Home > Carrier > Air Conditioner > Carrier Em1 Manual

Carrier Em1 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Carrier Em1 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							7-1
    T--311
    SECTION 7
    EVACUATION
    7.1 INTRODUCTION
    The process of evacuation is an important step in the
    servicing and maintenance of any air conditioning
    system. The purpose of evacuation is to remove all air
    and moisture from the system in preparation for adding
    refrigerant and oil during the charging process. It is
    imperative that all air and moisture be removed from the
    system, as their presence is detrimental and will
    negatively affect performance and longevity of the
    systems components. Air remaining in the air
    conditioning system will degrade the systems cooling
    performance, while any moisture remaining in the
    system is both non-condensable and a basis for acid
    formation. Moisture is the deadly enemy of refrigeration
    systems.
    7.2 REFRIGERANT SERVICE TOOLS
    The following equipment is essential when performing
    an installation of or servicing of any Carrier Transport Air
    Conditioning system. Refer to Figure 7-2 for service
    component connections.
    1Manifold Gauge Set -Provides access to and
    monitors pressures within the system. Manifold Gauge
    Sets are available in different configurations and styles.
    3-way or 4-way, Liquid filled, with or without a sight
    glass, 3 hoses or 4 hoses, 1/4 inch or 3/8 inch manifold
    connections, etc. All are acceptable for servicing a
    Carrier Transport Air Conditioning system. Familiarize
    yourself with the proper operation of your Manifold
    Gauge Set before attempting any service.
    2R134a Low Side (Suction) Coupler -Connects
    the air conditioning system Suction Access Port to the
    Manifold Gauge Set.
    3Ri34a High Side (Discharge) Coupler -Connects
    the air conditioning system Discharge Access Port to
    the Manifold Gauge Set.
    4Vacuum Pump - 2 Stage (5 CFM Minimum) -
    Removes moisture and air from the air conditioning
    system in order to obtain required micron level.
    5Micron Gauge -Monitors the evacuation process
    in units of microns. Micron gauges can be either digital
    (electronic) or analog. When the Micron Gauge is used
    as specified by the manufacturer you can be assured all
    contaminants have been removed from the air
    conditioning system. Proper use of the Micron Gauge
    will also serve as a first indication of a leak tight system.
    6Recovery/Recycle Machine (R134a) -Recovers
    and Recycles R134a refrigerant that is present within
    the air conditioning system.
    7Refrigerant Scale -Accurately weighs the transfer
    of refrigerant into the air conditioning system.
    8Refrigerant Cylinder -Storage tank for R134a.
    9Heat Blanket -Used to increase internal
    temperature of the refrigerant cylinder, greatly
    increasing the transfer of refrigerant to the air
    conditioning system.
    10Oil Injector -Used to add additional amounts of oil
    to a closed system.11Vacuum Pump -Air and moisture are removed
    from the system by inducing a vacuum through the use
    of a vacuum pump. Carrier Transport Air Conditioning
    recommends a 5 CFM or larger vacuum pump for
    optimum evacuation in the shortest time. A vacuum,
    which is measured in microns, results when pressure is
    reduced within the system. Functionally, reducing the
    pressure results in reducing the boiling point of water
    (moisture) that may be in the system. Through the
    process of vaporization, the water (moisture) changes
    state from a liquid to a vapor and is drawn off by the
    vacuum pump and removed from the system. If properly
    completed, the system is now ready for charging.
    NOTE
    Using a compound gauge (Low Side Gauge) for
    determination of vacum level is not recom-
    mended because of its inherent inaccuracy. A
    micron gauge must always be used to insure a
    proper evacuation.
    7.2.1 Preparation
    a. Evacuate and dehydrate only after pressure leak test.
    (Refer to paragraph 9.2 .)
    b. Essential tools to properly evacuate and dehydrate
    any system include a vacuum pump (5 cfm=8 m
    3/hr)
    volume displacement) and an electronic vacuum (mi-
    cron) gauge. (The pump is available from Carrier
    Transicold, P/N 07-00176-11.)
    c. If possible, keep the ambient temperature above
    60_F (15.6_C) to speed evaporation of moisture. If
    the ambient temperature is lower than 60_F
    (15.6_C), ice might form before moisture removal is
    complete. Heat lamps or alternate sources of heat
    may be used to raise the system temperature.
    7.2.2 Procedure - Complete system
    a. Remove all refrigerant using an approved refrigerant
    recovery system, following manufacturers recom-
    mendations.
    b. The recommended method to evacuate and dehy-
    drate the system is to connect two evacuation hoses
    (see Figure 7-2) to the vacuum pump and refrigera-
    tion system. Be sure the service hoses are suited for
    evacuation purposes.
    c. Test the evacuation setup for leaks by drawing a deep
    vacuum through the manifold gauge set, hoses, and
    service couplers with the vacuum pump. Shut off the
    pump and check to see if the vacuum holds. Repair
    leaks if necessary.
    d. Open the vacuum pump and electronic vacuum (mi-
    cron) gauge valves, if they are not already open. Start
    the vacuum pump. Evacuate unit until the electronic
    vacuum gauge indicates 2000 microns. Close the
    electronic vacuum gauge and vacuum pump valves.
    Shut off the vacuum pump. Wait a few minutes to be
    sure the vacuum holds.
    e. Break the vacuum with clean dry refrigerant 134a
    gas. Raise system pressure to approximately 2 psig
    (0.2 kg/cm@), monitoring it with the compound gauge.
    f. Remove refrigerant using a refrigerant recovery sys-
    tem. 
    						
