    THE NUMBER IN PARENTHESES FOLLOWING THE EVENT IS THE NUMBER THAT WILL BE 
    REPORTED AS THE ZONE NUMBER. IF THERE ARE NO PARENTHESES, THE ZONE WILL BE “0”. SEE 
    APPENDIX 3 FOR THE DEVICE NUMBERS. 
    * The character transmitted in this slot will be the first character from the event code of the zone that is 
    bypassed or in trouble (see locations 110 - 169). 
    NX-8E Installation manual Page 121 Date 08/09/04  
    						
    							
             
     
    GE Security g 
     
    APPENDIX 2: REPORTING ZONE CODES IN SIA OR 
    CONTACT ID   
     
    The NX-8E has the ability to report SIA level 1 transmissions to either or both phone numbers. Each report in 
    SIA consists of an Event Code and a Zone or User ID. The Zone ID will be the zone number that is in alarm. 
    The event code will come from the chart below, and it will be programmed in the configuration group event 
    code. 
    Programmed Event Code SIA Code Description 
    0 HA Holdup Alarm 
    1 FA Fire Alarm 
    2 PA Panic alarm 
    3 BA Burglary Alarm 
    4 BA Burglary Alarm 
    5 BA Burglary Alarm 
    6 UA Untyped Alarm 
    7 BA Burglary Alarm 
    8 BA Burglary Alarm 
    9 UA Untyped Alarm 
    10 HA Holdup Alarm 
    11 MA Medical Alarm 
    12 PA Panic alarm 
    13 TA Tamper Alarm 
    14 RP Periodic Test 
    15 GA Gas Alarm 
    16 KA Heat Alarm 
    17 WA Water Alarm 
    18 QA Emergency Alarm 
    19 SA Sprinkler Alarm 
    20 ZA Freeze Alarm 
     
    NX-8E Installation manual Page 122 Date 08/09/04  
    						
    							
             
     
    GE Security g 
     
     
    The NX-8E can report Ademco Contact ID transmissions. Each report in Contact ID consists of an Event 
    Code and a Zone ID. The zone ID is the zone that generated the alarm. The event code will come from the 
    chart below, and it will be programmed in the configuration group event code. 
    Programmed Event Code CONTACT-ID Description 
    0 122 Silent Panic 
    1 110 Fire Alarm 
    2 120 Panic alarm 
    3 130 Burglary Alarm 
    4 131 Perimeter Alarm 
    5 132 Interior Alarm 
    6 133 24 Hour Burglary 
    7 134 Entry Alarm 
    8 135 Day/Night Alarm 
    9 150 Non Burglary 24 Hour 
    10 121 Duress Alarm 
    11 100 Medical Alarm 
    12 123 Audible Panic Alarm 
    13 137 Tamper Alarm 
    14 602 Periodic Test 
    15 151 Gas Detected 
    16 158 High Temp 
    17 154 Water Leakage 
    18 140 General Alarm 
    19 140 General Alarm 
    20 159 Low Temp 
    21 158 High Temp Alarm 
    22 115 Manual Fire Alarm 
     
     
     
     
     
    NX-8E Installation manual Page 123 Date 08/09/04  
    						
    							
             
     
    GE Security g 
     
    APPENDIX 3: EXPANDER NUMBERS FOR REPORTING 
    EXPANDER TROUBLE 
    The tables below list the device numbers that will be reported for each expander/keypad where a trouble 
    condition is present. For trouble conditions relating to the control panel, the device number is “0”. 
     
    Keypads 
    KEYPAD PART 1 PART 2 PART 3 PART 4 PART 5 PART 6 PART 7 PART 8 
    1 192 193 194 195 196 197 198 199 
    2 200 201 202 203 204 205 206 207 
    3 208 209 210 211 212 213 214 215 
    4 216 217 218 219 220 221 222 223 
    5 224 225 226 227 228 229 230 231 
    6 232 233 234 235 236 237 238 239 
    7 240 241 242 243 244 245 246 247 
    8 248 249 250 251 252 253 254 255 
     
