Carrier Em1 Manual
Have a look at the manual Carrier Em1 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
vi T-311 LIST OF ILLUSTRATIONS -- Continued FigurePage ................................................................................. Figure 5-4 Drivers Control Panel 5-2............................................................. Figure 5-5 Controls Mounted Without Panel 5-2................................................... Figure 5-6 Drivers Control Panel (Dual Systems) 5-3.............................................. Figure 5-7 Electrical Control Panel (Typical) 5-3................................................... Figure 5-8 Total Control Key Pad/Display 5-3..................................................... Figure 5-9 Total Control Electrical Panel (Typical) 5-4.............................................. Figure 5-10 Gen 5 Total Control (Dual System) 5-4................................................ Figure 6-1 Metric Torque Specs 6-2............................................................. Figure 6-2 Metric Bolt Markings 6-2............................................................. Figure 6-3 U.S.S. Torque Specs 6-2............................................................. Figure 6-4 U.S.S. Bolt Markings 6-2............................................................. Figure 6-5 Belt Clearance Requirements 6-3..................................................... Figure 6-6 Belt Misalignment6-3 ................................................................ Figure 6-7 Straight-- Edge Application 6-3......................................................... Figure 6-8 Belt Tension Guide6-4 ............................................................... Figure 6-9 Compressor Mounting Angles 6-5..................................................... Figure 7-1 Manifold Gauge Set 7-2.............................................................. Figure 7-2 Refrigerant Service Connections (Split Systems) 7-3..................................... Figure 9-1 Refrigerant Service Connections (Split Systems) 9-2..................................... Figure 10-1 Warranty Registration Card 10-1..................................................... Figure 11-1 System Requirements Label 11-5.................................................... LIST OF TABLES Ta b l ePage .................................................................................. Table 1-1 ADDITIONAL SUPPORT MANUALS 1-1................................................ Table 1-2 CARRIER TRANSPORT AIR CONDITIONING SYSTEMS (GEN 4/5) 1-2.................... Table 1-3 GEN 4 EVAPORATORS 1-6............................................................ Table 1-4 GEN 5 EVAPORATORS 1-6............................................................ Table 1-5 CONDENSERS (Used With GEN 4 And GEN 5 Series) 1-7................................. Table 2-1 GEN 4 EVAPORATORS 2-2............................................................ Table 2-2 GEN 5 EVAPORATORS 2-2............................................................ Table 2-3 DISTANCE TO BACK WALL (GEN 4) 2-3................................................ Table 2-4 DISTANCE TO BACK WALL (GEN 5) 2-3................................................ Table 3-1 CONDENSERS (Used With GEN 4 And GEN 5 Series) 3-2................................. Table 3-2 SKIRT MOUNTED CONDENSERS 3-2.................................................. Table 8-1 SPLIT SYSTEM REFRIGERANT AND OIL CHARGING TABLE (THROUGH GEN 4) 8-1....... Table 8-2 SPLIT SYSTEM REFRIGERANT AND OIL CHARGING TABLE (GEN 5) 8-2................. Table 8-3 COMP. OIL TYPE & PART NUMBERS 8-2............................................... Table 8-4 CARRIER TRANSPORT AIR CONDITIONING SYSTEM PERFORMANCE CHART 8-3........
