Page 31
PQMII POWER QUALITY METER – INSTRUCTION MANUAL2–1 PQMII Power Quality Meter Chapter 2: Installation Digital Energy In stal lation 2.1 Physical Conf iguration 2.1.1 Mounting Physical dimensions and required cutout dimensions for the PQMII are shown below. Once the cutout and mounting holes are made in the panel, use the eight #6 self-tapping screws provided to secure the PQMII. Mount the unit on a panel or switchgear door to allow operator access to the keypad and indicators. FIGURE 2–1: Physical...
Page 32
2–2PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 2: INSTALLATION 2.1.2 Product Identif ication Product attributes vary according to the conf iguration and options selected on the customer order. Before applying power to the PQMII, examine the label on the back and ensure the correct options are installed. The following section explains the information included on the label shown below: FIGURE 2–2: Product Label •Model No: Shows the PQMII conf iguration. The model number for a basic panel...
Page 33
CHAPTER 2: INSTALLATION PQMII POWER QUALITY METER – INSTRUCTION MANUAL2–3 2.2 Electrical Conf iguration 2.2.1 External Connections Signal wiring is to Terminals 21 to 51. These terminals accommodate wires sizes up to 12 gauge. Please note that the maximum torque that can be applied to terminals 21 to 51 is 0.5 Nm (or 4.4 in ·lb.). CT, VT, and control power connections are made using Terminals 1 to 20. These #8 screw ring terminals accept wire sizes as large as 8 gauge. Consult the wiring diagrams...
Page 34
2–4PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 2: INSTALLATION Signal Upper Row (21 to 51)47 Comm 1 – 21 Analog shield 48 Comm 1 + 22 Analog in – 49 Comm 2 COM 23 Analog in + 50 Comm 2 – 24 Analog out com 51 Comm 2 + Table 2–1: PQMII External Connections Terminal Description Terminal Description
Page 35
CHAPTER 2: INSTALLATION PQMII POWER QUALITY METER – INSTRUCTION MANUAL2–5 2.2.2 Wiring Diagrams This wiring diagram below shows the typical 4-wire wye connection which will cover any voltage range. Select the S2 SYSTEM SETUP CURRENT/VOLTAGE CONFIGURATION VT WIRING: “4 Wire Wye (3 VTs)” setpoint . FIGURE 2–3: Wiring Diagram 4-wire Wye (3 VTs)
Page 36
2–6PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 2: INSTALLATION The 2½ element 4-wire wye connection can be used for situations where cost or size restrictions limit the number of VTs to two. With this connection, Phase Vbn voltage is calculated using the two existing voltages. Select the S2 SYSTEM SETUP CURRENT/VOLTAGE CONFIGURATION VT WIRING: “4 WIRE WYE (2 VTs)” setpoint . This wiring conf iguration will only provide accurate power measurements if the voltages are balanced.
Page 37
CHAPTER 2: INSTALLATION PQMII POWER QUALITY METER – INSTRUCTION MANUAL2–7 FIGURE 2–4: Wiring Diagram 4-wire Wye (2 VTs) Four-wire systems with voltages 347 V L-N or less can be directly connected to the PQMII without VTs. Select the S2 SYSTEM SETUP CURRENT/VOLTAGE CONFIGURATION VT WIRING: “4 WIRE WYE DIRECT” setpoint .
Page 38
2–8PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 2: INSTALLATION The PQMII voltage inputs should be directly connected using HRC fuses rated at 2 A to ensure adequate interrupting capacity. FIGURE 2–5: Wiring Diagram 4-wire Wye Direct (No VTs)
Page 39
CHAPTER 2: INSTALLATION PQMII POWER QUALITY METER – INSTRUCTION MANUAL2–9 This diagram shows the typical 3-wire delta connection which will cover any voltage range. Select the S2 SYSTEM SETUP CURRENT/VOLTAGE CONFIGURATION VT WIRING: “3 WIRE DELTA (2 VTs)” setpoint . FIGURE 2–6: Wiring Diagram 3-wire Delta (2 VTs)
Page 40
2–10PQMII POWER QUALITY METER – INSTRUCTION MANUAL CHAPTER 2: INSTALLATION Three-wire systems with voltages 600 V (L-L) or less can be directly connected to the PQMII without VTs. Select the S2 SYSTEM SETUP CURRENT/VOLTAGE CONFIGURATION VT WIRING: “3 WIRE DIRECT” setpoint . The PQMII voltage inputs should be directly connected using HRC fuses rated at 2 amps to ensure adequate interrupting capacity. FIGURE 2–7: Wiring Diagram 3-wire Direct (No VTs)