Home > Carrier > Thermostat > Carrier Systxccitn01a Manual

Carrier Systxccitn01a Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Carrier Systxccitn01a Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							43
    SHigh Heat:Selectable from 0 to 120 minutes
    dDefault = 5 minutes
    6.4.2. Furnace
    Make sure the furnace is properly installed.
    This option allows the furnace to be exercised. First, a low heat run time and high
    heat run time are selected. The furnace will execute its ignition start --up sequence.
    This sequence will be displayed on the screen. After the gas valve and blower
    motor turn on, the screen will show the current operating status of the furnace. After
    the selections are made, touchSTART.
    SLow Heat:Selectable from 0 to 120 minutes
    dDefault = 5 minutes
    SHigh Heat:Selectable from 0 to 120 minutes
    dDefault = 5 minutes
    6.4.3. Hydronic
    This option allows the hydronic heat relay to be exercised. First, it will energize the
    relay and turns on the blower. This sequence will be displayed on the screen. After
    the selections are made, touchSTART.
    SHydronic heater check:Selectable from 0 to 120 minutes
    dDefault = 5 minutes
    6.4.4. Air Conditioning
    This option allows the air conditioner to be exercised. With a 2 --stage AC unit, a
    low cool and a high cool run time are independently selectable to exercise. The
    display will change to show the AC operating status. After the selections are made,
    touchSTART. 
    						
    							44
    NOTE: Airflows during Checkout modes are fixed to theEFFICIENCYsetting
    and are independent of other airflow settings. To view airflows for normal air
    conditioning cooling mode, exit theCHECKOUTscreen and apply a heating
    demand to the system.
    SLow Cool Run Time:Selectable from 0 to 120 minutes
    dDefault = 5 minutes
    SHigh Cool Run Time:Selectable from 0 to 120 minutes
    dDefault = 5 minutes
    6.4.5. Heat Pump Heating
    The heat pump heating mode can be exercised with this menu option. With a
    2 --stage heat pump, a Low Heat and a High Heat Run Time are independently
    selectable to exercise.
    For variable speed heat pumps, you can select the speed at which the heat pump
    will exercise.
    After the selections are made, touchSTART.
    NOTE: Airflows during Checkout modes are fixed to theEFFICIENCYsetting
    and are independent of other airflow settings. To view airflows for normal air
    conditioning cooling mode, exit theCHECKOUTscreen and apply a heating
    demand to the system.
    SLow Heat Run Time:Selectable from 0 to 120 minutes
    dDefault = 5 minutes
    SHigh Heat Run Time:Selectable from 0 to 120 minutes
    dDefault = 5 minutes
    SSpeed (variable speed heat pump only):Selectable from lowest available to
    100%
    dDefault = lowest available as specified by variable speed heat pump 
    						
    							45
    SDefrost:Ye s o r N o
    dDefault = No
    6.4.6. Heat Pump Cooling
    The heat pump cooling mode can be exercised with this menu option. With a
    2 --stage heat pump, a Low Cool Run Time and a High Cool Run Time are
    independently selectable to exercise.
    For variable speed heat pumps, you can select the speed at which the heat pump
    will exercise.
    After the selections are made, touchSTART.
    NOTE: Airflows during Checkout modes are fixed to theEFFICIENCYsetting
    and are independent of other airflow settings. To view airflows for normal air
    conditioning cooling mode, exit theCHECKOUTscreen and apply a heating
    demand to the system.
    SLow Cool Run Time:Selectable from 0 to 120 minutes
    dDefault = 5 minutes
    SHigh Cool Run Time:Selectable from 0 to 120 minutes
    dDefault = 5 minutes
    SSpeed (variable speed heat pump only):Selectable from lowest available to
    100%
    dDefault = lowest available as specified by variable speed heat pump
    6.4.7. Humidifier
    The humidifier can be exercised On and Off with this menu option. To end the
    humidifier checkout, touchSTOP.
    SHumidifier Check:On or Off 
    						
    							46
    6.4.8. Ventilator
    The ventilator can be exercised through all of its operating speeds with this menu
    option. To end the ventilator checkout, touchSTOP.
    SHumidifier Check:High, Low or Off
    6.4.9. Zoning (if applicable)
    6.4.9.1. Airflow Limits
    Because there is no bypass damper, the zone airflow limit check will allow the
    installer to assess the airflow noise generated by the system providing the
    maximum amount of airflow to each zone. TouchAIRFLOW LIMITS:When
    STARTis touched, the selected zone’s damper will fully open, all others will close,
    and the indoor unit will provide the maximum airflow for that zone (as selected in
    SETUP — ZONING, Airflow Limits). If the airflow noise is objectionable, the
    installer can select a lower airflow noise limit. If the noise is not objectionable, the
    installer should leaveHIGHselected, or evenNO LIMIT.
    NOTE: Selecting a lower airflow noise limit may decrease the homeowner’s
    comfort in that zone.
    Touch the Left () buttons to change the desired zones. Once the
    proper airflow limits are set, touchSAVE,toseeZONING CHECKOUTmenu.
    6.4.9.2. Damper/Sensor Check
    The Sensor/Damper Check allows the installer to check each zone damper for
    operation, as well as insure the zone sensor corresponds to that particular zone.
    When first initiated, the Zone 1 damper will fully open, and all other zones will
    close. Using the Left () buttons, the installer can select each zone and
    verify the damper is fully open while all other dampers remain closed. 
    						
