Home > Carrier > Air Conditioner > Carrier Em1 Manual

Carrier Em1 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Carrier Em1 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							T--311
    3-8 u. Assemble, than attach liquid lines from the remote fil-
    ter drier/sightglass assembly to the liquid line fitting
    on the feed-thru-plate and the evaporator assembly
    (See Figure 3-9).
    v. Route suction line from the evaporator and discharge
    line from the condenser per instructions provided in
    Section 4, Hose Routing.
    Note
    Route the condenser electrical harness through
    the feed-thru-plate before bolting on the con-
    denser cover.
    w.Bolt rooftop cover on to rooftop frame with hardware
    supplied.
    x. Clean condenser cover with a mild cleaning solution
    and clear all debris from the roof of the bus.
    3.5.1 Connecting to Side-Mounted Evaporators
    The preceding steps are for connecting a rooftop
    condenser assembly (CM-7 or CM-11) to a rear
    mounted evaporator assembly. The standard
    feed-thru-plate should not be used with side mounted
    evaporators. Refrigerant hoses should be routed
    between the inner and outer skins of the bus ceiling and
    roof. When connecting to side mounted evaporators
    utilize the following procedures:
    a. Follow steps a. through f. from paragraph 3.5.
    Note
    When drilling into the bus ceiling and pulling the
    refrigerant hoses, care must be taken to re-
    move as little insulation as possible from the
    bus ceiling.
    b. Mark where the feed-thru-plate would normally be lo-
    cated and cut a 4-1/2 In. hole in roof skin only.
    c. Cut 4-1/2 In hole behind the side mounted evapora-
    tor, or, if ducted system, within the duct area.
    d. Use a fish-tape or wire to pull the liquid and discharge
    lines up to the condenser assembly from inside the
    bus.Note
    Both inside and outside cut-outs must be pro-
    tected with trim-lock or similar material to help
    keep the refrigerant hoses and harness from
    chaffing.
    e. Using the optional hose cover transition (Part #
    58-62028-00) allows for a smooth transition from the
    bus skin to the condenser assembly’s liquid and dis-
    charge hook-ups, plus it is easier to seal against wa-
    ter leaks.
    f. If the optional hose cover transition (see Figure 3-12)
    is not used, the roof hole must be sealed to prevent
    water leaks.
    g. Drill a1-1/8 In. Dia. hole in the hose cover for the #8
    Quick-Click refrigerant hose. Push grommet part #
    58-00065-36 into the hole (see Figure 3-12).
    h. Drill a1-3/8 In. Dia. hole in the hose cover for the #10
    Quick-Click refrigerant hose. Push grommet part
    #AC801-327 into the hole.
    i. Drill a .81 In. Dia. hole in the hose cover for the con-
    denser harness. Push grommet part #58-00065-22
    into the hole.
    i. h.
    g.
    Figure 3-12 Hose Cover Transition Cut-Outs
    j. Push the refrigerant hoses and harness through the
    appropriate grommets in the hose cover transition.
    k. Cut hose to length and install the appropriate Quick-
    Click fittings. Connect to the condenser liquid and dis-
    charge lines.
    l. Center the hose cover transition over the cut-out in
    the bus roof. Drill 13/64 In. Dia. holes thru the hose
    cover and bus roof (7 places).
    Discharge Line
    From CompressorLiquid Line
    To Evaporator
    Roof Bow
    Roof BowMounting Channel Mounting FootHose CoverBus Roof
    Figure 3-13 Hose Cover Transition & Refrigerant Hose Connections 
    						
    							T--311
    3-9 m.Remove any debris from the hose cover and cut-out.
    Apply a bead of sealant to bottom of the hose cover.
    Rivet hose cover in place with 3/16 India. rivets.
    n. Apply sealant to all the rivet heads and all areas open
    to the interior to prevent water leakage.
    o. Route suction line from the evaporator and discharge
    line from the condenser per instructions provided in
    Section 4, Hose Routing.Note
    Connect the electrical harness that was routed
    through the hose cover transition before bolting
    on the condenser cover.
    p.Bolt rooftop cover on to rooftop frame with hardware
    supplied.
    q. Clean condenser cover with a mild cleaning solution
    and clear all debris from the roof of the bus. 
    						