    							7-2
    T--311 g. Repeat steps d.and e. one time.
    h. Evacuate unit to 500 microns. Close the electronic
    vacuum gauge and vacuum pump valves. Shut off the
    vacuum pump. Wait five minutes to see if vacuum
    holds. This procedure checks for residual moisture
    and/or leaks.
    i. With a vacuum still in the unit, the refrigerant charge
    may be drawn into the system from a refrigerant con-
    tainer on weight scales.
    7.3 INSTALLING MANIFOLD GAUGES
    The manifold gauge set is used to determine system
    operating pressures, add refrigerant charge, and to
    equalize or evacuate the system.
    When the suction pressure hand valve is frontseated
    (turned all the way in), the suction (low) pressure can be
    checked. When the discharge pressure hand valve is
    frontseated, the discharge (high) pressure can be
    checked. When both valves are open (turned
    counter-clockwise all the way out), high pressure vapor
    will flow into the low side. When the suction pressure
    valve is open and the discharge pressure valve shut, the
    system can be charged. Oil can also be added to the
    system.
    A R-134a manifold gauge/hose set with self-sealing
    hoses is required for service of the models covered
    within this manual. The manifold gauge/hose set is
    available from Carrier Transicold. (Carrier Transicold
    P/N 07-00294-00, which includes items 1 through 6. To
    perform service using the manifold gage/hose set, do
    the following:
    a.Preparing Manifold Gauge/Hose Set For Use
    1. If the manifold gauge/hose set is new or was
    exposed to the atmosphere it will need to be eva-
    cuated to remove contaminants and air as follows:
    2. Back seat (turn counterclockwise ) both field service
    couplings (see Figure 7-1) and midseat both hand
    valves.
    3. Connect the yellow hose to a vacuum pump.
    4. Evacuate to 10 inches of vacuum.
    5 Connect yellow line to R134a cylinder, purge line,
    then charge with to a slightly positive pressure of 0.1
    kg/cm@(1.0 psig).
    6. Front seat both manifold gauge set valves and dis-
    connect from cylinder. The gauge set is now ready
    for use.
    b.Connecting Manifold Gauge/Hose Set
    Connection of the manifold gauge/hose set (see
    Figure 7-2) is dependent on the type system being
    serviced. The center hose connection is brought to the
    tool being used. To connect the manifold gauge/hose
    set, do the following.
    1. Connect the high side field service coupling to the
    discharge line service valve port.2. Turn the high side field service coupling knob (red)
    clockwise, which will open the high side of the sys-
    tem to the gauge set.
    3. Connect the low side field service coupling to the
    suction service valve port.
    4. Turn the low side field service coupling knob (blue)
    clockwise, which will open the low side of the system
    to the gauge set.
    CAUTION
    To prevent trapping liquid refrigerant in the
    manifold gauge set be sure set is brought to
    suction pressure before disconnecting.
    OPENED
    (Backseated )
    HAND VALVECLOSED
    (Frontseated)
    HAND VALVE SUCTION
    PRESSURE
    GAUGEDISCHARGE
    PRESSURE
    GAUGE
    To Low Side
    Access ValveTo High Side
    Access Valve
    Red Knob Blue Knob
    1
    43
    YELLOW2
    4
    5 63
    RED 3
    BLUE
    2
    1. Manifold Gauge Set
    2. Hose Fitting (0.5-16 Acme)
    3. Refrigeration and/or Evacuation Hose
    . (SAE J2196/R-134a)
    4. Hose Fitting w/O-ring (M14 x 1.5)
    5. High Side Field Service Coupling
    6. Low Side Field Service Coupling
    Figure 7-1 Manifold Gauge Set
    c.Removing the Manifold Gauge Set
    1. Midseat both hand valves on the manifold gauge set
    and allow the pressure in the manifold gauge set to
    be drawn down to suction pressure. This returns any
    liquid that may be in the high side hose to the system.
    2. Backseat both field service couplings and frontseat
    both manifold set valves. Remove the couplings
    from the service ports.
    3. Install both service port caps (finger-tight only). 
    						
