GE Security g LOCATION 106 - PARTITION 7 ENTRY EXIT TIMERS (6 segments, numerical data) Location 106 is used to enter the entry and exit times in seconds. There are 2 separate entry and exit times. Valid entries are 10-255 seconds. If all the segments are “0”, the entry and exit times for partition 1 will be used. Segment 1 Entry time 1 Entry time that will be used when a delay 1 zone type initiates an entry delay Segment 2 Entry time 2 Exit time that will be used for all zones designated as delay 1 Segment 3 Entry time 3 Entry time that will be used when a delay 2 zone type initiates an entry delay Segment 4 Entry time 4 Exit time that will be used for all zones designated as delay 2 Segment 5 Reserved Segment 6 Reserved LOCATION 107 - ACCOUNT CODE FOR PARTITION 8 (6 segments, numerical data) The account code that is sent when reporting partition 8 is programmed in location 107. If location 107 is left unprogrammed (all “10”) then the account code corresponding to the phone number that is dialled will be used. If the account code is less than six digits, program a “10” in the segment immediately after the last digit of the account code. If the account code is 6 digits long, program all 6 segments. LOCATION 108 - PARTITION 8 FEATURE AND REPORTING SELECTIONS (5 segments, feature selection data) Location 108 is used to enable certain features that the user can access or see from the keypad of the system. In addition, certain communicator reports are enabled in this location. Each of these features can be enabled by partition. This location contains 5 segments, with eight possible features per segment. Refer to location 23 for the feature selections. If all the segments are blank (nothing enabled), the features for partition 1 will be used. LOCATION 109 - PARTITION 8 ENTRY EXIT TIMERS (6 segments, numerical data) Location 109 is used to enter the entry and exit times in seconds. There are 2 separate entry and exit times. Valid entries are 10-255 seconds. If all the segments are “0”, the entry and exit times for partition 1 will be used. Segment 1 Entry time 1 Entry time that will be used when a delay 1 zone type initiates an entry delay Segment 2 Entry time 2 Exit time that will be used for all zones designated as delay 1 Segment 3 Entry time 3 Entry time that will be used when a delay 2 zone type initiates an entry delay Segment 4 Entry time 4 Exit time that will be used for all zones designated as delay 2 Segment 5 Reserved Segment 6 Reserved NX-8E Installation manual Page 71 Date 08/09/04
GE Security g Programming zone configuration groups LOCATIONS 110-169 ARE USED TO CHANGE THE ZONE CONFIGURATIONS AS LISTED IN THE TABLE ON PAGES 44-46. THESE LOCATIONS ARE CONSIDERED AS ADVANCED PROGRAMMING, AND THEY SHOULD ONLY BE CHANGED IF YOU HAVE A THOROUGH UNDERSTANDING OF THE OPERATION OF EACH BIT. LOCATION 110 - CONFIGURATION GROUP 1 ALARM EVENT CODE (1 segment, numerical data) Location 110 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 111 - CONFIGURATION GROUP 1 CHARACTERISTIC SELECT (5 segments, feature selection data) Segment 1 1 = Fire (turn on if this is a fire zone) 2 = 24 hour (turn on for non-fire 24 hour zones) 3 = Keyswitch zone (normally open switch) 4 = Follower (turn on for burglary zones that are Instant during non- entry times) 5 = Delay 1 zone (follows timer 1 Entry and Exit times) 6 = Delay 2 zone (follows timer 2 Entry and Exit times) 7 = Interior (turn on if this zone should Automatically Bypass or Bypass for Stay Arming) 8 = Local only (turn on if this zone should not be reported) Remark: for a maintained keyswitch (ON/OFF), program both “keyswitch” and “local” Segment 2 1 = On: if configuration group will beep the keypad for alarm 2 = On: if configuration group will sound the yelping siren for alarm 3 = On: if configuration group will sound the steady siren for alarm 4 = On: if configuration group will chime 5 = On: if configuration group can be bypassed 6 = On: if configuration group is included in the group shunt 7 = On: if configuration group is force armable 8 = On: if configuration group is entry guard Segment 3 1 = On: enables Fast Loop Response. (50mS) - Off= 500mS 2 = On: enables Double End Of Line Tamper zone. (Mainly used for tamper on wireless zones) 3 = On: enables Trouble Reporting zone. (Day zone and Fire zones) 4 = On: if configuration group is a Cross Zone 5 = On: enables Dialler Delay zone. (See location 40) 6 = On: if configuration group will use swinger shutdown. (See location 38) 7 = On: enables Restore reporting 8 = On: enables Listen-In. (See location 40) NX-8E Installation manual Page 72 Date 08/09/04
GE Security g Segment 4 1 = On: enables zone activity monitor 2 = On: enables end of line resistor defeat on non-fire/non-keyswitch zones 3 = On : enables zone to act as request to exit input / diables for alarm activation 4 = On : enables zone to act as access control zone (Door Shunt) 5 = Reserved 6 = Reserved 7 = Reserved 8 = Reserved Segment 5 1-8 Reserved LOCATION 112 - CONFIGURATION GROUP 2 ALARM EVENT CODE (1 segment, numerical data) Location 112 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 113 - CONFIGURATION GROUP 2 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 114 - CONFIGURATION GROUP 3 ALARM EVENT CODE (1 segment, numerical data) Location 114 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 115 - CONFIGURATION GROUP 3 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 116 - CONFIGURATION GROUP 4 ALARM EVENT CODE (1 segment, numerical data) Location 116 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). NX-8E Installation manual Page 73 Date 08/09/04
