Page 41
33 SCooling Lockout Temp:None, 45, 50 or 55 (_F) dDefault = None 6.3.4.2. Defrost Interval Time interval at which defrost cycles can occur on a heat pump.AUTOmeans the defrost interval is optimized by the outdoor control. After the selection is made, touch SAVE. SSet Defrost Interval:30, 60, 90, 120 minutes or AUTO dDefault = 30 minutes 6.3.4.3. Low Ambient Cooling SelectingYESwill enable the low ambient cooling operation in the outdoor unit. This setting is only available with communicating outdoor...
Page 42
34 heating capacity. Reducing this value will reduce the heating capacity of the heat pump. After the selection is made, touchSAVE. SAC Heat Pump Max RPM:Adjustable from 4500 – 7000 dDefault = 4500 RPM 6.3.4.6. High Cool Latch This option sets the outside temperature above which only the high stage (of a 2 --stage outdoor unit) will run when cooling. After the selection is made, touch SAVE. SHigh Cool Latch:Selectable from 80_F--110_F(27_Cto43_C),Off,Onor Disable dDefault = Off 6.3.4.7. High Heat Latch...
Page 43
35 6.3.4.9. Brownout Disable This option turns off the high voltage brownout detection function in the outdoor unit control. After the selection is made, touchSAVE. SBrownout Disable:On or Off dDefault = Off 6.3.4.10. Energy Efficiency This option is used to input the published ratings of the installed air conditioner or heat pump as part of the energy tracking calculation. After the ratings are entered, touchSAVE. 6.3.5. Heat Source Lockout First touchSETUP, then touchHEAT SOURCE LOCKOUTSto set up the...
Page 44
36 SHP Lockout:Adjustable from 5 to 55_F(--15to13_C) or None dDefault = None SFurnace, Electric Heat or Hydronic Lockout:Adjustable from 5 to 55_F (--15to13_C) or None dDefault = None SDefrost with Furnace, Electric Heat or Hydronic:Ye s o r N o dDefault = Yes 6.3.6. Zoning (if applicable) First touchSETUP, then touchZONINGto set up the parameters for the zoning system (if applicable). A12191 6.3.6.1. Zoning Disable This option allows the installer to enable or disable zoning. After the selection is...
Page 45
37 6.3.6.2. Zone Offsets This option allows actual temperature offset for each zone, allowing calibration (or deliberate miscalibration) of each sensor. Use the Left () buttons to change the zone. After the selection is made, touchSAVE. STemperature Offset:Adjustable between --5 to 5_F(--3to3_C) dDefault = 0_F 6.3.6.3. Zone Airflow Limits Since a bypass damper is prohibited in this system, this setting is used to select the maximum allowable noise/airflow relationship into each zone based on air noise...
Page 46
38 SDuct Assessment Time:Selectable between 12 AM and 11PM dDefault = 1 PM 6.3.7. Accessories First touchSETUP, then touchACCESSORIESto set up the parameters for the accessories installed with the system. A12192 6.3.7.1. Filter With this option, the installer has the option of selecting pressure monitoring, the type of filter installed, and the time interval for cleaning. After the selections are made, touchSAVE. SPressure Monitoring (not available with Electric Air Cleaner):Enable or Disable dDefault =...
Page 47
39 6.3.7.2. Humidifier With this option, the installer has the option of selecting whether a humidifier is installed, to humidify with the fan in low speed, and the time interval for changing the humidifier pad. After the selections are made, touchSAVE. SHumidifier Installed:Ye s o r N o dHumidifier selection made during installation; otherwise default = no SChange Pad:Selectable from 1 to 24 months dDefault = 12 months SHumidify with Fan:Ye s o r N o dDefault = No 6.3.7.3. Ultraviolet Lights With this...
Page 48
40 6.3.8. Utility Curtailment Utility Saver is used to force the equipment to a lower stage (low or off) when activated by the utility company, typically during peak load times. This setup is available only if the equipment has a utility saver input (refer to outdoor equipment Installation Instructions). This setup controls the response of the equipment when the utility saver input is active.DISABLEDmeans that the curtailment function is not active.TURN OFFmeans the outdoor unit is to be turned off when...
Page 49
41 A12194SAirflow:Selectable between Off to Max in 50 CFM increments dOff = 450 CFM, MAX = (odu_size in KBTU * 400) / 12) dDefault = Off SBlower On Delay:Selectable from 0 to 240 seconds dDefault = 30 seconds SBlower Off Delay:Selectable from 0 to 240 seconds dDefault = 0 seconds 6.4. Check out TouchCHECKOUTto view the equipment installed in the system. Perform checkout test to make sure each piece of equipment is operating properly.
Page 50
42 A12195 6.4.1. Electric Heat If you have a fan coil with electric heaters, this menu item will allow the heaters to be exercised. With self--identifying electric heaters, three stages of electric heat are available to be exercised in any combination. Non --identifying heaters will only provide one stage of heat. After the selections are made, touchSTART. SLow Heat:Selectable from 0 to 120 minutes dDefault = 5 minutes SMedium Heat:Selectable from 0 to 120 minutes dDefault = 5 minutes