    							A-33
    Catalyst 4500 E-Series Switches Installation Guide
    OL-13972-02
    Appendix A      Power Supply Specifications
      4200 W AC-Input Power Supply
    Ta b l e A - 2 7 shows the maximum output wattage with two 4200 W AC-input power supplies operating in 
    combined mode. 
    4200 W Power Supply AC Power Cords
    Ta b l e A - 2 8 lists the specifications for the AC power cords that are available for the 4200 W AC-input 
    power supply. 
    NoteAll 4200 W power supply power cords have an IEC60320/C19 appliance plug at one end. 
    Table A-26 Redundant Mode Output
    Source AC to Power Supplies +12 VDC +3.3 VDC –50 VDC Total (W)
    110 VAC to one input on supply 1 and one 
    100 VAC to one input on power supply 2660 W 40 W 700 W 1050 W
    110 VAC to both inputs on power supply 1 and 
    110 VAC to both inputs on power supply 2, or 
    one 220 VAC input to power supply 1 and one 
    220 VAC input to power supply 21360 W 40 W 1850 W 2100 W
    220 VAC to both inputs on power supply 1 and 
    power supply 21360 W 40 W 3700 W 4200 W
    Table A-27 4200 W Power Supplies in Combined Mode Output
    Source AC to Power Supplies W @ 
    +12 VDCW @ 
    +3.3 VDCW @ 
    –50 VDCMaximum 
    (W)
    Both power supplies with one input at 
    110 VAC 1200 W 40 W 1320 W 1870 W
    One 110 VAC input to one power supply 
    and two 110 VAC inputs to the other 
    power supply1800 W 40 W 2000 W 2730 W
    Both power supplies with two 110 VAC 
    inputs2200 W 40 W 3100 W 3800 W
    Both power supplies with one 220 VAC 
    input 2200 W 40 W 3100 W 3800 W
    Two 220 VAC inputs to one power supply, 
    one 220 VAC input to the other power 
    supply2200 W 40 W 4700 W 5500 W
    Both power supplies with two 220 VAC 
    inputs2200 W 40 W 6200 W 7600 W 
    						
    							A-34
    Catalyst 4500 E-Series Switches Installation Guide
    OL-13972-02
    Appendix A      Power Supply Specifications
      4200 W AC-Input Power Supply
    Table A-28 4200 W AC-Input Power Supply Power Cords
    LocalePower Cord Part 
    Number Length Cordset RatingAC Source Plug 
    Ty p e
    Japan, North 
    America
    120 VAC 
    operationCAB-US515P-C19-US 9.8 ft 
    (2.98 m)15 A, 125 VAC NEMA 5-15P
    Japan, North 
    America 
    (locking)
    200–240 VAC 
    operationCAB-L620P-C19-US 14 ft (4.2 m)  20 A, 250 VAC NEMA L6-20
    Japan, North 
    America 
    (nonlocking)
    200–240 VAC 
    operationCAB-US620P-C19-US 13.2 ft 
    (4.02 m)20 A, 250 VAC NEMA 6-20 
    non-locking 
    Europe CAB-CEE77-C19-EU 13.2 ft 
    (4.0 m)15 A, 250 VAC CEE 7/7
    International 
    (including 
    Argentina and 
    South Africa)CAB-I309-C19-INT 13.6 ft 
    (4.1 m)16 A, 250 VAC IEC 309
    Australia CAB-A3112-C19-AUS 14 ft (4.3 m) 15 A, 250 VAC AS/NZZS 3112
    Argentina CAB-IR2073-C19-AR= 
    (was CAB-7513ACR=)14 ft (4.3 m) 10 A, 250 VAC IRAM 2073
    Italy CAB-C2316-C19-IT 14 ft (4.3 m) 16 A, 250 VAC CEI 23-16
    120354
    120361
    120355
    120357
    120360
    120356
    120356
    120358 
    						
    							A-35
    Catalyst 4500 E-Series Switches Installation Guide
    OL-13972-02
    Appendix A      Power Supply Specifications
      6000 W AC-Input Power Supply
    6000 W AC-Input Power Supply
    The 6000 W AC-input power supply (PWR-C45-6000ACV), shown in Figure A-8, is supported in 
    following Catalyst 4500 E-series switch chassis:
    •Catalyst 4503-E
    •Catalyst 4506-E
    •Catalyst 4507R-E
    •Catalyst 4510R-E
    •Catalyst 4507R+E
    •Catalyst 4510R+E United 
    KingdomCAB-BS1363-C19-UK 14 ft (4.3 m) 13 A, 250 VAC BS 1363
    Israeli CAB-S132-C19-ISRL 14 ft (4.3 m) 16 A, 250 VAC SI32
    UPS 220V CAB-C19-CBN 9 ft (2.74 m) 20 A, 250 VAC IEC-60320-C20
    Table A-28 4200 W AC-Input Power Supply Power Cords (continued)
    LocalePower Cord Part 
    Number Length Cordset RatingAC Source Plug 
    Ty p e
    120359
    130922
    130923 
    						
