A-33 Catalyst 4500 E-Series Switches Installation Guide OL-13972-02 Appendix A Power Supply Specifications 4200 W AC-Input Power Supply Ta b l e A - 2 7 shows the maximum output wattage with two 4200 W AC-input power supplies operating in combined mode. 4200 W Power Supply AC Power Cords Ta b l e A - 2 8 lists the specifications for the AC power cords that are available for the 4200 W AC-input power supply. NoteAll 4200 W power supply power cords have an IEC60320/C19 appliance plug at one end. Table A-26 Redundant Mode Output Source AC to Power Supplies +12 VDC +3.3 VDC –50 VDC Total (W) 110 VAC to one input on supply 1 and one 100 VAC to one input on power supply 2660 W 40 W 700 W 1050 W 110 VAC to both inputs on power supply 1 and 110 VAC to both inputs on power supply 2, or one 220 VAC input to power supply 1 and one 220 VAC input to power supply 21360 W 40 W 1850 W 2100 W 220 VAC to both inputs on power supply 1 and power supply 21360 W 40 W 3700 W 4200 W Table A-27 4200 W Power Supplies in Combined Mode Output Source AC to Power Supplies W @ +12 VDCW @ +3.3 VDCW @ –50 VDCMaximum (W) Both power supplies with one input at 110 VAC 1200 W 40 W 1320 W 1870 W One 110 VAC input to one power supply and two 110 VAC inputs to the other power supply1800 W 40 W 2000 W 2730 W Both power supplies with two 110 VAC inputs2200 W 40 W 3100 W 3800 W Both power supplies with one 220 VAC input 2200 W 40 W 3100 W 3800 W Two 220 VAC inputs to one power supply, one 220 VAC input to the other power supply2200 W 40 W 4700 W 5500 W Both power supplies with two 220 VAC inputs2200 W 40 W 6200 W 7600 W
A-34 Catalyst 4500 E-Series Switches Installation Guide OL-13972-02 Appendix A Power Supply Specifications 4200 W AC-Input Power Supply Table A-28 4200 W AC-Input Power Supply Power Cords LocalePower Cord Part Number Length Cordset RatingAC Source Plug Ty p e Japan, North America 120 VAC operationCAB-US515P-C19-US 9.8 ft (2.98 m)15 A, 125 VAC NEMA 5-15P Japan, North America (locking) 200–240 VAC operationCAB-L620P-C19-US 14 ft (4.2 m) 20 A, 250 VAC NEMA L6-20 Japan, North America (nonlocking) 200–240 VAC operationCAB-US620P-C19-US 13.2 ft (4.02 m)20 A, 250 VAC NEMA 6-20 non-locking Europe CAB-CEE77-C19-EU 13.2 ft (4.0 m)15 A, 250 VAC CEE 7/7 International (including Argentina and South Africa)CAB-I309-C19-INT 13.6 ft (4.1 m)16 A, 250 VAC IEC 309 Australia CAB-A3112-C19-AUS 14 ft (4.3 m) 15 A, 250 VAC AS/NZZS 3112 Argentina CAB-IR2073-C19-AR= (was CAB-7513ACR=)14 ft (4.3 m) 10 A, 250 VAC IRAM 2073 Italy CAB-C2316-C19-IT 14 ft (4.3 m) 16 A, 250 VAC CEI 23-16 120354 120361 120355 120357 120360 120356 120356 120358
A-35 Catalyst 4500 E-Series Switches Installation Guide OL-13972-02 Appendix A Power Supply Specifications 6000 W AC-Input Power Supply 6000 W AC-Input Power Supply The 6000 W AC-input power supply (PWR-C45-6000ACV), shown in Figure A-8, is supported in following Catalyst 4500 E-series switch chassis: •Catalyst 4503-E •Catalyst 4506-E •Catalyst 4507R-E •Catalyst 4510R-E •Catalyst 4507R+E •Catalyst 4510R+E United KingdomCAB-BS1363-C19-UK 14 ft (4.3 m) 13 A, 250 VAC BS 1363 Israeli CAB-S132-C19-ISRL 14 ft (4.3 m) 16 A, 250 VAC SI32 UPS 220V CAB-C19-CBN 9 ft (2.74 m) 20 A, 250 VAC IEC-60320-C20 Table A-28 4200 W AC-Input Power Supply Power Cords (continued) LocalePower Cord Part Number Length Cordset RatingAC Source Plug Ty p e 120359 130922 130923