    							T--311
    3-10 3.6 KR-4 ROOFTOP CONDENSER ASSEMBLY
    The Carrier Transport Air Conditioning KR-4 condenser
    is designed to be installed on the roof of the bus.
    To install the KR-4 rooftop condenser utilize the
    following installation procedures:
    a. Select a location on the bus roof where the condenser
    and/or mounting channels will span three roof bows.
    (Three (3) are preferred, but never no less than two
    (2) roof bows.
    Note
    The ideal location will be close to the evaporator
    inside the bus as well as spanning three roof
    bows.
    b. Remove the rooftop condenser from the shipping
    box. Locate the two mounting channels (if used) and
    mounting hardware.
    Note
    Certain applications will not require the mount-
    ing channels due to the contour of the bus roof.
    c. Remove rooftop cover. Install the mounting rails (if
    used) with the inclosed hardware. Refer to inclosed
    installation drawing or see Figure 3-14.
    Note
    Do not tighten the mounting channel hardware
    at this time. They will have to be removed later.
    d. Carefully place the condenser at the predetermined
    location on the bus roof. Center the condenser side-
    to-side on the bus roof. Determined if the mounting
    channels are needed at this time. See Figure 3-15
    and Figure 3-16.
    CAUTION
    This condenserassembly must contact the
    bus roof in the center. If not, damage will oc-cur. Consult factory as optional mounting
    may be required.
    e. Trace around both mounting channels or condenser
    mounting surface. See Figure 3-14.
    f. Remove mounting channels (if used) from condenser
    assembly.
    Note
    It is recommended that a drill stop be used
    when drilling through the bus roof.
    CAUTION
    All 3/16 and 1/4 In. rivet engagement thick-
    ness (grip range) must be between 0.080
    and 0.625. Using rivets other than those
    specified may allow the condenserassem-
    bly to come loose from the bus roof.
    g. If using mounting channels drill (6 places each rail)
    13/64 In. Dia. holes thru the bus roof skin using the
    mounting channel holes as a guide. Apply sealant to
    the mounting channels or bus roof. Use 3/16 In. Dia.
    steel rivets to attach mounting channels to bus roof.
    Drill 17/64 In. Dia. holes thru the mounting channels
    and bus roof bows. Apply sealant to 1/4 In. Dia. steel
    rivets and rivet to the roof bows (minimum of two riv-
    ets per roof bow). Apply sealant to the rivet heads and
    around the mounting rails to prevent water leaks. At-
    tach condenser to mounting channels using the en-
    closed hardware. Torque to 20 Ft. Lbs. Refer to en-
    closed installation drawing or see Figure 3-17.
    h. If not using mounting channels, remove the condens-
    er assembly to expose outline tracing. Apply sealant
    where the condenser will be installed. Drill 17/64 In.
    Dia. holes thru the bus roof skin (6 places each side)
    and the roof bows (minimum of two rivets per roof
    bow). Apply sealant to 1/4 In. Dia. steel rivets and riv-
    et to the roof and roof bows. Apply sealant to the rivet
    heads and around the mounting rails to prevent water
    leaks. Refer to enclosed installation drawing or see
    Figure 3-18.
    Without Mounting Channel
    With Mounting Channel
    Bus roof outer skin
    Roof bow Sealant 1/4 In. steel
    monobolt.Bolt, 3/8-16 X 1-1/4 In.
    4 per side.
    3/8 In. flat washer
    3/8 In. flat washer
    Mounting channelBus roof outer skin
    Roof bow
    Figure 3-14 Mounting Options 
    						
    							T--311
    3-11
    Roof Bow
    Center of condenser assembly center must contact bus roof
    Figure 3-15 Condenser Mounted Without Mounting Channels
    Roof Bow
    Center of condenser assembly center must contact bus roof
    Bus RoofMounting
    Channel
    Figure 3-16 Condenser Mounted With Mounting Channels
    Roof Bow Roof BowApply sealant to unit mounting surface
    and rivet heads to prevent water leaksBus Roof
    Figure 3-17 Condenser Mounted Without Mounting Channels (Side View)
    Apply sealant to unit mounting surface
    and rivet heads to prevent water leaks Roof BowBus Roof
    Mounting
    ChannelRoof Bow
    Figure 3-18 Condenser Mounted With Mounting Channels (Side View)
    3.6.1 Connecting To The Evaporators
    When connecting to the evaporator(s) utilize the
    following procedures:
    a. Condenser assembly inlet and outlet should have
    been positioned as close to the evaporator assembly
    as possible (rear or side mount).
    b. Follow procedures in paragraph 3.5 and 3.5.1.c. After connecting refrigerant lines and condenser har-
    ness(s) install the condenser cover with hardware
    provided.
    d. Clean condenser cover with a mild cleaning solution
    and clear all debris from the roof of the bus. 
    						