    							A-36
    Catalyst 4500 E-Series Switches Installation Guide
    OL-13972-02
    Appendix A      Power Supply Specifications
      6000 W AC-Input Power Supply
    Figure A-8 6000 W Dual-Input AC Power Supply
    6000 W Power Supply Specifications
    Ta b l e A - 2 9 lists the specifications for the 6000 W AC-input power supplies. 1AC-input 2 receptacle4AC-input 1 receptacle
    2AC-input 2 on switch5Captive screws
    3AC-input 1 on switch6Remote power cycling terminal
    274931
    5
    4
    2
    1
    3
    6
    Table A-29 6000 W AC-Input Power Supply Specifications
    Item Specification
    AC-input type  Autoranging inputs with power factor correction
    NotePower factor correction is a standard feature on all Catalyst 4500 
    E-series AC-input power supplies. PFC reduces the reactive 
    component in the source AC current allowing higher power 
    factors (typically 99 percent or better) and lower harmonic 
    current components.
    AC-input voltage 
    •Low-line (120 VAC nominal)—85 VAC (min) to 132 VAC (max)
    •High-line (230 VAC nominal)—170 VAC (min) to 264 VAC (max)
    AC-input current 
    •12 A (max) @ 120 VAC (for each input)
    •16 A (max) @ 230 VAC (for each input)
    AC-input frequency  50/60 Hz (nominal) (±3% for full range) 
    						
    							A-37
    Catalyst 4500 E-Series Switches Installation Guide
    OL-13972-02
    Appendix A      Power Supply Specifications
      6000 W AC-Input Power Supply
    Ta b l e A - 3 0 list the 6000 W AC-input power supply LEDs and their meanings. Power supply output  Total output depends on the number of inputs connected and the source 
    AC voltage. If two inputs are used, they should both be of the same AC 
    voltage.
    •1050 W operation (with one 120 VAC nominal input)
    –70.8 A @ 12 VDC (data only)
    –12.5 A @ 3.3 VDC (data only)
    –18.4 A @ –50 VDC (PoE if used)
    •2100 W operation (with two 120 VAC nominal inputs)
    –141.6 A @ 12 VDC (data only)
    –12.5 A @ 3.3 VDC (data only)
    –37.0 A @ –50 VDC (PoE if used)
    •3000 W operation (with one 230 VAC nominal input)
    –183.3 A @ 12 VDC (data only)
    –12.5 A @ 3.3 VDC (data only)
    –48 A @ –50 VDC (PoE if used)
    •6000 W operation (with two 230 VAC nominal inputs)
    –183.3 A @ 12 VDC (data only)
    –12.5 A @ 3.3 VDC (data only)
    –96 A @ –50 VDC (PoE if used)
    Power supply output 
    capacity6000 W maximum
    Output holdup time 20 ms minimum 
    kVA rating
    16.8 kVA (power factor = 0.99)
    Heat dissipation 2,720 BTUs/hr (approx.)
    Minimum software 
    requirement Cisco IOS Release 12.2(52)SG
    Power over Ethernet  Supported, up to 4800 W 
    1. The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard 
    circuits and transformers to power a switch.
    Table A-29 6000 W AC-Input Power Supply Specifications
    Item Specification 
    						