    							7-3
    T--311
    TXV
    EVAPORATOR COIL
    CONDENSER COILFILTER DRYERSIGHT GLASS SUCTION ACCESS
    HPS
    LPS DISCHARGE
    ACCESS
    COMPRESSOR
    LPS (New Location GEN 5)
    (GEN 4
    Location)
    DS
    12 3
    4 5 6
    7
    1. Vacuum Pump
    2. Micron Gauge
    3. Manifold Gauge Set
    4. Refrigerant Cylinder5. Recovery/Recycle Machine
    6. R134a High (Discharge) Side Coupler
    7. R134a Low (Suction) Side Coupler
    Figure 7-2 Refrigerant Service Connections (Split Systems) 
    						
    							8-1T--311
    SECTION 8
    CHARGING PROCEDURES
    8.1 INTRODUCTION
    Charging is the process of calculating and then
    introducing the correct amounts of refrigerant and oil
    into the air conditioning system. Accurate charge levels
    will result in optimum system performance and insure
    the longevity of the system components.
    8.1.1 Proper R134a Charge.
    A system overcharged with refrigerant operates under
    high head pressure which can damage components. A
    system undercharged with refrigerant will result in poor
    system performance.
    NOTE
    An overcharged or undercharged system may
    contribute to system compressor failure.
    Calculations for determining the proper refrigerant
    charge are based on component capabilities and liquid
    line lengths as indicated on Carrier Transport Air
    Conditioning charging tables. Refer to Table 8-1 or
    Table 8-2 for the approximate refrigerant charge. Refer
    to Table 8-4 to determine the exact refrigerant charge.8.1.2 Proper Oil Charge.
    Accurate charge levels of oil with the refrigerant are also
    critical to proper performance and component longevity.
    A system undercharged with oil will result in reduced
    compressor life due to lack of lubrication. A system
    overcharged with oil will experience poor system
    performance due to reduced thermal transfer
    capabilities. Refer to Table 8-1 or Table 8-2 for the
    approximate oil amounts. Refer to Table 8-3 for the
    correct compressor oil type.
    8.1.3 Liquid Charging.
    The practice of charging liquid refrigerant into the
    suction side with the compressor running will damage or
    destroy the compressor, as the liquid is not
    compressible.
    8.1.4 PAG And POE Oils.
    It is very important to use the lubricant type specified by
    the compressor manufacturer. (Refer to Table 8-3).
    Using oil other than the specified oil can result in
    reduced performance and a reduction in compressor
    life.
    NOTE
    Using oil other than that specified in Table 8-3
    will void the compressor warranty.
    Table 8-1 SPLIT SYSTEM REFRIGERANT AND OIL CHARGING TABLE (THROUGH GEN 4)
    Evaporator
    Up to GEN 5
    Condenser
    All SeriesRecommended
    R134a ChargeRecommended
    Oil Charge*
    EM-1, EM-2, or EM-9CM-25.00 Pounds10.0 Ounces
    EM-1, EM-2, or EM-9CM-115.25 Pounds10.5 Ounces
    EM-6CM-24.00 Pounds8.0 Ounces
    EM-6CM-114.25 Pounds8.5 Ounces
    EM-1, EM-2, or EM-9CM-35.50 Pounds11.0 Ounces
    EM-1, EM-2, or EM-9CM-76.50 Pounds13.0 Ounces
    EM-3(2) CM-24.25 Pounds Each8.5 Ounces Each
    EM-3(2) CM-76.25 Pounds Each12.5 Ounces Each
    EM-3(2) CM-35.50 Pounds Each11.0 Ounces Each
    EM-3(2) CM-76.25 Pounds Each12.5 Ounces Each
    EM-14CM-23.50 Pounds7.0 Ounces
    EM-14CM-113.75 Pounds7.5 Ounces
    EM-17CM-519.0 PoundsConsult Factory
    EM-17KR-413.0 PoundsConsult Factory
    EM-17 Split System(2) CM-36.00 Pounds Each12.0 Ounces Each 
    						
