Carrier Em1 Manual
Have a look at the manual Carrier Em1 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
T--311 3-8 u. Assemble, than attach liquid lines from the remote fil- ter drier/sightglass assembly to the liquid line fitting on the feed-thru-plate and the evaporator assembly (See Figure 3-9). v. Route suction line from the evaporator and discharge line from the condenser per instructions provided in Section 4, Hose Routing. Note Route the condenser electrical harness through the feed-thru-plate before bolting on the con- denser cover. w.Bolt rooftop cover on to rooftop frame with hardware supplied. x. Clean condenser cover with a mild cleaning solution and clear all debris from the roof of the bus. 3.5.1 Connecting to Side-Mounted Evaporators The preceding steps are for connecting a rooftop condenser assembly (CM-7 or CM-11) to a rear mounted evaporator assembly. The standard feed-thru-plate should not be used with side mounted evaporators. Refrigerant hoses should be routed between the inner and outer skins of the bus ceiling and roof. When connecting to side mounted evaporators utilize the following procedures: a. Follow steps a. through f. from paragraph 3.5. Note When drilling into the bus ceiling and pulling the refrigerant hoses, care must be taken to re- move as little insulation as possible from the bus ceiling. b. Mark where the feed-thru-plate would normally be lo- cated and cut a 4-1/2 In. hole in roof skin only. c. Cut 4-1/2 In hole behind the side mounted evapora- tor, or, if ducted system, within the duct area. d. Use a fish-tape or wire to pull the liquid and discharge lines up to the condenser assembly from inside the bus.Note Both inside and outside cut-outs must be pro- tected with trim-lock or similar material to help keep the refrigerant hoses and harness from chaffing. e. Using the optional hose cover transition (Part # 58-62028-00) allows for a smooth transition from the bus skin to the condenser assembly’s liquid and dis- charge hook-ups, plus it is easier to seal against wa- ter leaks. f. If the optional hose cover transition (see Figure 3-12) is not used, the roof hole must be sealed to prevent water leaks. g. Drill a1-1/8 In. Dia. hole in the hose cover for the #8 Quick-Click refrigerant hose. Push grommet part # 58-00065-36 into the hole (see Figure 3-12). h. Drill a1-3/8 In. Dia. hole in the hose cover for the #10 Quick-Click refrigerant hose. Push grommet part #AC801-327 into the hole. i. Drill a .81 In. Dia. hole in the hose cover for the con- denser harness. Push grommet part #58-00065-22 into the hole. i. h. g. Figure 3-12 Hose Cover Transition Cut-Outs j. Push the refrigerant hoses and harness through the appropriate grommets in the hose cover transition. k. Cut hose to length and install the appropriate Quick- Click fittings. Connect to the condenser liquid and dis- charge lines. l. Center the hose cover transition over the cut-out in the bus roof. Drill 13/64 In. Dia. holes thru the hose cover and bus roof (7 places). Discharge Line From CompressorLiquid Line To Evaporator Roof Bow Roof BowMounting Channel Mounting FootHose CoverBus Roof Figure 3-13 Hose Cover Transition & Refrigerant Hose Connections
T--311 3-9 m.Remove any debris from the hose cover and cut-out. Apply a bead of sealant to bottom of the hose cover. Rivet hose cover in place with 3/16 India. rivets. n. Apply sealant to all the rivet heads and all areas open to the interior to prevent water leakage. o. Route suction line from the evaporator and discharge line from the condenser per instructions provided in Section 4, Hose Routing.Note Connect the electrical harness that was routed through the hose cover transition before bolting on the condenser cover. p.Bolt rooftop cover on to rooftop frame with hardware supplied. q. Clean condenser cover with a mild cleaning solution and clear all debris from the roof of the bus.
