    6.3.1.1. Auto Mode set up
    Once the auto changeover option has been selected, touch SAVE.
    SEnable or Disable: Choose to enable or disable auto changeover mode
    dDefault = Enable
    SAuto changeover time: Adjustable from 5 to 120 minutes
    dDefault = 30 minutes
    6.3.1.2. Heat/Cool Deadband
    The minimum difference enforced between heating and cooling desired
    temperatures. This can allow one setting to “push” the other to maintain this
    difference. When the correct deadband is set, touchSAVE.
    SDeadband: Adjustable from 0 to 6_F(0to2_C)
    dDefault = 2_F
    6.3.1.3. Offsets
    This option allows calibration (or deliberate miscalibration) of the temperature and
    humidity sensors. These offsets are added to the actual temperature/humidity
    values. When the correct offsets are made, touchSAVE. 
    						
    							24
    SOutdoor temperature:Adjustable from --5 to 5_F(--3to3_C)
    dDefault = 0_F
    SHumidity:Adjustable from --10 – 10%
    dDefault = 0%
    6.3.1.4. Reset factory defaults
    This option allows the installer to reset certain factory parameters. After the
    selections are made, touchSAVE.
    SProgram Schedule:Reset back to pre --programmed time and temperature.
    SUser Settings:Reset user settings back to pre --programmed values.
    SInstall Settings:Reset installation settings back to pre --programmed values.
    SLast 10 Faults:Reset the last 10 system faults under the Service menu.
    6.3.1.5. Scheduling Enable
    This option lets the installer allow programming features. After the selection is
    made, touchSAVE.
    SScheduling:On or Off
    dDefault = On
    6.3.1.6. Smart Recovery Enable
    Applies to programmable operation only. Will start recovery 90 minutes prior to
    schedule change in both heating and cooling mode. After the selection is made,
    touchSAVE.
    SSmart Recovery:On or Off
    dDefault = On 
    						
    							25
    6.3.1.7. Temperature Units Display
    This option allows the installer to choose between Fahrenheit and Celsius display.
    After the selection is made, touch SAVE.
    SDisplay Option:Selectable between_Fand_C
    dDefault =_F
    6.3.2. Fan Coil
    First touchSETUP, then touchFA N C O I Lto set up the parameters for the fan coil
    unit.
    A12188
    6.3.2.1. Fan Coil Airflow
    This option allows the installer to select the appropriate air flow based on the needs
    of the installation. TheQUIETairflow means the minimum cooling airflow that the
    system can safely run (typically 300 CFM/ton). Use this setting if duct noise is a
    severe problem. Note that duct sweating in high humidity environments could
    become an issue at low airflows. TheCOMFORTairflow means airflow is varied
    depending on humidity and temperature demand settings. This selection enables the
    full dehumidify and comfort capabilities of the system. TheEFF325airflow is a
    fixed airflow used to achieve specified ratings – no dehumidification airflow 
    						
    							26
    reduction is performed. This is nominally 325 CFM/ton, but will vary if a 2 --stage
    outdoor unit is used. TheEFF350airflow is a fixed airflow used to achieve
    specified ratings – no dehumidification airflow reduction is performed. This is
    nominally 350 CFM/ton, but will vary if a 2 --stage outdoor unit is used. TheMAX
    airflow is a fixed 400 CFM/ton. No dehumidification airflow reduction is
    performed.
    The dehumidify airflow, when set toNORMAL,isallowedtoadjusttoaminimum
    to satisfy the dehumidification call. When set toHIGH, the minimum airflow
    during the dehumidify mode is increased to reduce duct and register sweating. Also
    the airflow increases minimum airflow during normal cooling operation to help
    reduce duct sweating.
    After the selections are made, touchSAVE.
    SCooling Airflow:Quiet, Comfort, EFF325, EFF350, or Max
    dDefault = Comfort
    SDehumidify Airflow:Normal or High
    dDefault = Normal
    6.3.2.2. Fan Coil Dehumidification
    The Dehum Drain Time option turns off the continuous fan at the end of cooling for
    five minutes in order to drain the indoor coil of water. The fan will only be turned
    off if a dehumidify demand existed at the start of or during the cooling cycle.
    The Electric Reheat option enables the electric heat to be used while
    cool--to --dehumidify is running. This will allow the cool--to --dehumidify function to
    run longer, greatly improving humidity control in cooling mode. Accumulated
    electrical energy used while reheating (in kilowatt--hours) is shown on the Fan Coil
    Run Hours screen and can be reset there. This option is only available with fan coil
    systems.
    After the selections are made, touchSAVE.
    SDehum Drain Time:Adjustable from 5 to 60 minutes or OFF 
    						
    							27
    dDefault = 15 minutes
    SElectric Reheat:Ye s o r N o
    dDefault = No
    6.3.2.3. Fan Coil G--Terminal
    This setup option selects desired operation when the R--G circuit changes state on
    the fan coil control board depending on setup.
    Under the function option,FA Nturns on fan to selected fan speed when G terminal
    is energized.SHUTDOWNshuts off fan and equipment when initiated. After the
    selections are made, touchSAVE.
    SFunction:Disabled, Fan or Shutdown
    dDefault = Disabled
    SFan Speed:Low, Med, or High
    dDefault = Low
    SShutdown:
    dNormally Open
    dNormally Closed
    6.3.3. Furnace
    First touchSETUP, then touchFURNACEto set up the parameters for the furnace
    unit. 
    						
