWARE Select the Actual > Power Analysis > Trace Memory menu item to view the trace memory data. This launches the Trace Memory Waveform window. 4.5.4 Data Logger The data logger feature allows the PQMII to continuously log various specif ied parameters at the specif ied rate. The data logger uses the 64 samples/cycle data. This feature is implemented into EnerVista PQMII Setup Software as shown below. Select the Setpoint > System...
Page 77
CHAPTER 4: SOFTWARE PQMII POWER QUALITY METER – INSTRUCTION MANUAL4–17 FIGURE 4–4: Data Logger Setup Window 1. The Log 1(2) Mode parameters are set as follows: • “Run to Fill”: when the data logger is full (100%) it will stop logging • “Circulate”: when the data logger is full, it will start from the beginning and overwrite the previous data. 2. The Log 1(2) Interval parameters determine how frequently the PQMII logs each piece of data. 3. The total log size is approximately 192KB. The allotment of...
Page 78
4–18PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 4: SOFTWARE FIGURE 4–5: Data Logger Window 5. The Data Log 1(2) dialog box displays the record numbers, data log start time, the current time, and parameter values for the current cursor line position. 4.5.5 Voltage Disturbance Recorder The Voltage Disturbance Recorder allows the PQMII to monitor and record sag and swell disturbances. This function can record up to 500 sag/swell events for all voltages simultaneously. The events roll-over and...
Page 79
CHAPTER 4: SOFTWARE PQMII POWER QUALITY METER – INSTRUCTION MANUAL4–19 Select the Actual > Power Analysis > Voltage Disturbance Recorder menu item to view the voltage disturbance recorder events. Within the voltage disturbance recorder window, each event is listed and can be selected. When the event is selected the following values are displayed: •Dist . Number: The event number. The f irst event recorded (after the event recorder is cleared) will be given the event number of “1”. Each subsequent...
Page 80
4–20PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 4: SOFTWARE FIGURE 4–6: Voltage Disturbance Recorder