T--311 3-10 3.6 KR-4 ROOFTOP CONDENSER ASSEMBLY The Carrier Transport Air Conditioning KR-4 condenser is designed to be installed on the roof of the bus. To install the KR-4 rooftop condenser utilize the following installation procedures: a. Select a location on the bus roof where the condenser and/or mounting channels will span three roof bows. (Three (3) are preferred, but never no less than two (2) roof bows. Note The ideal location will be close to the evaporator inside the bus as well as spanning three roof bows. b. Remove the rooftop condenser from the shipping box. Locate the two mounting channels (if used) and mounting hardware. Note Certain applications will not require the mount- ing channels due to the contour of the bus roof. c. Remove rooftop cover. Install the mounting rails (if used) with the inclosed hardware. Refer to inclosed installation drawing or see Figure 3-14. Note Do not tighten the mounting channel hardware at this time. They will have to be removed later. d. Carefully place the condenser at the predetermined location on the bus roof. Center the condenser side- to-side on the bus roof. Determined if the mounting channels are needed at this time. See Figure 3-15 and Figure 3-16. CAUTION This condenserassembly must contact the bus roof in the center. If not, damage will oc-cur. Consult factory as optional mounting may be required. e. Trace around both mounting channels or condenser mounting surface. See Figure 3-14. f. Remove mounting channels (if used) from condenser assembly. Note It is recommended that a drill stop be used when drilling through the bus roof. CAUTION All 3/16 and 1/4 In. rivet engagement thick- ness (grip range) must be between 0.080 and 0.625. Using rivets other than those specified may allow the condenserassem- bly to come loose from the bus roof. g. If using mounting channels drill (6 places each rail) 13/64 In. Dia. holes thru the bus roof skin using the mounting channel holes as a guide. Apply sealant to the mounting channels or bus roof. Use 3/16 In. Dia. steel rivets to attach mounting channels to bus roof. Drill 17/64 In. Dia. holes thru the mounting channels and bus roof bows. Apply sealant to 1/4 In. Dia. steel rivets and rivet to the roof bows (minimum of two riv- ets per roof bow). Apply sealant to the rivet heads and around the mounting rails to prevent water leaks. At- tach condenser to mounting channels using the en- closed hardware. Torque to 20 Ft. Lbs. Refer to en- closed installation drawing or see Figure 3-17. h. If not using mounting channels, remove the condens- er assembly to expose outline tracing. Apply sealant where the condenser will be installed. Drill 17/64 In. Dia. holes thru the bus roof skin (6 places each side) and the roof bows (minimum of two rivets per roof bow). Apply sealant to 1/4 In. Dia. steel rivets and riv- et to the roof and roof bows. Apply sealant to the rivet heads and around the mounting rails to prevent water leaks. Refer to enclosed installation drawing or see Figure 3-18. Without Mounting Channel With Mounting Channel Bus roof outer skin Roof bow Sealant 1/4 In. steel monobolt.Bolt, 3/8-16 X 1-1/4 In. 4 per side. 3/8 In. flat washer 3/8 In. flat washer Mounting channelBus roof outer skin Roof bow Figure 3-14 Mounting Options
T--311 3-11 Roof Bow Center of condenser assembly center must contact bus roof Figure 3-15 Condenser Mounted Without Mounting Channels Roof Bow Center of condenser assembly center must contact bus roof Bus RoofMounting Channel Figure 3-16 Condenser Mounted With Mounting Channels Roof Bow Roof BowApply sealant to unit mounting surface and rivet heads to prevent water leaksBus Roof Figure 3-17 Condenser Mounted Without Mounting Channels (Side View) Apply sealant to unit mounting surface and rivet heads to prevent water leaks Roof BowBus Roof Mounting ChannelRoof Bow Figure 3-18 Condenser Mounted With Mounting Channels (Side View) 3.6.1 Connecting To The Evaporators When connecting to the evaporator(s) utilize the following procedures: a. Condenser assembly inlet and outlet should have been positioned as close to the evaporator assembly as possible (rear or side mount). b. Follow procedures in paragraph 3.5 and 3.5.1.c. After connecting refrigerant lines and condenser har- ness(s) install the condenser cover with hardware provided. d. Clean condenser cover with a mild cleaning solution and clear all debris from the roof of the bus.