    							28
    A12189
    6.3.3.1. Furnace Airflow
    Selects the airflow of the furnace when heating.EFFICIENCYis the airflow used
    to meet specified ratings,COMFORTis a decreased airflow used to increase the
    output air temperature and provide increased comfort.
    For the Low heat rise option, set to ON if the system contains a bypass humidifier.
    The ON setting will increase the furnace low heat airflow.
    After the selections are made, touchSAVE.
    SFurnace Air Flow:Comfort or Efficiency
    dDefault = Comfort
    SLow Heat Rise:On or Off
    dDefault = Off
    6.3.3.2. AC/HP Air Flow
    This option elects the airflow of the furnace when cooling, heat pump heating, and
    dehumidification.
    TheQUIETairflow means the minimum cooling airflow that the system can safely
    run (typically 300 CFM/ton). Use this setting if duct noise is a severe problem. Note
    that duct sweating in high humidity environments could become an issue at low 
    						
    							29
    airflows. TheCOMFORTairflow means airflow is varied depending on humidity
    and temperature demand settings. This selection enables the full dehumidify and
    comfort capabilities of the system. TheEFF325airflow is a fixed airflow used to
    achieve specified ratings – no dehumidification airflow reduction is performed.
    This is nominally 325 CFM/ton, but will vary if a 2 --stage outdoor unit is used. The
    EFF350airflow is a fixed airflow used to achieve specified ratings – no
    dehumidification airflow reduction is performed. This is nominally 350 CFM/ton,
    but will vary if a 2 --stage outdoor unit is used. TheMAXairflow is a fixed 400
    CFM/ton. No dehumidification airflow reduction is performed.
    The dehumidify airflow, when set toNORMAL, the airflow is allowed to adjust to
    a minimum to satisfy the dehumidification call. When set toHIGH, the minimum
    airflow during the dehumidify mode is increased to reduce duct and register
    sweating. Also the airflow increases minimum airflow during normal cooling
    operation to help reduce duct sweating.
    After the selections are made, touchSAVE.
    SCool:Quiet, Comfort, EFF325, EFF350, or Max
    dDefault = Comfort
    SHP Heat:Comfort or EFF350
    dDefault = Comfort
    SDehumidify:Normal or High
    dDefault = Normal
    6.3.3.3. Furnace Staging
    This option controls the staging of the furnace and selects the minimum amount of
    time low stage must operate before high stage is activated.SYSTEMsetting will
    allow the InfinityrZone Control to determine furnace staging.LOWwill only run
    the low stage of furnace heat.LOW-- MEDwill run the low and medium stages (2
    stages of heat).MEDwill only run the medium stage of heat.MED-- HIGHwill run 
    						
    							30
    the medium and high stages (2 stages of heat).HIGHwill only run the high stage
    of furnace heat.
    NOTE: Two --stage furnace hasLOWandHIGHselections only.
    SStages: System, Low, Low --Med, Med, Med --High, or High
    dDefault = System
    SHigh Stage Timer:Selectable from 10 to 60 minutes
    dDefault = 10 minutes
    6.3.3.4. Furnace Airflow Limits (modulating furnace only)
    The following settings allow the installer to restrict the furnace within certain
    minimum and maximum airflows. These airflows are converted to capacities. The
    Min and Max limits are determined by the equipment size. These settings are not
    the same as the zoning airflow limits.
    SMin. modulating limits:Minimum CFM to run a modulating furnace. This will
    increase the minimum operating capacity of the furnace.
    dDefault value is the furnace air flow for the lowest heat capacity.
    SMax. modulating limits:Maximum CFM to run a modulating furnace. This
    will increase the maximum operating capacity of the furnace.
    dDefault value is the furnace air flow for the highest heat capacity
    6.3.3.5. Furnace Off Delay
    This option denotes the amount of time the blower will continue to run after heating
    has shut off. After the selection is made, touchSAVE.
    SFurnace Off Delay:90, 120, 150 or 180 seconds
    dDefault = 120 seconds 
    						
    							31
    6.3.3.6. Altitude
    This setting will adjust the furnace’s airflow to compensate for altitude. Altitude
    adjustment is not available with older furnaces. Please see furnace instructions for
    further details. After the selection is made, touchSAVE.
    SAltitude:0000 – 2000, US 2001 – 3000, CN 2100 – 4500, US 3001 – 4000,
    US 4001 – 5000, US 5001 6000, US 6001 – 7000, US 7001 – 8000, US 8001 –
    9000, and US > 9000.
    dDefault = US 2001 --3000
    6.3.3.7. Furnace Dehumidifier Drain
    This option selects the time the continuous fan turns off at the end of cooling in
    order to drain the indoor coil of water. The fan will only be turned off if a
    dehumidify demand existed at the start of or during the cooling cycle.
    SDehumidify Drain Time:Adjustable from 5 to 60 minutes
    dDefault = 15 minutes
    6.3.3.8. Furnace G Terminal
    This setup option selects desired operation when the R--G circuit changes state on
    the furnace control board depending on setup.
    Under the function option,FA Nturns on fan to selected fan speed when G terminal
    is energized.SHUTDOWNshuts off fan and equipment when initiated.
    After the selections are made, touchSAVE.
    SFunction: Disabled, Fan or Shutdown
    dDefault = Disabled
    SFan Speed:Low,Med,orHigh
    dDefault = Low 
    						
    							32
    SShutdown:
    dNormally Open
    dNormally Closed
    6.3.4. AC/Heat Pump
    First touchSETUP, then touchAC/HEAT PUMPto set up the parameters for the
    AC/Heat Pump unit.
    A12190
    6.3.4.1. Cooling Lockout
    Outside temperature below which cooling will not be provided. After the selection
    is made, touchSAVE. 
    						