A-36 Catalyst 4500 E-Series Switches Installation Guide OL-13972-02 Appendix A Power Supply Specifications 6000 W AC-Input Power Supply Figure A-8 6000 W Dual-Input AC Power Supply 6000 W Power Supply Specifications Ta b l e A - 2 9 lists the specifications for the 6000 W AC-input power supplies. 1AC-input 2 receptacle4AC-input 1 receptacle 2AC-input 2 on switch5Captive screws 3AC-input 1 on switch6Remote power cycling terminal 274931 5 4 2 1 3 6 Table A-29 6000 W AC-Input Power Supply Specifications Item Specification AC-input type Autoranging inputs with power factor correction NotePower factor correction is a standard feature on all Catalyst 4500 E-series AC-input power supplies. PFC reduces the reactive component in the source AC current allowing higher power factors (typically 99 percent or better) and lower harmonic current components. AC-input voltage •Low-line (120 VAC nominal)—85 VAC (min) to 132 VAC (max) •High-line (230 VAC nominal)—170 VAC (min) to 264 VAC (max) AC-input current •12 A (max) @ 120 VAC (for each input) •16 A (max) @ 230 VAC (for each input) AC-input frequency 50/60 Hz (nominal) (±3% for full range)
A-37 Catalyst 4500 E-Series Switches Installation Guide OL-13972-02 Appendix A Power Supply Specifications 6000 W AC-Input Power Supply Ta b l e A - 3 0 list the 6000 W AC-input power supply LEDs and their meanings. Power supply output Total output depends on the number of inputs connected and the source AC voltage. If two inputs are used, they should both be of the same AC voltage. •1050 W operation (with one 120 VAC nominal input) –70.8 A @ 12 VDC (data only) –12.5 A @ 3.3 VDC (data only) –18.4 A @ –50 VDC (PoE if used) •2100 W operation (with two 120 VAC nominal inputs) –141.6 A @ 12 VDC (data only) –12.5 A @ 3.3 VDC (data only) –37.0 A @ –50 VDC (PoE if used) •3000 W operation (with one 230 VAC nominal input) –183.3 A @ 12 VDC (data only) –12.5 A @ 3.3 VDC (data only) –48 A @ –50 VDC (PoE if used) •6000 W operation (with two 230 VAC nominal inputs) –183.3 A @ 12 VDC (data only) –12.5 A @ 3.3 VDC (data only) –96 A @ –50 VDC (PoE if used) Power supply output capacity6000 W maximum Output holdup time 20 ms minimum kVA rating 16.8 kVA (power factor = 0.99) Heat dissipation 2,720 BTUs/hr (approx.) Minimum software requirement Cisco IOS Release 12.2(52)SG Power over Ethernet Supported, up to 4800 W 1. The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch. Table A-29 6000 W AC-Input Power Supply Specifications Item Specification
A-38 Catalyst 4500 E-Series Switches Installation Guide OL-13972-02 Appendix A Power Supply Specifications 6000 W AC-Input Power Supply NoteThe 6000 W AC-input power supply should not be used in mixed-voltage configurations. All the inputs in a chassis must be at the same voltage (110 VAC or 220 VAC). Ta b l e A - 3 1 shows the wattage output possible from a 6000 W AC-input power supply in redundant mode. In redundant mode, two power supplies must have identical inputs and all inputs must be at the same voltage. If the input voltages are mismatched, choose the value matching the weaker of the two power supplies. Ta b l e A - 3 2 shows the maximum output wattage with two 6000 W AC-input power supplies in combined mode. Table A-30 6000 W AC-input Power Supply LEDs LED Meaning INPUT OK •Green—Source AC voltage is OK. (Input voltage is 85 VAC or greater.) •Off—Source AC voltage falls below 70 VAC, is not present, or the power supply is turned off. FAN OK •Green—Power supply fan is operating properly. •Off—Power supply fan failure is detected. OUTPUT FAIL •Red—Problem with one or more of the DC-output voltages of the power supply is detected. •Off—DC-output voltage with acceptable margins. NoteFor proper operation of the OUTPUT FAIL