T--311 3-12 3.7 CM-2 AND CM-3 STACKED CONDENSER AS- SEMBLIES The Carrier Transport Air Conditioning stacked condensers are designed to be installed in the skirt of the bus when there is insufficient room for a standard installations. To install Stacked Condensers utilize the following installation procedures: NOTE The top and bottom condenser assemblies can be assembled as one then installed as a com- plete stacked condenser assembly to the bus stringers. CAUTION Condenserassemblies must be properly installed using graded hardware. The CM-2 condenserassembly requires at least 4 bolts and the CM-3 requires at least 6 bolts. a. Install top condenser to the bus stringers (floor) as de- scribed in paragraph 3.3 b. Assemble bottom condenser assembly to the top condenser assembly with the hardware supplied inthe appropriate (2 or 3) stacked condenser kit. Refer to the enclosed installation drawing or Figure 3-19 and Figure 3-20. c. Place air inlet stiffener over air inlet bracket and loosely attach to the top condenser assembly. Repeat on other side of assembly. d. Loosely attach air outlet bracket to top condenser as- sembly. Repeat on other side of condenser assembly. e. Attach bottom condenser assembly to top assembly using the air inlet stiffener bracket, air outlet brackets, and the required hardware. f. Attach block-off plate to both air inlet brackets. g. Slide air inlet bracket and block-off plate against the bus skirt. h. Tighten all bolts. NOTE The CM-3 Condenser assembly requires the installation of a front bracket. See Figure 3-20. This bracket helps to support the bottom con- denser assembly. i. Install condenser screens (2) to the bus skirt, air inlet bracket and block-off plate. FLOOR MEMBER (STRINGER) BUS FLOOR CHASSIS RAIL Top Condenser Bottom Condenser Bus Skirt Air Outlet BracketAir Inlet Stiffen Air Inlet Bracket Figure 3-19 Stacked Condenser Assembly (Side View)
T--311 3-13 Front Bracket Block-Off Plate Air Inlet Bracket Air Inlet Bracket Figure 3-20 Stacked Condenser Assembly (Bus Skirt View)
T--311 4-1 SECTION 4 HOSE ROUTING 4.1 INTRODUCTION All bus air conditioning systems use a network of refrigerant hose and fittings to connect the major components and carry the refrigerant gas and liquid through the system. 4.1.1 Planning Extreme care must be used when piping a bus. Plan the routing of the hose prior to the installation, being careful to avoid sources of high heat and sharp edges. If the hose is routed near any heat source it should be protected with a heat-resistant insulation. When hoses are run through sheet metal or other sharp parts of the frame, the hose should be protected by grommets or clamped off in a manner that prevents chaffing. Failure to protect the hose may result in leaks, loss of refrigerant and cooling, and possible compressor damage. 4.1.2 ServiceLoop When refrigerant hoses are attached to any component, it is highly recommended that the hoses are not pulled tight. Use a service loop at the compressor and extra hose at other locations to provide strain relief. This will allow the engine and road vibration to be absorbed by the hose and not the fittings. Failure to give strain relief may result in leaks or fractured fittings. Do not, however, leave the extra hose unsupported. 4.1.3 Dual Systems When a bus has dual (2) systems, care must be taken to assure that the electrical system and hose routing are independent of each other. Connections of the piping for one system to the electrical signals from the other may result in failures to both systems through miscommunication with the pressure switches. Marking both ends of the hose assembly for identification is recommended. 4.1.4 Connection Lubrication (Mineral Oil) System hose connections, fitting threads, and “O” -Rings must always be lubricated with mineral oil. Never use PAG or POE oils. Failure to lubricate the system “O”-Rings and fitting threads or the use of an improper lubricant may lead to torn seals, local corrosion, and leaks. 4.1.5 Quick-Click Hose & Clamps It is highly recommended that all installations be performed using Carrier Transportation Air Conditioning “Quick-Click” hose and fittings. 4.1.6 Barrier Type Hose & Fittings If “Barrier” type hose and fittings are used, it is highly recommended that you review Carrier Transport Air Conditioning Hose Crimping Procedures (Form No. 310-011). The setup, operation and equipment maintenance are all critical. Failure to crimp properly will result in immediate leaks or leaks that become evident due to heat and vibration. When using beadlock type fittings it is critical to have initial interference between the hose inside diameter and fitting tube outside diameter. Use of a combination that has clearance between components will result in a much higher probability of leaks.4.2 EVAPORATOR HOSE ROUTING-INSIDE THE BUS WALL Always keep hose capped until ready to connect to a system component (see Figure 4-- 1). Figure 4--1 Quick-Click Hose (Capped) Cutaway bus hose routing will normally be routed through the bus floor, up the lower wall (see Figure 4-- 2), and then behind the upper off-set rear wall. This type of routing must be accomplished before the evaporator is mounted to the bus ceiling. On some buses the hose, harness, and drain lines can be routed (hidden) behind the lower wall also. Figure 4-- 2 Bus With Rear Seat Removed 1. Determine which side of the vehicle the hoses should be routed; the drivers side or passenger side.