    							T--311
    3-12 3.7 CM-2 AND CM-3 STACKED CONDENSER AS-
    SEMBLIES
    The Carrier Transport Air Conditioning stacked
    condensers are designed to be installed in the skirt of
    the bus when there is insufficient room for a standard
    installations.
    To install Stacked Condensers utilize the following
    installation procedures:
    NOTE
    The top and bottom condenser assemblies can
    be assembled as one then installed as a com-
    plete stacked condenser assembly to the bus
    stringers.
    CAUTION
    Condenserassemblies must be properly
    installed using graded hardware. The CM-2
    condenserassembly requires at least 4
    bolts and the CM-3 requires at least 6 bolts.
    a. Install top condenser to the bus stringers (floor) as de-
    scribed in paragraph 3.3
    b. Assemble bottom condenser assembly to the top
    condenser assembly with the hardware supplied inthe appropriate (2 or 3) stacked condenser kit. Refer
    to the enclosed installation drawing or Figure 3-19
    and Figure 3-20.
    c. Place air inlet stiffener over air inlet bracket and
    loosely attach to the top condenser assembly. Repeat
    on other side of assembly.
    d. Loosely attach air outlet bracket to top condenser as-
    sembly. Repeat on other side of condenser assembly.
    e. Attach bottom condenser assembly to top assembly
    using the air inlet stiffener bracket, air outlet brackets,
    and the required hardware.
    f. Attach block-off plate to both air inlet brackets.
    g. Slide air inlet bracket and block-off plate against the
    bus skirt.
    h. Tighten all bolts.
    NOTE
    The CM-3 Condenser assembly requires the
    installation of a front bracket. See Figure 3-20.
    This bracket helps to support the bottom con-
    denser assembly.
    i. Install condenser screens (2) to the bus skirt, air inlet
    bracket and block-off plate.
    FLOOR MEMBER (STRINGER) BUS FLOOR
    CHASSIS
    RAIL
    Top Condenser
    Bottom Condenser
    Bus Skirt Air Outlet BracketAir Inlet Stiffen
    Air Inlet Bracket
    Figure 3-19 Stacked Condenser Assembly (Side View) 
    						
    							T--311
    3-13
    Front Bracket
    Block-Off Plate
    Air Inlet Bracket
    Air Inlet Bracket
    Figure 3-20 Stacked Condenser Assembly (Bus Skirt View) 
    						
    							T--311 4-1
    SECTION 4
    HOSE ROUTING
    4.1 INTRODUCTION
    All bus air conditioning systems use a network of
    refrigerant hose and fittings to connect the major
    components and carry the refrigerant gas and liquid
    through the system.
    4.1.1 Planning
    Extreme care must be used when piping a bus. Plan the
    routing of the hose prior to the installation, being careful
    to avoid sources of high heat and sharp edges. If the
    hose is routed near any heat source it should be
    protected with a heat-resistant insulation. When hoses
    are run through sheet metal or other sharp parts of the
    frame, the hose should be protected by grommets or
    clamped off in a manner that prevents chaffing. Failure
    to protect the hose may result in leaks, loss of refrigerant
    and cooling, and possible compressor damage.
    4.1.2 ServiceLoop
    When refrigerant hoses are attached to any component,
    it is highly recommended that the hoses are not pulled
    tight. Use a service loop at the compressor and extra
    hose at other locations to provide strain relief. This will
    allow the engine and road vibration to be absorbed by
    the hose and not the fittings. Failure to give strain relief
    may result in leaks or fractured fittings. Do not, however,
    leave the extra hose unsupported.
    4.1.3 Dual Systems
    When a bus has dual (2) systems, care must be taken to
    assure that the electrical system and hose routing are
    independent of each other. Connections of the piping for
    one system to the electrical signals from the other may
    result in failures to both systems through
    miscommunication with the pressure switches. Marking
    both ends of the hose assembly for identification is
    recommended.
    4.1.4 Connection Lubrication (Mineral Oil)
    System hose connections, fitting threads, and “O”
    -Rings must always be lubricated with mineral oil. Never
    use PAG or POE oils. Failure to lubricate the system
    “O”-Rings and fitting threads or the use of an improper
    lubricant may lead to torn seals, local corrosion, and
    leaks.
    4.1.5 Quick-Click Hose & Clamps
    It is highly recommended that all installations be
    performed using Carrier Transportation Air Conditioning
    “Quick-Click” hose and fittings.
    4.1.6 Barrier Type Hose & Fittings
    If “Barrier” type hose and fittings are used, it is highly
    recommended that you review Carrier Transport Air
    Conditioning Hose Crimping Procedures (Form No.
    310-011). The setup, operation and equipment
    maintenance are all critical. Failure to crimp properly will
    result in immediate leaks or leaks that become evident
    due to heat and vibration. When using beadlock type
    fittings it is critical to have initial interference between
    the hose inside diameter and fitting tube outside
    diameter. Use of a combination that has clearance
    between components will result in a much higher
    probability of leaks.4.2 EVAPORATOR HOSE ROUTING-INSIDE THE
    BUS WALL
    Always keep hose capped until ready to connect to a
    system component (see Figure 4-- 1).
    Figure 4--1 Quick-Click Hose (Capped)
    Cutaway bus hose routing will normally be routed
    through the bus floor, up the lower wall (see Figure 4-- 2),
    and then behind the upper off-set rear wall. This type of
    routing must be accomplished before the evaporator is
    mounted to the bus ceiling. On some buses the hose,
    harness, and drain lines can be routed (hidden) behind
    the lower wall also.
    Figure 4-- 2 Bus With Rear Seat Removed
    1. Determine which side of the vehicle the hoses
    should be routed; the drivers side or passenger side. 
    						