LED, systems with single power supplies must be configured with a minimum of one fan tray assembly and one supervisor engine. Systems with dual power supplies must have a minimum configuration of one fan tray assembly, one supervisor engine, and one additional module. Failure to meet these minimum configuration requirements can cause a false power supply output fail signal. Table A-31 Redundant Mode Output 12 VDC 3.3 VDC –50 VDC Total 110 VAC to a single input on both supplies 850 W 40 W 922 W 1050 W 110 VAC to both inputs on both supplies 1700 W 40 W 1850 W 2100 W 220 VAC input to one input on both supplies 2200 W 40 W 2400 W 3000 W 220 VAC to both inputs on both supplies 2200 W 40 W 4600 W 6000 W
A-39 Catalyst 4500 E-Series Switches Installation Guide OL-13972-02 Appendix A Power Supply Specifications 6000 W AC-Input Power Supply 6000 W Power Supply AC Power Cords Ta b l e A - 3 3 lists the specifications for the AC power cords that are available for the 6000 W AC-input power supply. The table includes references to power cord illustrations. NoteAll 6000 W AC-input power supply power cords have an IEC60320/C19 appliance plug at one end. Table A-32 Combined Mode Output W @ 12 VDCW @3.3 VDCW @ –50 VDC Maximum (W) Both PS with one input at 110 VAC 1400 W 40 W 1670 W 1710 W One 110 VAC input to one PS, two 110 VAC inputs to the other PS2360 W 40 W 2560 W 2800 W Both PS with two 110 VAC inputs 3090 W 40 W 3360 W 3700 W Both PS with one 220 VAC input 4000 W 40 W 4360 W 5400 W Two 220 VAC inputs to one PS, one 220 VAC input to the other PS4000 W 40 W 6600 W 6200 W Both PS with two 220 VAC inputs 4000 W 40 W 8700 W 10900 W Table A-33 6000 W AC-Input Power Supply Power Cords LocalePower Cord Part Number Length Cordset RatingAC Source Plug Ty p e Japan, North America 120 VAC operationCAB-US515P-C19-US 9.8 ft (2.98 m)15 A, 125 VAC NEMA 5-15P Japan, North America (nonlocking) 200–240 VAC operationCAB-US620P-C19-US 13.2 ft (4.02 m)20 A, 250 VAC NEMA 6-20 non-locking Europe CAB-AC-2800W-EU= CAB-CEE77-C19-EU=13.2 ft (4.0 m)16 A, 250 VAC CEE 7/7 120354 120355 120357
A-40 Catalyst 4500 E-Series Switches Installation Guide OL-13972-02 Appendix A Power Supply Specifications 6000 W AC-Input Power Supply International CAB-AC-2800W-INT= CAB-I309-C19-INT=13.6 ft (4.1 m)20 A, 250 VAC IEC 309 Japan, North America (locking) 200–240 VAC operationCAB-AC-2800W-TWLK= CAB-L620P-C19-US=13.6 ft (4.1 m)16 A, 250 VAC NEMA L6-20 Australia CAB-AC-16A-AUS CAB-A3112-C19-AUS=14 ft (4.3 m) 16 A, 250 VAC AU20S3 Argentina CAB-IR2073-C19-AR= 14 ft (4.3 m) 16 A, 250 VAC IRAM 2073 China 200–240 VAC operationCAB-9K16A-CH 14 ft (4.3 m) 16 A, 250 VAC GB16C Switzerland CAB-ACS-16 8 ft (2.9 m) 16 A, 250 VAC G23 India CAB-SABS-C19-IND 14 ft (4.3 m) 16 A, 250 VAC SABS 164-1 United KingdomCAB-AC-2800W-INT CAB-I309-C19-INT14 ft (4.3 m) 16 A, 250 VAC IEC 309 Table A-33 6000 W AC-Input Power Supply Power Cords (continued) LocalePower Cord Part Number Length Cordset RatingAC Source Plug Ty p e 120360 120361 275667 120356 275664 275665 275666 120360
