Page 31
23 A12187 6.3.1.1. Auto Mode set up Once the auto changeover option has been selected, touch SAVE. SEnable or Disable: Choose to enable or disable auto changeover mode dDefault = Enable SAuto changeover time: Adjustable from 5 to 120 minutes dDefault = 30 minutes 6.3.1.2. Heat/Cool Deadband The minimum difference enforced between heating and cooling desired temperatures. This can allow one setting to “push” the other to maintain this difference. When the correct deadband is set, touchSAVE. SDeadband:...
Page 32
24 SOutdoor temperature:Adjustable from --5 to 5_F(--3to3_C) dDefault = 0_F SHumidity:Adjustable from --10 – 10% dDefault = 0% 6.3.1.4. Reset factory defaults This option allows the installer to reset certain factory parameters. After the selections are made, touchSAVE. SProgram Schedule:Reset back to pre --programmed time and temperature. SUser Settings:Reset user settings back to pre --programmed values. SInstall Settings:Reset installation settings back to pre --programmed values. SLast 10...
Page 33
25 6.3.1.7. Temperature Units Display This option allows the installer to choose between Fahrenheit and Celsius display. After the selection is made, touch SAVE. SDisplay Option:Selectable between_Fand_C dDefault =_F 6.3.2. Fan Coil First touchSETUP, then touchFA N C O I Lto set up the parameters for the fan coil unit. A12188 6.3.2.1. Fan Coil Airflow This option allows the installer to select the appropriate air flow based on the needs of the installation. TheQUIETairflow means the minimum cooling...
Page 34
26 reduction is performed. This is nominally 325 CFM/ton, but will vary if a 2 --stage outdoor unit is used. TheEFF350airflow is a fixed airflow used to achieve specified ratings – no dehumidification airflow reduction is performed. This is nominally 350 CFM/ton, but will vary if a 2 --stage outdoor unit is used. TheMAX airflow is a fixed 400 CFM/ton. No dehumidification airflow reduction is performed. The dehumidify airflow, when set toNORMAL,isallowedtoadjusttoaminimum to satisfy the dehumidification...
Page 35
27 dDefault = 15 minutes SElectric Reheat:Ye s o r N o dDefault = No 6.3.2.3. Fan Coil G--Terminal This setup option selects desired operation when the R--G circuit changes state on the fan coil control board depending on setup. Under the function option,FA Nturns on fan to selected fan speed when G terminal is energized.SHUTDOWNshuts off fan and equipment when initiated. After the selections are made, touchSAVE. SFunction:Disabled, Fan or Shutdown dDefault = Disabled SFan Speed:Low, Med, or High...
Page 36
28 A12189 6.3.3.1. Furnace Airflow Selects the airflow of the furnace when heating.EFFICIENCYis the airflow used to meet specified ratings,COMFORTis a decreased airflow used to increase the output air temperature and provide increased comfort. For the Low heat rise option, set to ON if the system contains a bypass humidifier. The ON setting will increase the furnace low heat airflow. After the selections are made, touchSAVE. SFurnace Air Flow:Comfort or Efficiency dDefault = Comfort SLow Heat Rise:On or...
Page 37
29 airflows. TheCOMFORTairflow means airflow is varied depending on humidity and temperature demand settings. This selection enables the full dehumidify and comfort capabilities of the system. TheEFF325airflow is a fixed airflow used to achieve specified ratings – no dehumidification airflow reduction is performed. This is nominally 325 CFM/ton, but will vary if a 2 --stage outdoor unit is used. The EFF350airflow is a fixed airflow used to achieve specified ratings – no dehumidification airflow reduction...
Page 38
30 the medium and high stages (2 stages of heat).HIGHwill only run the high stage of furnace heat. NOTE: Two --stage furnace hasLOWandHIGHselections only. SStages: System, Low, Low --Med, Med, Med --High, or High dDefault = System SHigh Stage Timer:Selectable from 10 to 60 minutes dDefault = 10 minutes 6.3.3.4. Furnace Airflow Limits (modulating furnace only) The following settings allow the installer to restrict the furnace within certain minimum and maximum airflows. These airflows are converted to...
Page 39
31 6.3.3.6. Altitude This setting will adjust the furnace’s airflow to compensate for altitude. Altitude adjustment is not available with older furnaces. Please see furnace instructions for further details. After the selection is made, touchSAVE. SAltitude:0000 – 2000, US 2001 – 3000, CN 2100 – 4500, US 3001 – 4000, US 4001 – 5000, US 5001 6000, US 6001 – 7000, US 7001 – 8000, US 8001 – 9000, and US > 9000. dDefault = US 2001 --3000 6.3.3.7. Furnace Dehumidifier Drain This option selects the time the...
Page 40
32 SShutdown: dNormally Open dNormally Closed 6.3.4. AC/Heat Pump First touchSETUP, then touchAC/HEAT PUMPto set up the parameters for the AC/Heat Pump unit. A12190 6.3.4.1. Cooling Lockout Outside temperature below which cooling will not be provided. After the selection is made, touchSAVE.