T--311 1-1 SECTION 1 DESCRIPTION 1.1 INTRODUCTION This manual contains instructions for the proper preparation of and installation of Carrier Transport Air Conditioning split systems. This manual does not replace proper training and/or certification required by the EPA or other local agencies. The purpose of this manual is to assist you in completing a quality, trouble-free installation which will compliment a quality product, and ensure optimum system performance for the life of the vehicle. While this manual does not cover all combinations, variations, and details, it does set up standards from which installation processes can be measured. Common sense and care for quality will result in superior installations and customer satisfaction. A Split System normally includes an evaporator(s), a condenser(s) a compressor(s) and interconnecting refrigerant hoses, fittings, and electrical harnesses and controls. Refer to Table 1-3 & Table 1-4 for evaporator models and Table 1-5 for condenser models. Table 1-2 shows popular system designations. Additional support manuals are listed in Table 1-1. When in doubt about a particular installation or if you require additional information, do not hesitate to call Carrier Transport Air Conditioning technical service Hot Line for assistance (800-450-2211). 1.2 WHAT IS AIR CONDITIONING Air Conditioning is the cooling, dehumidification, and filtration of the air located within the passenger compartment of your vehicle. 1.3 SYSTEM NOMENCLATURE DESIGNATIONS All Carrier Transport Air Conditioning split system applications will have system numbers consisting of 2 letters followed by 3 or more numbers (ie. AC-512), identifying them as a free blow or ducted system, approximate BTU rating, type of evaporator assembly and type of condenser assembly. The letter “A” from the letters “AC” means this systems evaporator(s) are free blow units.The letter “D” from the letters “DC” means this systems evaporator(s) are corner ducted. The first number after the letters “AC” or “DC” is the capacity of the system in BTU”s to the nearest 10 thousand. (Example - 26,000 BTU’s would be rounded off to 30,000 BTU’s, or the number 3.) The second and third numbers designate the evaporator(s) assembly. The fourth and fifth numbers designate the condenser(s) assembly. When only three numbers are in the designation, the second number is the evaporator and the third number is the condenser. (Example - AC-512 = AC designates a free-blow system, 5 means approximately 50,000 BTU, 1 is an EM-1 evaporator assembly, while the 2 designates a CM-2 condenser assembly). 1.3.1 Model And Serial Number Tags In order to identify the air conditioning system you are installing, you will need to know the model number and serial number. All Carrier Transport Air Conditioning system components have a model and serial number data tag located on each evaporator and condenser assembly. See Figure 1-1 for skirt mounted condenser data tag location, Figure 1-2 for GEN 4 evaporator data tag location, Figure 1-3 for GEN 5 evaporator data tag location and Figure 1-4 for the CM-7 & CM-11 rooftop condensers data tag location. Knowing these locations and the information on the data tags will aid you in completing the Warranty Registration Card (refer to Section 10), and if needed, ordering the correct replacement parts. NOTE The EM-9 evaporator data tag is located on the side of the evaporator assembly, not between the blower assemblies. 1.3.2 System Requirements Label The system requirements label (See Figure 11-1) is filled out after the installation and is affixed as close to the vehicle compressor as possible. Refer to paragraph 11.1 for instruction on completing the system requirements label. Table 1-1 ADDITIONAL SUPPORT MANUALS MANUAL NUMBER EQUIPMENT COVEREDTYPE OF MANUAL T-299Split SystemsOperation & Service T-299PLSplit SystemsParts List 62-10686Split SystemsInstallation Video 62-50455Basic RefrigerationService Training 62-50468Transport RefrigerationService Training 62-03213Service ToolsService Tools 62-02737Transport Air ConditioningWarranty Policy & Procedures