A-41 Catalyst 4500 E-Series Switches Installation Guide OL-13972-02 Appendix A Power Supply Specifications 6000 W AC-Input Power Supply Remote Power Cycling Feature The 6000 W AC-input power supply is equipped with a remote power cycling feature that allows you to remotely turn on or turn off the power supply through an external relay controller box. Figure A-9 shows a typical remote power on/off setup. A three-position terminal block, located on the lower right quadrant of the power supply faceplate, provides the interface to the external relay controller box. (See Figure A-9.) Figure A-9 Remote Power On/Off Feature Components Italy CAB-C2316-C19-IT= 14 ft (4.3 m) 16 A, 250 VAC CEI 23-16 Israel CAB-S132-C19-ISRL= 14 ft (4.3 m) 16 A, 250 VAC SI 16S3 Brazil CAB-EL224-C19-BR= 8 ft (2.9 m) 16 A, 250 VAC NBR 14136 UPS 220V CAB-C19-CBN 9 ft (2.74 m) 20 A, 250 VAC IEC-60320-C20 Table A-33 6000 W AC-Input Power Supply Power Cords (continued) LocalePower Cord Part Number Length Cordset RatingAC Source Plug Ty p e 120358 130922 275665 130923 274932 Remote power on/off terminal block Ferrite bead Relay controller 6000 Watt power supply Network Relaycontrollerpower
A-42 Catalyst 4500 E-Series Switches Installation Guide OL-13972-02 Appendix A Power Supply Specifications 6000 W AC-Input Power Supply Terminal Block The terminal block has four contacts labeled +V, IN, GND, and FB. Two control wires from an external relay controller box attach to either +V and IN or IN and GND. +V and IN are used when the relay controller box contains a normally-open (NO) type of relay. IN and GND are used when using an RS-232 interface. Ferrite Bead A plastic bag containing one ferrite bead and two 4-inch plastic ties is included with the 6000 W power supply AC power cords. The ferrite bead is a passive device that limits high-frequency interference on interface and control cables and is only required when you install the remote power-cycling feature that is supported by the 6000 W power supply. The ferrite bead is installed on the two control wires that come from the relay controller box to the terminal block on the 6000 W power supply. The ferrite bead should be installed as close as possible to the power supply terminal block for the bead to be effective. You do not need the ferrite bead for 6000 W power supply installations that do not include the remote power-cycling feature. Remote Power-Cycling Operation This feature allows you to remotely power cycle the Catalyst 4500 E-series switch using any appropriate third-party relay controller. This feature eliminates the need for you to have access to the supervisor engine console or CLI to control power cycling. Ta b l e A - 3 4 lists the relay controller box relay type, the corresponding power supply terminal block positions, and a description of the power-cycling operation. Table A-34 6000 W Power Supply Relay Controller Switch Settings and Operation External Relay Controller Box Relay Ty p ePower Supply Terminal Block Positions Used Remote Power-Cycling Operation Normally open (NO) relay.The +V pin is internally pulled up to 12 VDC with a 10 K ohms pull up resistor, and pin IN is connected to the input pin (either pin 1, 4, 10, or 13) of the line receiver. •Power supply cycled from on to off. The power supply is powered off by energizing the relay (relay contacts go from open to closed) for more than 5 seconds. •Power supply cycled from off to on. The power supply is powered on by reenergizing the relay (relay contacts go from closed to open) after a 10 second delay. RS232 driver. Pin IN is connected to the input pin (either pin 1, 4, 10, or 13) of the line receiver, and pin GND is connected to ground. A capacitor of 1 uF should be used between the line receiver input and the ground to bypass noise peaks. •Power supply cycles from on to off. The power supply is powered off by RS-232 logic HI for more than 5 seconds. •Power supply cycles from off to on— The power supply is powered on by RS-232 logic LO after a 10 second delay. No relay attached. Remote power-cycling feature not installed.——