23
A12187
6.3.1.1. Auto Mode set up
Once the auto changeover option has been selected, touch SAVE.
SEnable or Disable: Choose to enable or disable auto changeover mode
dDefault = Enable
SAuto changeover time: Adjustable from 5 to 120 minutes
dDefault = 30 minutes
6.3.1.2. Heat/Cool Deadband
The minimum difference enforced between heating and cooling desired
temperatures. This can allow one setting to “push” the other to maintain this
difference. When the correct deadband is set, touchSAVE.
SDeadband:...

Page 32

24
SOutdoor temperature:Adjustable from --5 to 5_F(--3to3_C)
dDefault = 0_F
SHumidity:Adjustable from --10 – 10%
dDefault = 0%
6.3.1.4. Reset factory defaults
This option allows the installer to reset certain factory parameters. After the
selections are made, touchSAVE.
SProgram Schedule:Reset back to pre --programmed time and temperature.
SUser Settings:Reset user settings back to pre --programmed values.
SInstall Settings:Reset installation settings back to pre --programmed values.
SLast 10...

Page 33

25
6.3.1.7. Temperature Units Display
This option allows the installer to choose between Fahrenheit and Celsius display.
After the selection is made, touch SAVE.
SDisplay Option:Selectable between_Fand_C
dDefault =_F
6.3.2. Fan Coil
First touchSETUP, then touchFA N C O I Lto set up the parameters for the fan coil
unit.
A12188
6.3.2.1. Fan Coil Airflow
This option allows the installer to select the appropriate air flow based on the needs
of the installation. TheQUIETairflow means the minimum cooling...

Page 34

26
reduction is performed. This is nominally 325 CFM/ton, but will vary if a 2 --stage
outdoor unit is used. TheEFF350airflow is a fixed airflow used to achieve
specified ratings – no dehumidification airflow reduction is performed. This is
nominally 350 CFM/ton, but will vary if a 2 --stage outdoor unit is used. TheMAX
airflow is a fixed 400 CFM/ton. No dehumidification airflow reduction is
performed.
The dehumidify airflow, when set toNORMAL,isallowedtoadjusttoaminimum
to satisfy the dehumidification...

Page 35

27
dDefault = 15 minutes
SElectric Reheat:Ye s o r N o
dDefault = No
6.3.2.3. Fan Coil G--Terminal
This setup option selects desired operation when the R--G circuit changes state on
the fan coil control board depending on setup.
Under the function option,FA Nturns on fan to selected fan speed when G terminal
is energized.SHUTDOWNshuts off fan and equipment when initiated. After the
selections are made, touchSAVE.
SFunction:Disabled, Fan or Shutdown
dDefault = Disabled
SFan Speed:Low, Med, or High...

Page 36

28
A12189
6.3.3.1. Furnace Airflow
Selects the airflow of the furnace when heating.EFFICIENCYis the airflow used
to meet specified ratings,COMFORTis a decreased airflow used to increase the
output air temperature and provide increased comfort.
For the Low heat rise option, set to ON if the system contains a bypass humidifier.
The ON setting will increase the furnace low heat airflow.
After the selections are made, touchSAVE.
SFurnace Air Flow:Comfort or Efficiency
dDefault = Comfort
SLow Heat Rise:On or...

Page 37

29
airflows. TheCOMFORTairflow means airflow is varied depending on humidity
and temperature demand settings. This selection enables the full dehumidify and
comfort capabilities of the system. TheEFF325airflow is a fixed airflow used to
achieve specified ratings – no dehumidification airflow reduction is performed.
This is nominally 325 CFM/ton, but will vary if a 2 --stage outdoor unit is used. The
EFF350airflow is a fixed airflow used to achieve specified ratings – no
dehumidification airflow reduction...

Page 38

30
the medium and high stages (2 stages of heat).HIGHwill only run the high stage
of furnace heat.
NOTE: Two --stage furnace hasLOWandHIGHselections only.
SStages: System, Low, Low --Med, Med, Med --High, or High
dDefault = System
SHigh Stage Timer:Selectable from 10 to 60 minutes
dDefault = 10 minutes
6.3.3.4. Furnace Airflow Limits (modulating furnace only)
The following settings allow the installer to restrict the furnace within certain
minimum and maximum airflows. These airflows are converted to...

Page 39

31
6.3.3.6. Altitude
This setting will adjust the furnace’s airflow to compensate for altitude. Altitude
adjustment is not available with older furnaces. Please see furnace instructions for
further details. After the selection is made, touchSAVE.
SAltitude:0000 – 2000, US 2001 – 3000, CN 2100 – 4500, US 3001 – 4000,
US 4001 – 5000, US 5001 6000, US 6001 – 7000, US 7001 – 8000, US 8001 –
9000, and US > 9000.
dDefault = US 2001 --3000
6.3.3.7. Furnace Dehumidifier Drain
This option selects the time the...

Page 40

32
SShutdown:
dNormally Open
dNormally Closed
6.3.4. AC/Heat Pump
First touchSETUP, then touchAC/HEAT PUMPto set up the parameters for the
AC/Heat Pump unit.
A12190
6.3.4.1. Cooling Lockout
Outside temperature below which cooling will not be provided. After the selection
is made, touchSAVE. 