T--3114-2 2. Determine what route the hoses will take. Take into consideration there are going to be obstacles that the hoses may have to be routed around, such as seats, wheelchair lifts, windows, etc. 3. Lay out the hose cover backs in the position that they eventually will be installed, and mark their position (see Figure 4-- 3). Mark the sides and where they stop at the floor and wall. This will give you an outline where the holes for the hoses should be placed. Figure 4--3 Hose Back Positioning Before drilling holes for the hoses in the wall or through the floor, make sure there are no electrical harnesses, braces, etc. in the path of the hose routing and hole saw. 4. Drill a 3/16 inch pilot hole in the center of where you are going to drill the two 1 1/2 inch holes. This will show you if you can safely cut the two 1 1/2 inch holes in the floor. 5. Drill two 1-1/2 inch holes side by side within the hose cover markings (see Figure 4--4). Figure 4--4 Hole-Saw Cuts in Floor 6. Saw out any material remaining between the two holes, leaving an oblong hole to route the hoses through (see Figure 4-- 5). Figure 4--5 Hole-Saw Cuts Joined Repeat steps 1. through 6. to obtain access to the wall or floor, depending which one you start with. Figure 4-- 6 Rear Wall Access 7. Remove any sharp edges from around the holes to prevent hose cutting and/or chaffing. After holes are drilled, sawed and deburred, you are ready to mount the hose cover backs using common fasteners such as screws or pop rivets (see Figure 4-- 7 & Figure 4-- 8).
T--311 4-3 Figure 4--7 Hose Cover Back Figure 4-- 8 Hose Cover Backs On Rear WallCaution When drilling into the vehicle wall, always use a drill stop to help protect against dam- aging any wiring that might be located be- hind the wall. Installation Hint To help keep hoses, harness, and drain lines secure and in the center of the hose covers, 3/16 inch holes can be drilled in the hose cover backs. Insert Tie-Wraps through the holes be- fore securing the hose cover backs to the wall (See Figure 4-- 14). 8. Drill a 3 inch hole in the vehicle wall in order to rout the hoses and harness to the evaporator area. 9. Remove (deburr) any rough edges from around the cut-out. Using a small piece of “Trim-Loc” or similar material around the cut-out will help protect the hoses and harness from chaffing and/or cutting. (See Figure 4-- 9). Trim-Lock Figure 4-- 9 Access Hole With Trim-Lock 10. Route the hoses and harness at this time. Protection Figure 4--10 Hoses Routed Through Access Before fastening to the hose cover backs, protect the hoses and harness wherever they go through the floor or wall (see Figure 4-- 10 & Figure 4-- 11)
T--3114-4 Protection Figure 4--11 Hoses Routed Through Floor A piece of scrap drain hose or heater hose, split down the middle, can be used for protection. 11. After hoses and harness are protected, secure them to the hose cover backs with the Tie-Wraps. Figure 4-- 12 Hoses/Harness Secured With Tie-Wraps To Hose Cover Back