T--311 1-2 Table 1-2 CARRIER TRANSPORT AIR CONDITIONING SYSTEMS (GEN 4/5) SYSTEM TYPEBTUEVAP (S)COND (S)COMP (S) AC-3140FB26,000(1) EM-14OEMOEM AC-360FB30,000(1) EM-6OEMOEM AC-3142FB26,000(1) EM-14(1) CM-2(1) 10 CID AC-362FB30,000(1) EM-6(1) CM-2(1) 10 CID AC-422FB40,000(1) EM-2(1) CM-2(1) 10 CID AC-512FB48,000(1) EM-1(1) CM-2(1) 10 CID AC-513FB52,000(1) EM-1(1) CM-3(1) 10 CID AC-633FB60,000(1) EM-3(1) CM-3(1) 12.6 CID AC-8322FB78,000(1) EM-3(2) CM-2(2) 10 CID AC-82222FB80,000(2) EM-2(2) CM-2(2) 10 CID AC-91223FB92,000(1) EM-1, (1) EM-2(1) CM-2, (1) CM-3(2) 10 CID AC-11122FB96,000(2) EM-1(2) CM-2(2) 10 CID DC-19922CD96,000(2) EM-9(2) CM-2(2) 10 CID AC-11133FB104,000(2) EM-1(2) CM-3(2) 10 CID DC-19933CD104,000(2) EM-9(2) CM-3(2) 10 CID AC-16333FB108,000(1) EM-3, (1) EM-6(2) CM-3(2) 10 CID DC-12175CD120.000(1) EM-3(1) CM-5(1) 05K or 05G LEGEND: FB = Free Blow CD = Corner DuctedEM = Evaporator Module CM = Condenser Module CID = Cubic Inch Displacemrnt Figure 1-1 Condenser Model - Serial Number Location EM-9 Location Figure 1-2 GEN 4 Evaporator Model - Serial Number Location
T--311 1-3 Figure 1-3 GEN 5 Evaporator Model - Serial Number Location Figure 1-4 CM-7/11 Rooftop Condensers - Serial Number Location 1.4 SYSTEM COMPONENTS 1. Thermostat - A thermostat is a temperature sensitive device, which when activated, signals the electro-magnetic clutch to engage. 2. Electro-Magnetic Clutch - The electro-magnetic clutch controls the operation of the compressor. When engaged, the compressor circulates refrigerant and provides cooling (See Figure 1-5). 3. Compressor - The compressor is a belt driven, high-pressure pump, which circulates the refrigerant through the evaporator and condenser (See Figure 1-5). The operation of the compressor is controlled by the electro-magnetic clutch, which in turn is controlled by the thermostat. 4. Condenser - The condenser is normally located in the skirt or on the roof of the bus (vehicle), (See Figure 1-5). Its primary function is to reject heat, whichwas transferred to the refrigerant by the evaporator from the passenger compartment of the bus (vehicle). 5. Filter/Dryer - The filter/dryer removes moisture and particulate matter from the refrigerant (See Figure 1-5). 6. Expansion Valve/Block Valve - Meters the refrigerant flow into the evaporator coil. 7. Evaporator - The evaporator is located in the interior of the bus (vehicle) (See Figure 1-5). Its primary function is to transfer heat contained in the passenger compartment air, into the refrigerant, which is circulated by the compressor, through the evaporator coil. During this process the air is also filtered and dehumidified 8. Refrigerant - A refrigerant is any material that possesses high heat transfer capabilities. Its primary function is to act as the medium for heat transfer, which facilitates the movement of heat from the passenger compartment to the outside air. Refrigerant under varying pressures exists in different states, and
T--311 1-4 performs different heat transfer functions. Under low pressure, refrigerant exists as a gas that can absorb heat. under high pressure, refrigerant exists as a liquid that can reject heat. The heat transfer propertiesexhibited when refrigerant changes state is the foundation of the refrigerant cycle. 1 234 56 7Ambient Air InCool Air Out 1. Compressor 2. Discharge Line (hot gas) 3. Condenser 4. Liquid Line5. Filter Dryer 6. Evaporator 7. Suction Line Figure 1-5 Refrigerant Flow and Typical Component Locations 1.5 COOLING CYCLE The unit operates as a vapor compression system using R-134a as the refrigerant (See Figure 1-6). The compressor raises the pressure and the temperature of the refrigerant and forces it thru the discharge lines into the condenser tubes. The condenser fan circulates surrounding air (which is at a temperature lower than the refrigerant) over the outside of the condenser tubes. Heat transfer is established from the refrigerant (inside the tubes) to the condenser air (flowing over the tubes). The condenser tubes have fins designed to improve the transfer of heat from the refrigerant gas to the air; this removal of heat causes the refrigerant to liquify. Liquid refrigerant leaves the condenser and flows to the filterdrier. The filter drier contains a medium (absorbent) that keeps the refrigerant clean and dry. From the filter-drier, the liquid refrigerant then flows to the block type expansion valve. The expansion valve reduces pressure and temperature of the liquid and meters the flow of liquid refrigerant to the evaporator to obtain maximum use of the evaporator heat transfer surface. The low pressure, low temperature liquid that flows into the evaporator tubes is colder than the air that is circulated over the evaporator tubes by the evaporator fans. Heat transfer is established from the evaporator air (flowing over the tubes) to the refrigerant (flowing inside the tubes). The evaporator tubes have fins to increase heat transfer from the air to the refrigerant;