    							T--3114-2 2. Determine what route the hoses will take. Take into
    consideration there are going to be obstacles that
    the hoses may have to be routed around, such as
    seats, wheelchair lifts, windows, etc.
    3. Lay out the hose cover backs in the position that they
    eventually will be installed, and mark their position
    (see Figure 4-- 3). Mark the sides and where they
    stop at the floor and wall. This will give you an outline
    where the holes for the hoses should be placed.
    Figure 4--3 Hose Back Positioning
    Before drilling holes for the hoses in the wall or through
    the floor, make sure there are no electrical harnesses,
    braces, etc. in the path of the hose routing and hole saw.
    4. Drill a 3/16 inch pilot hole in the center of where you
    are going to drill the two 1 1/2 inch holes. This will
    show you if you can safely cut the two 1 1/2 inch
    holes in the floor.
    5. Drill two 1-1/2 inch holes side by side within the hose
    cover markings (see Figure 4--4).
    Figure 4--4 Hole-Saw Cuts in Floor
    6. Saw out any material remaining between the two
    holes, leaving an oblong hole to route the hoses
    through (see Figure 4-- 5).
    Figure 4--5 Hole-Saw Cuts Joined
    Repeat steps 1. through 6. to obtain access to the wall or
    floor, depending which one you start with.
    Figure 4-- 6 Rear Wall Access
    7. Remove any sharp edges from around the holes to
    prevent hose cutting and/or chaffing.
    After holes are drilled, sawed and deburred, you are
    ready to mount the hose cover backs using common
    fasteners such as screws or pop rivets (see Figure 4-- 7
    & Figure 4-- 8). 
    						
    							T--311 4-3
    Figure 4--7 Hose Cover Back
    Figure 4-- 8 Hose Cover Backs On Rear WallCaution
    When drilling into the vehicle wall, always
    use a drill stop to help protect against dam-
    aging any wiring that might be located be-
    hind the wall.
    Installation Hint
    To help keep hoses, harness, and drain lines
    secure and in the center of the hose covers,
    3/16 inch holes can be drilled in the hose cover
    backs. Insert Tie-Wraps through the holes be-
    fore securing the hose cover backs to the wall
    (See Figure 4-- 14).
    8. Drill a 3 inch hole in the vehicle wall in order to rout
    the hoses and harness to the evaporator area.
    9. Remove (deburr) any rough edges from around the
    cut-out.
    Using a small piece of “Trim-Loc” or similar material
    around the cut-out will help protect the hoses and
    harness from chaffing and/or cutting. (See Figure 4-- 9).
    Trim-Lock
    Figure 4-- 9 Access Hole With Trim-Lock
    10. Route the hoses and harness at this time.
    Protection
    Figure 4--10 Hoses Routed Through Access
    Before fastening to the hose cover backs, protect the
    hoses and harness wherever they go through the floor
    or wall (see Figure 4-- 10 & Figure 4-- 11) 
    						
    							T--3114-4
    Protection
    Figure 4--11 Hoses Routed Through Floor
    A piece of scrap drain hose or heater hose, split down
    the middle, can be used for protection.
    11. After hoses and harness are protected, secure them
    to the hose cover backs with the Tie-Wraps.
    Figure 4-- 12 Hoses/Harness Secured With
    Tie-Wraps To Hose Cover Back 
    						
    All Carrier manuals Comments (0)

    Related Manuals for Carrier Em1 Manual