    							8-2 T--311Table 8-2 SPLIT SYSTEM REFRIGERANT AND OIL CHARGING TABLE (GEN 5)
    Evaporator
    GEN 5
    Condenser
    All SeriesRecommended
    R134a ChargeRecommended
    Oil Charge*
    GEN 5 - EM-1CM-2 or CM-44.75 Pounds9.5 Ounces
    GEN 5 - EM-1CM-115.00 Pounds10.0 Ounces
    GEN 5 - EM-1CM-35.25 Pounds10.5 Ounces
    GEN 5 - EM-1CM-76.25 Pounds12.5 Ounces
    GEN 5 - EM-7CM-2 or CM-44.00 Pounds8.0 Ounces
    GEN 5 - EM-7CM-114.25 Pounds8.5 Ounces
    GEN 5 - EM-2CM-2 or CM-44.50 Pounds9.0 Ounces
    GEN 5 - EM-2CM-114.75 Pounds9.5 Ounces
    GEN 5 - EM-2CM-35.00 Pounds10.0 Ounces
    GEN 5 - EM-2CM-76.00 Pounds12.0 Ounces
    The data listed in Table 8-1 and Table 8-2 is based on a
    20 foot liquid line. Increase the charge by 0.5 pound for
    each additional 10 feet of liquid line.
    8.1.5 Evaporator Tie-In.
    When an after market in-dash evaporator is added to a
    standard system the refrigerant charge will increase by
    approximately 1 pound.
    If attempting to use a CM-2 condenser with a tie-in call
    Carrier Transport Air conditioning technical support for
    an application review.
    Table 8-3 COMP. OIL TYPE & PART NUMBERS
    Manufacturer
    Oil TypePart Number
    Tama/Zexel/IcePA G07-00336-00
    SandenPA G07-00335-00
    General MotorsPA G46-50003-00
    DodgePA G07-00332-00
    FordPA G07-00334-00
    Climate ControlPOE07-00317-00
    For questions regarding charging procedures, call
    Carrier Transport Air Conditioning technical support at
    1-800- 450-2211.8.1.6 Adding Refrigerant to System (Full Charge).
    a. Evacuate unit and leave in deep vacuum.
    b. Place cylinder of R-134a on scale and connect charg-
    ing line from cylinder to liquid line valve. Purge charg-
    ing line at liquid line valve and then note weight of cyl-
    inder and refrigerant.
    c. Calculate the approximate refrigerant charge using
    either Table 8-1 or Table 8-2. Open liquid valve on re-
    frigerant cylinder. Open suction line service port cou-
    pler and allow the liquid refrigerant to flow into the unit
    until the correct weight of refrigerant has been added
    as indicated by scales.
    NOTE
    It may be necessary to finish charging unit
    through suction service port in gas form, due to
    pressure rise in high side of the system.
    d. Close suction line service port coupler. Close liquid
    valve on cylinder.
    e. Start unit in cooling mode. Run approximately 10 min-
    utes and check the refrigerant charge. (Refer to
    Table 8-4). 
    						
    							8-3T--311 Table 8-4 CARRIER TRANSPORT AIR CONDITIONING SYSTEM PERFORMANCE CHART
    Determine the approximate refrigerant charge using Table 8-1 or Table 8-2 .
    Follow the procedures listed below to determine if the correct charge has been obtained.
    Ta b l e
    ProcedureYour EntryExample
    Pres-
    sureRefrigerant Temp.1.Connect Manifold Gauge Set To
    Air ConditioningSystemNONENONEPSIGR-12R134a
    AirConditioningSystem
    Certified Air Conditioning MechanicNONENONE
    (A)(B)(C)
    CertifiedAirConditioningMechanic
    Only
    958785
    10090882.Measure outside(ambient)air
    1059390
    2.Measureoutside(ambient)air
    temperature.DegreesF100DegreesF11 09693Enter here ------------ -->______DegreesF100DegreesF
    11 59996
    12010298
    125104100
    40DF40DF1301071033.Add 40 degrees F to the outside
    (bit)itt
    40 Degrees F
    DegreesF
    40 Degrees F
    140DegreesF135109105(ambient) air temperature --->______DegreesF140DegreesF
    14011 2107
    14511 4109
    15011 711 2
    15511 911 44.Find closest refrigerant
    temperatureinTableDegreesF139DegreesF16012111 6temperatureinTable
    (B or C) and enter here --- -->______DegreesF139DegreesF
    16512311 8
    (BorC)andenterhere>
    170126120
    175128122
    1801301235. Going across the Table, find the
    di(A)(D)=PSI225PSI185132125corresponding pressure (A) -->(D)=______PSI225PSI
    190134127
    195136129
    2001381316.If the Discharge Pressure
    (HighSide)ongaugers205140132(HighSide)on gaugers
    (With compressor engaged,
    210142134
    (Withcompressorengaged,
    engine speed 1200 RPM, and
    215143136
    enginespeed1200RPM,and
    system operating) is :
    220145137
    Gtth(D)Rdfit
    ******
    225147139Greater than (D) - Reduce refrigerant
    by4ounceincrements235150142by 4 ounce increments.
    245154145Lessthan(D)-Addrefrigerant255157148Lessthan(D)-Addrefrigerant
    265160151Wait 10 minutesfor system to
    275163153
    Wait10minutesforsystemto
    stabilize before taking new readings 
    						