T--311 1-5 therefore the cooler air is circulated to the interior of the vehicle. The transfer of heat from the air to the low temperature liquid refrigerant in the evaporator causes the liquid tovaporize. This low temperature, low pressure vapor refrigerant then continues through the suction line and returns to the compressor where the cycle repeats. 1 234 5 6 78 9 10 1. Compressor 2. Electro-Magnetic Clutch 3. Discharge Line 4. Condenser 5. Filter Dryer6. Liquid Line 7. Evaporator 8. Block Valve 9. Thermostat-(Freeze-Up) 10. Suction Line Figure 1-6 Refrigerant Flow Diagram
T--311 1-6 1.6 EVAPORATORS Evaporators are located in the interior of the vehicle. Their primary function is to transfer heat contained in the passenger compartment into the refrigerant. The evaporators may be free blow mounted in the front, side or rear of the vehicle (bus) to blow directly into theinterior or ducted to distribute the air in a planned pattern, (the EM-20 is designed to sit on the vehicle’s floor). Refer to Table 1-3 (Gen 4) and Table 1-4 (Gen 5) for Carrier Transport Air Conditioning evaporator assemblies, their approximate CFM, Amp draw, weight, and cooling/heating BTU’s. Table 1-3 GEN 4 EVAPORATORS Component Ty p eCFM (Approx)Amps (High Speed)WeightBTU Cooling (Approx)BTU Heating (Optional) EM-1 GEN 4FB - F/R/[email protected] Lbs.52,00060,000 EM-2 GEN 4FB - F/R/[email protected] 10@25V55 Lbs.39,00040,000 EM-3 GEN 4FB - [email protected] 26@25V96 Lbs.86,00070,000 EM-6 GEN 4FB - F/R/[email protected] 10@25V56 Lbs.30,00030,000 EM-9DT - [email protected] Lbs.52,00060,000 EM-10DT - RM206057@25V150 Lbs86,00090,000 EM-14FB or [email protected] 12@25V35 Lbs.26,00035,000 EM-17RM - DT206057@25V196 Lbs.125,00090.000 EM-20FL - MT - [email protected] 12@25V30 Lbs.27,00035,000 EM-21AMB - FB - [email protected] Lbs.27,00035,000 EM-22FB - [email protected] 12@25V40 Lbs.25,00030,000 IW-1FB - [email protected] Lbs.43,000Not Available IW-2FB - [email protected] Lbs.28,000Not Available IW-7FB - [email protected] Lbs.20,000Not Available IW-14FB - [email protected] Lbs.30,000Not Available Table 1-4 GEN 5 EVAPORATORS Component Ty p eCFM (Approx)Amps (High Speed)WeightBTU Cooling (Approx)BTU Heating (Optional) EM-1FB - F/R/[email protected] 16@25V60 Lbs.53,000Not Available EM-2FB - F/R/[email protected] 12@25V49 Lbs.43,000Not Available EM-3FB - [email protected] 24@25V90 Lbs.90,000Not Available EM-7FB - F/R/[email protected] 10@25V41 Lbs.35,000Not Available LEGEND: AMB Ambulance Unit DT Ducted Unit FM Front Mount FW Front Wall Mounted IW In-Wall UnitEM Evaporator Module FB - Free Blow Unit FL Floor Mounted RW Rear Wall Mounted RM Rear Mount
T--311 1-7 1.7 CONDENSERS Condensers are normally located on the outside of the vehicle. Their primary function is to reject heat absorbed by the refrigerant from the passenger compartment to the outside air. Condensers are normally located on thevehicle skirt or on the roof. If space in the vehicle skirt is a problem, two (2) CM-2’s or two (2) CM-3’s can be stacked on each other with a kit available from Carrier Transport Air Conditioning. Carrier Transport Air Conditioning condensers are listed in Table 1-5. Ta b l e 1 -5CONDENSERS (Used With GEN 4 And GEN 5 Series) Component Ty p eCFM (Approx)AmpsWeightBTU Heat Rejection CM-2SKT [email protected] 16@25V66 Lbs.57,000 CM-3SKT [email protected] 24@25V76 Lbs.76,000 CM-4SKT OR RF [email protected] Lbs.43,000 CM-5SKT MT600041@24V202 Lbs.162,000 CM-7RF [email protected] 12@25V87 Lbs.76,000 CM-11RF [email protected] Lbs.57,000 KR-4RF [email protected] 22@25V187 Lbs.130,000 CM-14SKT [email protected] 30@25V92 Lbs.85,000 CM-2 STKD (2 ea)SKT [email protected] Lbs.114,000 CM-3 STKD (2 ea)SKT [email protected] Lbs.152,000 LEGEND: CM - Condenser Module KR - 4 Fan Roof Mounted SKT - Skirt Mounted RF - Roof Mounted STKD - Stacked Condenser Assembly 1.8 PRE-INSTALLATION INSPECTION Immediately upon receipt of your Carrier Transport Air Conditioning system: Check the number/amount of cartons and skids/pallets against