    							A-38
    Catalyst 4500 E-Series Switches Installation Guide
    OL-13972-02
    Appendix A      Power Supply Specifications
      6000 W AC-Input Power Supply
    NoteThe 6000 W AC-input power supply should not be used in mixed-voltage configurations. All the inputs 
    in a chassis must be at the same voltage (110 VAC or 220 VAC).
    Ta b l e A - 3 1 shows the wattage output possible from a 6000 W AC-input power supply in redundant 
    mode. In redundant mode, two power supplies must have identical inputs and all inputs must be at the 
    same voltage. If the input voltages are mismatched, choose the value matching the weaker of the two 
    power supplies.
    Ta b l e A - 3 2 shows the maximum output wattage with two 6000 W AC-input power supplies in combined 
    mode.
    Table A-30 6000 W AC-input Power Supply LEDs
    LED Meaning
    INPUT OK
    •Green—Source AC voltage is OK. (Input voltage is 85 VAC or 
    greater.)
    •Off—Source AC voltage falls below 70 VAC, is not present, or the 
    power supply is turned off.
    FAN OK
    •Green—Power supply fan is operating properly.
    •Off—Power supply fan failure is detected.
    OUTPUT FAIL
    •Red—Problem with one or more of the DC-output voltages of the 
    power supply is detected.
    •Off—DC-output voltage with acceptable margins.
    NoteFor proper operation of the OUTPUT FAIL LED, systems with 
    single power supplies must be configured with a minimum of 
    one fan tray assembly and one supervisor engine. Systems with 
    dual power supplies must have a minimum configuration of one 
    fan tray assembly, one supervisor engine, and one additional 
    module. Failure to meet these minimum configuration 
    requirements can cause a false power supply output fail signal.
    Table A-31 Redundant Mode Output
    12 VDC 3.3 VDC –50 VDC Total
    110 VAC to a single input on both supplies 850 W 40 W 922 W 1050 W
    110 VAC to both inputs on both supplies  1700 W 40 W 1850 W 2100 W
    220 VAC input to one input on both supplies 2200 W 40 W 2400 W 3000 W
    220 VAC to both inputs on both supplies 2200 W 40 W 4600 W 6000 W 
    						
    							A-39
    Catalyst 4500 E-Series Switches Installation Guide
    OL-13972-02
    Appendix A      Power Supply Specifications
      6000 W AC-Input Power Supply
    6000 W Power Supply AC Power Cords
    Ta b l e A - 3 3 lists the specifications for the AC power cords that are available for the 6000 W AC-input 
    power supply. The table includes references to power cord illustrations.
    NoteAll 6000 W AC-input power supply power cords have an IEC60320/C19 appliance plug at one end. 
    Table A-32 Combined Mode Output
    W @ 12 VDCW @3.3 
    VDCW @ –50 
    VDC Maximum (W)
    Both PS with one input at 110 VAC  1400 W 40 W 1670 W 1710 W
    One 110 VAC input to one PS, two 
    110 VAC inputs to the other PS2360 W 40 W 2560 W 2800 W
    Both PS with two 110 VAC inputs 3090 W 40 W 3360 W 3700 W
    Both PS with one 220 VAC input  4000 W 40 W 4360 W 5400 W
    Two 220 VAC inputs to one PS, one 
    220 VAC input to the other PS4000 W 40 W 6600 W 6200 W
    Both PS with two 220 VAC inputs 4000 W 40 W 8700 W 10900 W
    Table A-33 6000 W AC-Input Power Supply Power Cords
    LocalePower Cord Part 
    Number Length Cordset RatingAC Source Plug 
    Ty p e
    Japan, North 
    America
    120 VAC 
    operationCAB-US515P-C19-US 9.8 ft 
    (2.98 m)15 A, 125 VAC NEMA 5-15P
    Japan, North 
    America 
    (nonlocking)
    200–240 VAC 
    operationCAB-US620P-C19-US 13.2 ft 
    (4.02 m)20 A, 250 VAC NEMA 6-20 
    non-locking 
    Europe CAB-AC-2800W-EU=
    CAB-CEE77-C19-EU=13.2 ft 
    (4.0 m)16 A, 250 VAC CEE 7/7
    120354
    120355
    120357 
    						
    							A-40
    Catalyst 4500 E-Series Switches Installation Guide
    OL-13972-02
    Appendix A      Power Supply Specifications
      6000 W AC-Input Power Supply
    International CAB-AC-2800W-INT=
    CAB-I309-C19-INT=13.6 ft 
    (4.1 m)20 A, 250 VAC IEC 309
    Japan, North 
    America 
    (locking)
    200–240 VAC 
    operationCAB-AC-2800W-TWLK=
    CAB-L620P-C19-US=13.6 ft 
    (4.1 m)16 A, 250 VAC NEMA L6-20
    Australia CAB-AC-16A-AUS 
    CAB-A3112-C19-AUS=14 ft (4.3 m) 16 A, 250 VAC AU20S3
    Argentina CAB-IR2073-C19-AR=  14 ft (4.3 m) 16 A, 250 VAC IRAM 2073
    China 
    200–240 VAC 
    operationCAB-9K16A-CH 14 ft (4.3 m) 16 A, 250 VAC GB16C
    Switzerland CAB-ACS-16 8 ft (2.9 m) 16 A, 250 VAC G23
    India CAB-SABS-C19-IND 14 ft (4.3 m) 16 A, 250 VAC SABS 164-1
    United 
    KingdomCAB-AC-2800W-INT
    CAB-I309-C19-INT14 ft (4.3 m) 16 A, 250 VAC IEC 309
    Table A-33 6000 W AC-Input Power Supply Power Cords (continued)
    LocalePower Cord Part 
    Number Length Cordset RatingAC Source Plug 
    Ty p e
    120360
    120361
    275667
    120356
    275664
    275665
    275666
    120360 
    						