    							9-1 T-- 311
    SECTION 9
    LEAK CHECKING
    9.1 INTRODUCTION
    The purpose of leak checking is to verify the integrity of
    the hose/fitting connections and components. A
    refrigerant leak check should always be performed after
    installing a new system or the system has been opened
    to replace or repair a component. It is imperative that the
    inspection for refrigerant leaks be conducted in a
    through and meticulous manner. Even the smallest leak
    can result in poor system performance and premature
    compressor failure. When a leak occurs, the refrigerant
    is replaced by air and moisture from outside the system.
    Without a complete charge of refrigerant in the system,
    insufficient oil is returned to the compressor. The
    compressor will overheat and eventually fail. Following
    established leak checking procedures will result in long
    term performance and assure longevity of the system
    components.
    9.1.1 Micron (Vacuum) Gauge
    Carrier Transport Air Conditioning recommends a
    Micron (Vacuum) Gauge to assure that the proper
    vacuum level is attained. When isolated according to
    instructions the Micron Gauge will show a loss of
    evacuation vacuum, making it an excellent first leak
    check.
    9.1.2 Nitrogen
    A common method in use for leak detection, is
    pressurizing the system with dry nitrogen and checking
    with a soap bubble solution at suspected leak sites.
    While this method will find large leaks, it is limited in
    detection of the smaller leaks found with R134a.
    WARNING
    DO NOT USE A NITROGEN CYLINDER
    WITHOUT A PRESSURE REGULATOR
    NOTE
    If the system is to be pressurized with refriger-
    ant gas it must be emphasized that only the cor-
    rect refrigerant cylinder be connected to pres-
    surize the system. Any other gas or vapor will
    contaminate the system, which will require
    additional evacuations (Refer to Figure 9-1 for
    service connections).9.2 REFRIGERANT LEAK CHECKING
    WARNING
    Never use air for leak testing. It has been de-
    termined that pressurized, air-rich mixtures
    of refrigerants and air canundergo com-
    bustion when exposed to an ignition
    source.
    a. Charge the system with refrigerant 134a to build up
    pressure between 30 to 50 psig.
    b. Add sufficient nitrogen to raise system pressure
    to150/200 psig. (10.21/13.61 bar).
    Note
    Larger split systems may be equipped with ser-
    vice valves and a liquid line solenoid. Ensure
    these service valves are open and power the
    liquid line service valve from an external
    source.
    c. The recommended procedure for finding leaks in a
    system is with a R-134a electronic leak detector (CTD
    Part Number 07-00295-00). Testing joints with soap-
    suds is satisfactory only for locating large leaks.
    d. Remove refrigerant using a refrigerant recovery sys-
    tem and repair any leaks.
    e. Evacuate and dehydrate the unit (Refer to Section 7).
    f. Charge the unit. (Refer to Section 8). 
    						
    							9-2 T--311
    TXV
    EVAPORATOR COIL
    CONDENSER COILFILTER DRYERSIGHT GLASS SUCTION ACCESS
    HPS
    LPS DISCHARGE
    ACCESS
    COMPRESSOR
    LPS
    (New Location GEN 5)
    (GEN 4
    Location)
    DS
    1 7
    6
    5
    43
    2
    1. Vacuum Pump
    2. Micron Gauge
    3. Manifold Gauge Set
    4. Refrigerant Cylinder5. Recovery/Recycle Machine
    6. R134a High (Discharge) Side Coupler
    7. R134a Low (Suction) Side Coupler
    Figure 9-1 Refrigerant Service Connections (Split Systems) 
    						