GE Security g LOCATION 117 - CONFIGURATION GROUP 4 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 118 - CONFIGURATION GROUP 5 ALARM EVENT CODE (1 segment, numerical data) Location 118 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 119 - CONFIGURATION GROUP 5 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 120 - CONFIGURATION GROUP 6 ALARM EVENT CODE (1 segment, numerical data) Location 120 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 121 - CONFIGURATION GROUP 6 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 122 - CONFIGURATION GROUP 7 ALARM EVENT CODE (1 segment, numerical data) Location 122 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on page 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 123 - CONFIGURATION GROUP 7 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. NX-8E Installation manual Page 74 Date 08/09/04
GE Security g LOCATION 124 - CONFIGURATION GROUP 8 ALARM EVENT CODE (1 segment, numerical data) Location 124 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 125 - CONFIGURATION GROUP 8 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 126 - CONFIGURATION GROUP 9 ALARM EVENT CODE (1 segment, numerical data) Location 126 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 127 - CONFIGURATION GROUP 9 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 128 - CONFIGURATION GROUP 10 ALARM EVENT CODE (1 segment, numerical data) Location 128 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 129 - CONFIGURATION GROUP 10 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 130 - CONFIGURATION GROUP 11 ALARM EVENT CODE (1 segment, numerical data) Location 130 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). NX-8E Installation manual Page 75 Date 08/09/04
GE Security g LOCATION 131 - CONFIGURATION GROUP 11 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 132 - CONFIGURATION GROUP 12 ALARM EVENT CODE (1 segment, numerical data) Location 132 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 133 - CONFIGURATION GROUP 12 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 134 - CONFIGURATION GROUP 13 ALARM EVENT CODE (1 segment, numerical data) Location 134 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 135 - CONFIGURATION GROUP 13 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 136 - CONFIGURATION GROUP 14 ALARM EVENT CODE (1 segment, numerical data) Location 136 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 137 - CONFIGURATION GROUP 14 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. NX-8E Installation manual Page 76 Date 08/09/04
GE Security g LOCATION 138 - CONFIGURATION GROUP 15 ALARM EVENT CODE (1 segment, numerical data) Location 138 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 139 - CONFIGURATION GROUP 15 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 140 - CONFIGURATION GROUP 16 ALARM EVENT CODE (1 segment, numerical data) Location 140 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 141 - CONFIGURATION GROUP 16 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 142 - CONFIGURATION GROUP 17 ALARM EVENT CODE (1 segment, numerical data) Location 142 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 143 - CONFIGURATION GROUP 17 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 144 - CONFIGURATION GROUP 18 ALARM EVENT CODE (1 segment, numerical data) Location 144 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). NX-8E Installation manual Page 77 Date 08/09/04
GE Security g LOCATION 145 - CONFIGURATION GROUP 18 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 146 - CONFIGURATION GROUP 19 ALARM EVENT CODE (1 segment, numerical data) Location 146 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 147 - CONFIGURATION GROUP 19 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 148 - CONFIGURATION GROUP 20 ALARM EVENT CODE (1 segment, numerical data) Location 148 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 149 - CONFIGURATION GROUP 20 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 150 - CONFIGURATION GROUP 21 ALARM EVENT CODE (1 segment, numerical data) Location 150 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 151 - CONFIGURATION GROUP 21 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. NX-8E Installation manual Page 78 Date 08/09/04
GE Security g LOCATION 152 - CONFIGURATION GROUP 22 ALARM EVENT CODE (1 segment, numerical data) Location 152 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 153 - CONFIGURATION GROUP 22 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 154 - CONFIGURATION GROUP 23 ALARM EVENT CODE (1 segment, numerical data) Location 154 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 155 - CONFIGURATION GROUP 23 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 156 - CONFIGURATION GROUP 24 ALARM EVENT CODE (1 segment, numerical data) Location 156 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 157 - CONFIGURATION GROUP 24 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 158 - CONFIGURATION GROUP 25 ALARM EVENT CODE (1 segment, numerical data) Location 158 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). NX-8E Installation manual Page 79 Date 08/09/04
GE Security g LOCATION 159 - CONFIGURATION GROUP 25 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 160 - CONFIGURATION GROUP 26 ALARM EVENT CODE (1 segment, numerical data) Location 160 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 161 - CONFIGURATION GROUP 26 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 162 - CONFIGURATION GROUP 27 ALARM EVENT CODE (1 segment, numerical data) Location 162 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 163 - CONFIGURATION GROUP 27 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. LOCATION 164 - CONFIGURATION GROUP 28 ALARM EVENT CODE (1 segment, numerical data) Location 164 contains the event code that is sent for a Contact ID or SIA report. The desired event code should be chosen from the list on pages 121-122. The zone ID will be the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain the alarm report code for the Robofon format (value 00-99). LOCATION 165 - CONFIGURATION GROUP 28 CHARACTERISTIC SELECT (5 segments, feature selection data) Use the “Configuration Group Characteristic Selections” described in Location 111. NX-8E Installation manual Page 80 Date 08/09/04