    							47
    After proper damper operation has been verified, the installer can now check and
    verify that each Remote Room Sensor corresponds to the proper zone damper in the
    same zone. For systems with remote room sensor, temporarily disconnect any other
    zone Remote Room Sensor (at sensor location). That zone damper will now open,
    while the Zone 1 damper will close.
    For systems using Smart Sensors, the installer may press and hold the Hold and
    Mode buttons simultaneously for 3 seconds to change the zone under test. This
    should be done with each zone to verify that the zone sensor corresponds to that
    particular zone.
    Once each zone has been checked, touchDONEto return to theZONING
    CHECKOUTmenu.
    6.4.9.3. Zone Duct Assessment
    This screen shows the results from the previous duct assessment. The duct
    assessment is performed at initial start --up and at 1 P.M. or the installer selected time
    each day. If another duct assessment is desired, the service technician should
    perform a re --install of the system.
    NOTE: A Duct Assessment will automatically occur every 24 hours at selected
    time to check system static and calibrate dampers.
    Once the duct assessment is complete, touchDONEto return to theZONING
    CHECKOUTmenu.
    6.4.9.4. Sensor Type
    This option shows a list of all zones with corresponding sensor types.
    6.5. Service Information
    The Service Info menu will only show the equipment installed in the system. To
    enter this menu of options, touchSERVICE INFORMATION. 
    						
    							48
    A12196
    6.5.1. Fan Coil Status
    The fan coil status screen displays relevant information about the fan coil operation.
    To return to the previous screen, touchBACK. To exit the Service menus, touch
    DONE.
    A12197
    6.5.2. Furnace Status
    The furnace status screen displays relevant information about the furnace operation.
    To return to the previous screen, touchBACK. To exit the Service menus, touch
    DONE. 
    						
    							49
    A12198
    6.5.3. AC Status
    The AC status screen displays relevant information about the AC operation. To
    return to the previous screen, touchBACK. To exit the Service menus, touch
    DONE.
    A12199
    6.5.4. Heat Pump Status
    The heat pump status screen displays relevant information about the heat pump
    operation. To return to the previous screen, touchBACK. To exit the Service
    menus, touchDONE. 
    						
    							50
    A12200
    6.5.5. Zoning Status
    The zoning status screen displays relevant information about the zoning operation.
    To return to the previous screen, touchBACK. To exit the Service menus, touch
    DONE.
    A12201
    6.5.6. Last 10 System Faults
    This screen will show the last 10 events that occurred throughout the system. Each
    entry has the time and date incident recorded. These events are stored in the
    memory of the control and are resettable in theTHERMOSTAT SETUPscreen
    under theRESET FACTORY DEFAULTselection. Each entry shows the 
    						
    							51
    equipment that generated the event. To return to the previous screen, touchBACK.
    To exit the Service menus, touchDONE.
    A12151
    6.5.7. Run/Fault History
    This information is stored in the equipment circuit boards (if communicating) and
    displayed on the control. The indoor unit and outdoor unit (if communicating) have
    the following histories. To return to the previous screen, touchBACK.To exitthe
    Service menus, touchDONE.
    SResettable Faults:Fault counters for each piece of equipment that can be reset.
    SCycle Counters:Number of heat/cool/power cycles the unit has performed.
    SRun Times:Lifetime hours of operation in heating, cooling, and how long the
    unit has been powered. 
    						
    							52
    A12202
    6.5.8. Model/Serial Numbers
    This menu item allows the installer to view the model number and serial number (if
    available) of all communicating pieces of equipment in the system, including the
    wall control. This information resides in the original equipment circuit board(s)
    from the factory. If an equipment circuit board has been replaced, the model and
    serial number will no longer be displayed. To return to the previous screen, touch
    BACK. To exit the Service menus, touchDONE.
    6.5.9. Service Phone Number
    This menu item allows the installer to view the name and phone number that the
    homeowner can call for future service of the system. This name and phone number
    will appear to the homeowner whenever a service reminder pop --up message is
    displayed (i.e. Change Filter, etc.). To return to the previous screen, touchBACK.
    To exit, touchDONE. See Section 6.7.
    6.5.10. Energy Tracking Watt Meter
    This menu item allows the installer to view the energy usage of each piece of
    equipment connected to the system. To return to the previous screen, touchBACK.
    To exit the Service menus, touchDONE. 
    						
    All Carrier manuals Comments (0)

    Related Manuals for Carrier Systxccitn01a Manual