    							T--311
    10-1
    SECTION 10
    WARRANTY REGISTRATION
    10.1 INTRODUCTION
    The warranty registration process is an important part of
    the installation of any air conditioning system. In order to
    experience the full benefits of Carrier Transport Air
    Conditioning’s warranty, it is imperative that your
    system is registered completely and accurately. Failure
    to properly register the system will adversly affect the
    availability of warranty coverage. A properly registered
    system will enable Carrier Transport Air Conditioning to
    respond immediately in the event of a warrantable
    failure.
    10.2 PROCEDURES
    Locate the warranty registration card that is inclosed
    with the installation kit. (See Figure 10-1).
    The warranty registration card consists of three (3)
    copies.
    1. Yellow copy:Installer copy:
    a. Completely fill out all Installer and Product informa-
    tion. Date of Installation, Installer Name, Address,
    City, State, Zip code and Phone number.
    b. When Purchaser information is known, the installer
    can complete this part of the form also.c. If the Warranty Registration Card is complete, the
    white (pre-addressed) copy can be mailed to Carrier
    Transport Air Conditioning at this time.
    d. Installer to keep yellow copy for file.
    e. Installer to forward (with bus) green and white copy
    to purchaser (end-used).
    2. Green copy:Purchaser (End User) copy:
    a. Complete Purchaser copy, sign, then mail white
    (pre-addressed) copy to Carrier Transport Air Condi-
    tioning.
    b. Purchaser (end user) to keep green copy for file.
    NOTE
    The Carrier Transport Air Conditioning limited
    warranty is printed on the back of the purchaser
    (green) copy.
    3. White Copy:Carrier Transport Air Conditioning
    copy:
    a. Must be mailed to Carrier Transport Air Conditioning
    in order to validate the system warranty.
    Figure 10-1 Warranty Registration Card
    10.3 WARRANTY POLICY
    10.3.1 In-Line Failures - OEM/Installer Repair
    Refer to Warranty Policy, Procedures & LaborAllowance Manual (62-02737) for instructions on
    returning, replacing or repairing any parts that were
    defective at time of installation. Or call Carrier Transport
    Air Conditioning Technical Support Hot-Line (800)
    450-2211) for assistance. 
    						
    							T--311
    11 - 1
    SECTION 11
    FINAL (CHECK-OUT SHEET)
    INSTALLATION CHECK-OUT
    The installation checkout procedure is an important step in the installation of any air conditioning system. The reason
    for the installation checkout procedure is to insure that all Carrier Transport Air Conditioning standards of installation
    quality have been met. An itemized checkout form will help you in the checkout process and will provide a device for
    permanently recording your findings. The form that follows this introduction represents a guideline, that can be used as
    is, or as a starting point for the development of your own custom installation checkout sheet. A correctly completed
    final checkout will guarantee a quality installation that will last the life of the bus.
    GENERAL INFORMATION
    BUS MODEL/BODY_______________________BUS VIN#__________________________________
    CARRIER TAC SYSTEM___________________EVAP’S_______COND’S_______COMP’S_______
    ENGINE AREA:
    YES NO
    ____ ____
    Is compressor and compressor mount secure?
    ____ ____Were bolts torqued to proper specifications when noted on mount kit drawing?
    ____ ____Is there good alignment between the compressor, idler and crank pulley? Always use a
    straight edge to determine alignment. Eye sighting is not good enough!
    ____ ____Were belts tightened per manufacturers recommendations?
    ____ ____Are refrigerant hoses routed through the engine compartment to the compressor
    correctly? Refrigerant hose must be protected from heat sources and sharp objects!
    Refrigerant hose should be supported with insulated clamps wherever possible.
    ____ ____Was mineral oilused to lubricate the fittings, hose and O Rings?
    ____ ____Was excess oil wiped from fittings and hose?
    ____ ____Is 12.5 Volts available at the compressor clutch?
    ____ ____Are the Quick-Click fittings clamped to the Quick-Click refrigerant hose correctly?
    CONDENSER AREA:
    YES NO
    ____ ____
    Is the condenser(s) mounted securely to the bus floor?
    ____ ____ Is condenser(s) mounted as close as possible to bus skirt? If condenser cannot be
    mounted close to the skirt, a shroud must be installed to prevent re-circulation of heat.
    ____ ____ Is bus skirt cut out to allow maximum airflow across the coil? Cut out must beat
    least as large as the condenser coil to allow for maximum heat rejection. 
    						
    All Carrier manuals Comments (0)