    Remote power supply NX-320E  
    Power supply DIP 1 DIP 2 DIP 3 Expander number 
    reported 
    1 OFF OFF OFF 84 
    2 ON 85 OFF OFF 
    3 OFF ON OFF 86 
    4 ON ON OFF 87 
    5 OFF OFF ON 88 
    6 ON OFF ON 89 
    7 OFF ON ON 90 
    8 ON ON ON 91 
     
    Wireless receiver NX-448E  
    Wireless receiver DIP 1 DIP 2 DIP 3 Expander number 
    reported 
    1 OFF 35 OFF OFF 
    2 ON OFF OFF 36 
    3 OFF ON OFF 37 
    4 ON ON OFF 38 
    5 OFF OFF ON 39 
    6 ON OFF ON 32 
    7 OFF ON ON 33 
    8 ON ON ON 34 
     
    NX-8E Installation manual Page 124 Date 08/09/04  
    						
    							
             
     
    GE Security g 
    Output module NX-507E or NX-508E 
    Output module DIP 1 DIP 2 DIP 3 Expander number 
    reported 
    1 ON ON OFF 24 
    2 OFF OFF ON 25 
    3 ON OFF ON 26 
    4 OFF ON ON 27 
    5 ON ON ON 28 
    6 OFF OFF OFF 29 
    7 ON OFF OFF 30 
    8 OFF ON OFF 31 
     
     
    Hardwired expander NX-216E 
    Starting zone 
    number 
    DIP 1 DIP 2 DIP 3 DIP 4 DIP 5 DIP 6 Expander number 
    reported 
    Zone 9 ON OFF OFF OFF OFF N/A 23 
    Zone 17 OFF ON OFF OFF OFF N/A 16 
    Zone 25 ON ON OFF OFF OFF N/A 17 
    Zone 33 OFF OFF ON OFF OFF N/A 18 
    Zone 41 ON OFF ON OFF OFF N/A 19 
    Zone 49 ON 20 OFF ON OFF OFF N/A 
    Zone 57 ON ON ON OFF OFF N/A 21 
    Zone 65 OFF OFF OFF ON OFF N/A 96 
    Zone 73 ON OFF OFF 97 ON OFF N/A 
    Zone 81 OFF ON OFF OFF ON N/A 98 
    Zone 89 ON ON OFF ON OFF N/A 99 
    Zone 97 OFF OFF ON ON OFF N/A 100 
    Zone 105 ON OFF N/A ON ON OFF 101 
    Zone 113 ON OFF ON ON OFF N/A 102 
    Zone 121 ON ON ON ON OFF N/A 103 
    Zone 129 OFF OFF OFF OFF ON N/A 104 
    Zone 137 ON ON OFF OFF OFF N/A 105 
    Zone 145 OFF ON OFF OFF ON N/A 106 
    Zone 153 ON ON OFF OFF ON N/A 107 
    Zone 161 OFF ON OFF ON OFF N/A 108 
    Zone 169 ON OFF ON OFF ON N/A 109 
    Zone 177 OFF ON ON OFF ON N/A 110 
    Zone 185 ON ON N/A ON OFF ON 111 
     
    NX-8E Installation manual Page 125 Date 08/09/04  
    						
    							
             
     
    GE Security g 
      
    Security g 
    CE DECLARATION 
    NX-8E Installation manual Page 126 Date 08/09/04  
    						
    							
             
     
    GE Security g 
     
     
    NX-8E Installation manual Page 127 Date 08/09/04  
    						
    							
             
     
    GE Security g 
     
     
     
    NX-8E Installation manual Page 128 Date 08/09/04  
    						
    							
             
    NX-8E Installation manual Page 129 Date 08/09/04 
     
    GE Security g  
    						
    							
     
     
     
     
     
     
    www.gesecurity.com
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
      
     
    EMEA Distribution is a division of GE Security EMEA bvba 
     
    COPYRIGHT ©2004 
     
    © GE Security EMEA bvba.  All rights reserved. GE Security EMEA bvba grants the right to reprint this 
    manual for internal use only. GE Security EMEA bvba reserves the right to change information without 
    notice. 
      
    						
    All GE manuals Comments (0)