    							A-41
    Catalyst 4500 E-Series Switches Installation Guide
    OL-13972-02
    Appendix A      Power Supply Specifications
      6000 W AC-Input Power Supply
    Remote Power Cycling Feature
    The 6000 W AC-input power supply is equipped with a remote power cycling feature that allows you to 
    remotely turn on or turn off the power supply through an external relay controller box. Figure A-9 shows 
    a typical remote power on/off setup. A three-position terminal block, located on the lower right quadrant 
    of the power supply faceplate, provides the interface to the external relay controller box. (See 
    Figure A-9.)
    Figure A-9 Remote Power On/Off Feature Components
    Italy CAB-C2316-C19-IT= 14 ft (4.3 m) 16 A, 250 VAC CEI 23-16
    Israel CAB-S132-C19-ISRL= 14 ft (4.3 m) 16 A, 250 VAC SI 16S3
    Brazil CAB-EL224-C19-BR= 8 ft (2.9 m) 16 A, 250 VAC NBR 14136
    UPS 220V CAB-C19-CBN 9 ft (2.74 m) 20 A, 250 VAC IEC-60320-C20
    Table A-33 6000 W AC-Input Power Supply Power Cords (continued)
    LocalePower Cord Part 
    Number Length Cordset RatingAC Source Plug 
    Ty p e
    120358
    130922
    275665
    130923
    274932
    Remote
    power on/off
    terminal block
    Ferrite
    bead Relay controller
    6000 Watt power supply
    Network
    Relaycontrollerpower 
    						
    							A-42
    Catalyst 4500 E-Series Switches Installation Guide
    OL-13972-02
    Appendix A      Power Supply Specifications
      6000 W AC-Input Power Supply
    Terminal Block
    The terminal block has four contacts labeled +V, IN, GND, and FB. Two control wires from an external 
    relay controller box attach to either +V and IN or IN and GND. +V and IN are used when the relay 
    controller box contains a normally-open (NO) type of relay. IN and GND are used when using an RS-232 
    interface. 
    Ferrite Bead
    A plastic bag containing one ferrite bead and two 4-inch plastic ties is included with the 6000 W power 
    supply AC power cords. The ferrite bead is a passive device that limits high-frequency interference on 
    interface and control cables and is only required when you install the remote power-cycling feature that 
    is supported by the 6000 W power supply. The ferrite bead is installed on the two control wires that come 
    from the relay controller box to the terminal block on the 6000 W power supply. The ferrite bead should 
    be installed as close as possible to the power supply terminal block for the bead to be effective. You do 
    not need the ferrite bead for 6000 W power supply installations that do not include the remote 
    power-cycling feature.
    Remote Power-Cycling Operation
    This feature allows you to remotely power cycle the Catalyst 4500 E-series switch using any appropriate 
    third-party relay controller. This feature eliminates the need for you to have access to the supervisor 
    engine console or CLI to control power cycling. Ta b l e A - 3 4 lists the relay controller box relay type, the 
    corresponding power supply terminal block positions, and a description of the power-cycling operation. 
    Table A-34 6000 W Power Supply Relay Controller Switch Settings and Operation
    External Relay 
    Controller Box Relay 
    Ty p ePower Supply Terminal Block Positions Used Remote Power-Cycling Operation 
    Normally open 
    (NO) relay.The +V pin is internally pulled up to 12 VDC 
    with a 10 K ohms pull up resistor, and pin IN is 
    connected to the input pin (either pin 1, 4, 10, or 
    13) of the line receiver. 
    •Power supply cycled from on to off. The 
    power supply is powered off by energizing 
    the relay (relay contacts go from open to 
    closed) for more than 5 seconds. 
    •Power supply cycled from off to on. The 
    power supply is powered on by reenergizing 
    the relay (relay contacts go from closed to 
    open) after a 10 second delay.
    RS232 driver. Pin IN is connected to the input pin (either pin 
    1, 4, 10, or 13) of the line receiver, and pin GND 
    is connected to ground. A capacitor of 1 uF 
    should be used between the line receiver input 
    and the ground to bypass noise peaks.
    •Power supply cycles from on to off. The 
    power supply is powered off by RS-232 
    logic HI for more than 5 seconds.
    •Power supply cycles from off to on— The 
    power supply is powered on by RS-232 
    logic LO after a 10 second delay.
    No relay attached. 
    Remote power-cycling 
    feature not installed.—— 
    						