the shipping company’s “Bill of Lading” (B.O.L.). Inspect all shipping cartons for any evidence of damage in transit. If visible damage exists, indicate on “Bill of lading” and initiate a claim directly with the transporting company. All instances of visible damage or missing cartons are the responsibility of the transporting company.Unpack and check components for hidden damage. If hidden damage exists, initiate a claim directly with the transporting company. All instances of hidden damage are also the responsibility of the transporting company. Check contents of cartons against the enclosed packing lists. If any parts are missing, incomplete, or defective, call Carrier Transport Air Conditioning customer service for assistance. Before installing any evaporator assembly, spin the blower wheels by hand to insure they turn freely. It is possible they could have been knocked out of alignment during transit. This would be easy to correct before installing. Note Before attempting to install any evaporator or condenser always insure that each component will fit in the location of choice.
T--311 2-1 SECTION 2 EVAPORATORS 2.1 INTRODUCTION 2.1.1 Description Evaporators are located in the interior of the bus. Their primary function is to transfer heat contained in the passenger compartment into the refrigerant. The evaporators may be free blow mounted in the front, side or rear of the bus to blow directly into the interior or ducted to distribute the air in a planned pattern. 2.1.2 Location Before attempting to install any evaporator, always insure that the evaporator will fit in the location of choice. 2.1.3 Cap Plugs Carrier Transport Air Conditioning evaporators are leak-checked at the factory then shipped with a small charge of inert gas which keeps the coil free from moisture. The evaporator caps/plugs must not be removed until ready to use. 2.1.4 Blower Wheels Before installing any evaporator assembly, spin the blower wheels by hand to insure they turn freely. It is possible they could have been knocked out of alignment during transit. This would be easier to correct before installing. 2.1.5 Aesthetics When the installation is completed, the evaporator fittings and trim should be visually examined for completeness and looks. All trim should be flush and mounting hardware hidden from sight where possible in a manner designed to be pleasing to the customer. 2.1.6 Mounting (Front & Rear) Carrier Transport Air Conditioning recommends sufficient structure be built into the bus ceiling by the “OEM” (original equipment manufacturer) so that the bus roof will not have to be drilled through when mounting the evaporator assemblies. When and if the bus roof is drilled through to mount the evaporator, caremust be taken to ensure that the bus roof is properly sealed to prevent leaks. 2.1.7 Mounting (Side) Mounting brackets (front & rear) must always be attached to the bus roof bows. Mounting brackets to the bus ceiling skin will not provide sufficient support for the evaporator. 2.1.8 Drain Lines The drain lines must always run down hill immediately from the attachment point on the evaporator drain pans. Both drains should be run independently and in opposite directions for maximum efficiency. Drain line routing must be smooth and without kinks. Failure to properly route the drain lines may result in water back-up into the passenger compartment. 2.1.9 Ducted Systems In ducted systems, insure that all refrigerant hoses and electrical harnesses are firmly attached to the ceiling. Failure to secure these components may cause noise and vibration, inadequate air flow, or a blockage that will degrade the system cooling. 2.1.10 Bus Headliners Bus ceilings with noise abatement headliners (perforated) must be sealed with a non-porous material in the areas that will be covered by ducts prior to installation of the ducts to the ceiling. Failure to seal these areas will cause dissipation of the air and marginal cooling. 2.1.11 Mounting Hardware All Carrier Transport Air Conditioning evaporators are supplied with the proper mounting hardware. Never substitute mounting hardware without the permission of Carrier Transport Air Conditioning. Proper mounting procedures are supplied with every evaporator. Use of substitute hardware or failure to follow the installation instructions may result in structural fatigue and/or breakage.
T--311 2-2 2.2 REAR MOUNTED EVAPORATORS 2.2.1 GEN 4/5 Series EM-1, EM-2, EM-3, EM-7, EM-6, & EM-14 To install the evaporator assembly in the rear of a bus utilize the following installation procedures: 1. Un-pack the evaporator and check for any obvious damage (Refer to Sec. 1.8). 2. Check the interior of the bus/vehicle to make sure the evaporator(s) can be safely and properly installed in the selected area. Refer to Table 2-1 or Table 2-2 for evaporator dimensions. Table 2-1 GEN 4 EVAPORATORS Evaporator A(width)B(height)C(depth) EM-141.12inch9.88 inch22.25 inch EM-241.12 inch9.88 inch22.25 inch EM-359.44 inch10.75 inch22.75 inch EM-625.63 inch9.88 inch22.25 inch EM-1436.13 inch7.00 inch19.91 inch Table 2-2 GEN 5 EVAPORATORS Evaporator A(width)B(height)C(depth) EM-141.25inch7.62 inch19.13 inch EM-233.95 inch7.62 inch19.13 inch EM-359.44 inch7.62 inch19.13 inch EM-726.64 inch7.62 inch19.13 inch NOTE Except for the EM-3, all the evaporators listed in paragraph 2.2.1 can also be mounted in the front and/or on either side of the vehicle.NOTE In some cases it may be necessary to relocate the ceiling lights and/or speakers. 3. Plan refrigerant hose, drain lines, and electrical har- ness routing. Some small bus applications will allow routing inside the walls and back panel. If this is the case it is better to route your hose, drain lines, and electrical harnesses before mounting the evaporator. Refer to Section 4 for detailed instructions regarding hose, harness, and drain-line routing. 4. Locate and review installation instructions supplied with the evaporator assembly. Review piping and wir- ing diagrams for proper hose and fitting size, plus the proper wiring harness. Refer to Section 4 for detailed instructions regarding hose and harness routing. 5. For ease of installation, trace evaporator tray unto cardboard or other thin material. Refer to the installa- tion drawing for the dimension the evaporator assem- bly has to be from the back wall. Refer to Table 2-3 or Table 2-4 for these dimensions if the installation drawing is not available. Example: For an EM-1 Gen 4, this dimension is 7 Inches. Without this added di- mension the return air grill will not fit on to the evapo- rator cover. NOTE An optional rear panel is available for all the Gen 5 evaporator assemblies. This panel is used when the rear wall is curved and the evap- orator cover cannot fit flat against the rear wall. This panel can be trimmed to compensate for the ceiling curve. 6. Mark and drill all mounting holes and cut out template. SeeFigure2-1. 7. Mark center of template in order to match center of bus ceiling. See Figure 2-1. Cardboard EM-1/2 Template Drain Line LocationDrain Line Location Evaporator Mounting HolesEvaporator Mounting Holes Center of Te m p l a t e Center of Bus Ceiling Back Wall of Bus Figure 2-1 Template For EM-1 And EM-2 (GEN 4)